Schneider Electric AKS-1100 Receiver Controller Setpoint Adjuster and Scale Plates


Setpoint adjuster and scale plates used to provide remote setpoint adjustment of RKS-2001, RKS- 4002, and RKSR-4000 receiver-controllers. May also be used to manually pilot pneumatic relays.
• Allows the setpoint of a pneumatic receiver-controller to be raised or lowered from a location up to 1000 ft. (305 m) from the receiver-controller.
• Series available to work with various transmitter ranges.
• A receiver gauge, mounted near the setpoint adjuster shows the actual result of remotely adjusting the receivercontroller’s setpoint.
Select a link under the "item" tab below to order.
Cat # | Descriptions |
AKS-1100 | Remote setpoint adjuster. |
Construction: | Aluminum housing, precision flapper-nozzle assembly. | |
Output: | Linear 3 to 15 psig (21 to 102 kPa). | |
Air pressure: | Clean, oil free, dry air required (reference EN-123). | |
Maximum | 30 psig (207 kPa). | |
Ambient limits: | Shipping temperatures | -40 to 150°F (-40 to 65°C). |
Operating temperatures | 40 to 120°F (4 to 49°C). | |
Humidity | 5 to 95% RH, non-condensing. | |
Air connection: | Barbed connection for 1/4 in. O.D. plastic tubing. | |
Air consumption for sizing air compressor: |
41.5 scim (11.3 mL/s). | |
Air capacity for sizing air mains: | 48 scim (13.1 mL/s). | |
Mounting: | Panel or wall box. Panel requires 5/8 in. (16 mm) hole for mounting the remote setpoint adjuster. | |
Panel space required: | 2-3/8 H x 2-1/4 W x 2-1/2 D in. (60 x 57 x 63 mm). | |
AKS-11xx scale plates (must be ordered separately): |
White letters on black background, keyed for proper locating on setpoint adjuster. |