Jump to Navigation

KMC Controls CSC-2000 Series Reset Volume Controllers

Reset Volume Controllers
CSC-2000 Series

The pneumatic CSC-2000 series are designed for use on VAV terminal units in HVAC systems. These are ifferential-pressure, submaster controllers with adjustable minimum and maximum airflow settings. A master controller, typically a room thermostat, resets the CSC velocity setpoint.

Direct acting models are for normally open VAV terminal units. Reverse acting are for normal closed VAV terminal units.

Each is equipped with separate adjustment knobs for minimum and maximum airflow settings. All models should be calibrated with the use of airflow measuring equipment.

• Each is equipped with separate adjustment knobs for minimum and maximum airflow settings.
• NOTE: The CSC-2007/2017/2008/2018 models with 14.4 scim air consumption are primarily for replacing Trane, Carnes, and other controllers with small restrictors

Select a link under the "item" tab below to order.

Cat #0–10 Molded Plastic DialAir ConsumptionReset Pressure BandFor HeatingMin.For CoolingMax.
CSC-2001Yes14.4 scim @ 20 psig8 ±0.5 to 13 psigReverse Acting0 to 1.0” wcDirect ActingMin. plus 1.0” wc
CSC-2003No — has paper label instead14.4 scim @ 20 psig8 ±0.5 to 13 psigReverse Acting0 to 1.0” wcDirect ActingMin. plus 1.0” wc
CSC-2007No — has paper label instead11.5 scim @ 20 psig8 ±0.5 to 13 psigReverse Acting0 to 1.0” wcDirect ActingMin. plus 1.0” wc
CSC-2009No — has paper label instead14.4 scim @ 20 psig8 ±0.5 to 13 psigReverse Acting0 to 2.0” wcDirect ActingMin. plus 2.0” wc
CSC-2017No — has paper label instead11.5 scim @ 20 psig8 ±0.5 to 13 psigReverse Acting0 to 2.0” wcDirect ActingMin. plus 2.0” wc
CSC-2002Yes14.4 scim @ 20 psig3 ±0.5 to 8 psigDirect Acting0 to Max.Reverse Acting0 to 1.0” wc
CSC-2004No — has paper label instead14.4 scim @ 20 psig3 ±0.5 to 8 psigDirect Acting0 to Max.Reverse Acting0 to 1.0” wc
CSC-2008No — has paper label instead11.5 scim @ 20 psig3 ±0.5 to 8 psigDirect Acting0 to Max.Reverse Acting0 to 1.0” wc
CSC-2010No — has paper label instead14.4 scim @ 20 psig3 ±0.5 to 8 psigDirect Acting0 to Max.Reverse Acting0 to 2.0” wc
CSC-2018No — has paper label instead11.5 scim @ 20 psig3 ±0.5 to 8 psigDirect Acting0 to Max.Reverse Acting0 to 2.0” wc
Output Sensitivity:
0–1" Range Units: 5 psig/.02" wc (35 kPA/5 Pa)
5 psig/.02" wc (35 kPA/5 Pa): 5 psig/.04" wc (35 kPA/10 Pa)
Main Pressure Air: 15 to 30 psig (103 to 207 kPa)
Maximum Signal Pressure : 6" wc (1493 Pa) applied to either port (X or Y)
Material:
Temperature Limits: 40 to 120° F (4 to 49° C)
Shipping: –40 to 140° F (–40 to 60° C)