Precision Digital PD662 3½+ Digit NEMA 4X Loop-Powered Meter


The PD662 Hatchet NEMA 4X loop-powered meter is perfect for applications where a simple, inexpensive display is required and AC power is not available. That’s because the PD662 derives all its power from the 4-20 mA loop. The PD662 is scaled using four push buttons and can be done without applying an actual calibration signal. The PD662’s display will read up to 2,999; we call this 3½+ digits! The loop-powered backlighting option lets you see the display under any lighting condition and is powered completely from the 4-20 mA loop. This means there is no need for additional wiring and never any batteries to change. The PD662 Hatchet is housed in rugged NEMA 4X enclosure and is provided with one ½ conduit hole. The PD662 is available with an optional 24 VDC powered heater that allows the PD662 to operate in temperatures as low as -55°C.
QUICKSTAR
The PD662 is designed to be easily wired into your current loop and quickly programmed.
• 4-20 mA Input
• 3½+ Digit 0.6 Display
• Easy Four-Button Programming
• Programmable Noise Filter
• Max/Min Display
• Password Protection
• HART Protocol Transparent
• Loop-Powered Backlight Option
• 1.7 Volt Drop
• NEMA 4X Enclosure
• Operates from -40 to 85°C (-55 to 85°C with Heater Option)
Select a link under the "item" tab below to order.
Cat # | Descriptions |
PD662-0L0-00 | NEMA 4X Loop-Powered Meter |
PD662-0K0-00 | NEMA 4X Loop-Powered Meter with Backlight |
PD662-0L0-A0 | NEMA 4X Loop-Powered Meter with Heater |
PD662-0K0-A0 | NEMA 4X Loop-Powered Meter with Backlight + Heater |
General | |||
Display: | 0.6" (15.24 mm) LCD, 3½+ digits; -1999 to 2999 | ||
Display Update Rate: | 2 Updates/Second | ||
Over-Range: | Display Flashes 2999 | ||
Under-Range: | Display Flashes -1999 | ||
Programming Method: | 4 Front Panel Pushbuttons | ||
Noise Filter: | Programmable HI, LOW, or OFF | ||
Recalibration: | Recalibration is recommended at least every 12 months. | ||
Max/Min Display: | Max/Min readings reached by the process are stored until reset by the user or until power to the meter is turned off. | ||
Password: | Programmable password restricts modification of programmed settings. | ||
Non-Volatile Memory: | All programmed settings are stored in non-volatile memory for a minimum of ten years if power is lost. | ||
Normal Mode Rejection: | 64 dB at 50/60 Hz | ||
Operating Temperature: | -40 to 85°C (-55 to 85°C with heater option) | ||
Storage Temperature: | -40 to 85°C | ||
Relative Humidity: | 0 to 90% non-condensing | ||
Connections: | Removable screw terminals accept 12 to 22 AWG | ||
Tightening Torque: | Screw terminal connectors: 4.5 lb-in (0.5 Nm) | ||
Enclosure: | Impact-resistant polyester plastic, body color gray, clear cover with blue faceplate; NEMA 4X, IP66; ½" conduit hole provided at base | ||
Weight: | 9.3 oz (264 g) | ||
Overall Dimensions: | 3.15" x 4.33" x 2.76" (80 mm x 110 mm x 70 mm) (W x H x D) | ||
Warranty: | 3 years parts & labor | ||
Input | |||
Input: | 4-20 mA | ||
Accuracy: | ±1 count | ||
Temperature Drift: | 50 PPM/°C from -40 to 85°C ambient | ||
Decimal Point: | User selectable decimal point | ||
Minimum Span: | Input 1 & Input 2: 0.40 mA | ||
Maximum Voltage Drop: | 1.7 VDC @ 20 mA; 4.9 VDC @ 20 mA with backlight option. | ||
Equivalent Resistance: | 85 Ω @ 20 mA without backlight; 245 Ω @ 20 mA with backlight | ||
Loop-Powered Backlight Option: | Factory installed only with field wiring option. Powered directly from the 4-20 mA loop, no batteries required. The display brightness will increase as the input signal current increases. | ||
Heater Option | |||
Power: | 24 VDC, 11 W Maximum. The heater unit only draws power when required to keep the meter at approximately -20°C. | ||
Ambient Temperature Range: | Allows PD662 to operate at -55°C to 85°C. | ||
Temperature Cutoff: | Internal 104°C thermal cutoff for over temperature protection. |