Jump to Navigation

Schneider Electric TK-1xxx Series, TK-5xxx Series Single Setpoint Room Thermostats

Single Setpoint Room Thermostats
TK-1xxx Series, TK-5xxx Series

For proportional temperature control of pneumatic valves and damper actuators to maintain room air temperatures in heating, ventilating, and air conditioning systems.

• Branch-line to sensing-element pneumatic feedback for linear, stable operation.
• Plastic cover supplied with exposed setpoint and thermometer.
• Cover inserts included for: - Exposed setpoint only. - Blank face plate with logo.

Select a link under the "item" tab below to order.

Cat #Type ThermostatControl Actionb Supply PressureDial Markings
TK-1001Two pipeDirect Acting55 to 85°F
TK-1001-116Two pipeDirect Acting13 to 29°C
TK-1001-600Two pipeDirect Acting55 to 85°F
TK-1101Two pipeReverse Acting55 to 85°F
TK-1101-116Two pipeReverse Acting13 to 29°C
TK-1101-600Two pipeReverse Acting55 to 85°F
TK-1201Two pipe15 psig Reverse Acting 20 psig Direct A55 to 85°F
TK-1281Two pipe20 psig ReverseActing 15 psig Direct Acting55 to 85°F
TK-1301Two pipe with manual overrideDirect Acting 15 psig day − 20 psig nig55 to 85°F
TK-1301-116Two pipe with manual overrideDirect Acting 15 psig day − 20 psig nig13 to 29°C
TK-1381Two pipe with manual overrideReverse Acting 15 psig day − 20 psig night55 to 85°F
TK-1601cdThree pipe with manual overrideDirect Acting 15 psig day − 20 psig night55 to 85°F
TK-5001Single PipeDirect Acting55 to 85°F
TK-5001-116Single PipeDirect Acting13 to 29°C
TK-5101Single PipeReverse Acting55 to 85°F
TK-5101-116Single PipeReverse Acting13 to 29°C
Thermostat: Proportional type.
Sensing element: Bimetal.
Night setback: To 20°F (11°C) below day setpoint for Day/Night heating models.
Night setup: To 20°F (11°C) above day setpoint for Day/Night cooling models.
Control dial range: Refer to Model Chart.
Throttling Range: Adjustable 2 to 10°F/10 psi, factory set at 4°F/10 psi.
Output air signal: 0.5 psig to supply air pressure -0.5 psig.
Action: Refer to Model Chart.
Ambient limits: Shipping -40 to 150°F (-40 to 65°C). 0 to 98% RH, non-condensing.
Operating 40 to 150°F (4 to 65°C). 10 to 98% RH, non-condensing.
Supply air pressure: Clean, oil free, dry air required (refer to EN-123).
Nominal: Refer to Model Chart.
Maximum: 30 psig (207 kPa).
Air connections: Main (black) 5/32 in. dia. spring reinforced plastic tubing.
Branch (white) 5/32 in. dia. spring reinforced plastic tubing.
Air consumption for sizing air compressor:
TK-1001, 1101, 12x1, 13x1 13.8 scim (3.8 mL/s).
Air capacity for sizing air mains: TK-1001, 1101, 12x1, 13x1 16 scim (4.4 mL/s).
TK-16x1 32 scim (8.8 mL/s).
Cover: Beige plastic.
Mounting: Upright position on wall.
Dimensions: 4-3/8 H x 2-3/4 W x 1-5/8 D in. (111 x 70 x 43 mm).