Precision Digital PD6200 Analog Input Dual-Line Flow Rate/Totalizers


The PD6200 and PD6300 ProVu meters are 1/8 DIN flow rate/totalizers specifically designed for displaying flow rate and total from flow meters with analog or pulse outputs. These flow rate/totalizers are particularly well-suited for flow applications because they can display flow rate and flow total at the same time, provide power to drive the flow meter, and display flow total, flow grand total, or non-resettable flow total on up to nine digits.
• 0-20 mA, 4-20 mA, 0-5 V, 1-5 V, and ±10 V Inputs
• Isolated 24 VDC @ 200 mA Transmitter Power Supply
• Open Channel Flow with Programmable Exponent
• Square Root Extraction
• 32-Point Linearization
COMMON METER FEATURES
• NEMA 4X, IP65 Front
• Universal 85-265 VAC or 12/24 VDC Input Power
• Large Dual-Line 6-Digit Display, 0.60 & 0.46
• Programmable Displays & Function Keys
• Sunlight Readable Display
• 2 or 4 Relays + Isolated 4-20 mA Output Options
• External 4-Relay & Digital I/O Expansion Modules
• RS-232, RS-422/485 Serial Communication Options
• -40 to 65°C Operating Temperature Range
Select a link under the "item" tab below to order.
Cat # | Descriptions |
PD6200-6R0 | ProVu Analog Input Dual-line Flow Rate/Totalizer; No Options; Powered from 85-265 VAC |
PD6200-6R2 | ProVu Analog Input Dual-line Flow Rate/Totalizer; 2 Relays; Powered from 85- 265 VAC |
PD6200-6R3 | ProVu Analog Input Dual-line Flow Rate/Totalizer; 4-20 mA Output; Powered from 85-265 VAC |
PD6200-6R4 | ProVu Analog Input Dual-line Flow Rate/Totalizer; 4 Relays; Powered from 85- 265 VAC |
PD6200-6R5 | ProVu Analog Input Dual-line Flow Rate/Totalizer; 2 Relays + 4-20 mA Output; Powered from 85-265 VAC |
PD6200-6R7 | ProVu Analog Input Dual-line Flow Rate/Totalizer; 4 Relays + 4-20 mA Output ; Powered from 85-265 VAC |
PD6200-7R0 | ProVu Analog Input Dual-line Flow Rate/Totalizer; No Options; Powered from 12-24 VDC |
PD6200-7R2 | ProVu Analog Input Dual-line Flow Rate/Totalizer; 2 Relays; Powered from 12- 24 VDC |
PD6200-7R3 | ProVu Analog Input Dual-line Flow Rate/Totalizer; 4-20 mA Output; Powered from 12-24 VDC |
PD6200-7R4 | ProVu Analog Input Dual-line Flow Rate/Totalizer; 4 Relays; Powered from 12- 24 VDC |
PD6200-7R5 | ProVu Analog Input Dual-line Flow Rate/Totalizer; 2 Relays + 4-20 mA Output; Powered from 12-24 VDC |
PD6200-7R7 | ProVu Analog Input Dual-line Flow Rate/Totalizer; 4 Relays + 4-20 mA Output; Powered from 12-24 VDC |
General | |||
Display: | Main display: 0.60" (15 mm) high, second display: 0.46" (12 mm) high. Both displays are 6 digits (-99999 to 999999), red LEDs with leading zero blanking | ||
Display Intensity: | Eight user selectable intensity levels | ||
Overrange: | Display flashes 999999 | ||
Underrange: | Display flashes -99999 | ||
Front Panel: | NEMA 4X, IP65 | ||
Programming Methods: | Four front panel buttons, digital inputs, PC and multi-point linearization utility, or cloning using Copy function | ||
Recalibration: | All ranges are calibrated at the factory. Recalibration is recommended at least every 12 months | ||
Max/Min Display: | Max (Peak) / min (Valley) readings reached by the process are stored until reset by the user or until power to the meter is turned off | ||
Password: | Three programmable passwords restrict modification of programmed settings and two prevent resetting the totals. Pass 1: Allows use of the F1–F3 function keys. Pass 2: Allows use of the F1–F3 function keys and changing the set/reset points. Pass 3: Restricts all programming and F1–F3 keys. Total: Prevents resetting the total manually. Gtotal: Prevents resetting the grand total manually | ||
Non-Volatile Memory: | All programmed settings are stored in non-volatile memory for a minimum of ten years if power is lost | ||
Power Options: | 85-265 VAC 50/60 Hz, 90-265 VDC 20 W max, or jumper selectable 12/24 VDC ±10%, 15 W max. | ||
Fuse: | Required external fuse: UL Recognized, 5 A max, slow blow; up to 6 meters may share one 5 A fuse | ||
Isolated Transmitter Power Supply: | Terminals P+ & P-: 24 VDC ± 5% @ 200 mA max (standard), (12/24 VDC powered models rated @ 100 mA max). 5 or 10 VDC @ 50 mA max, selectable with internal jumper J4 | ||
Isolation: | 4 kV input/output-to-power line. 500 V input-to-output or output-to-P+ supply | ||
Environmental: | Operating temperature range: -40 to 65°C. Storage temperature range: -40 to 85°C. Relative humidity: 0 to 90% non-condensing | ||
Connections: | Removable screw terminal blocks accept 12 to 22 AWG wire, RJ45 for external relays, digital I/O, and serial communication adapters | ||
Enclosure: | 1/8 DIN, high impact plastic, UL 94V-0, color: black | ||
Mounting: | 1/8 DIN panel cutout required: 3.622" x 1.772"(92 mm x 45 mm). Two panel mounting bracket assemblies are provided | ||
Tightening Torque: | Screw terminal connectors: 5 lb-in (0.56 Nm) | ||
Overall Dimensions: | 4.68" x 2.45" x 5.64" (119 mm x 62 mm x 143 mm) (W x H x D) | ||
Weight: | 9.5 oz (269 g) | ||
UL File Number: | UL & c-UL Listed. E160849; 508 Industrial Control Equipment | ||
Warranty: | 3 years parts & labor |