Johnson Controls CD-Pxx-00-0 Series Duct Mount CO₂ Transmitter


Johnson Controls offers a complete line of carbon dioxide (CO₂) modules that measure and transmit CO₂ levels ranging from 0 to 2,000 parts per million [ppm]. This compact device offers a choice o f 0 to 10 V or 0 to 20 mA output signals and features an optional relay output with or without a digital display. Johnson Controls CO₂ transmitters are easy to install and to operate.
The silicon-based CARBOCAP® sensor delivers high accuracy and long-term measurement stability (±100 ppm) over a five year period without calibration. The diffusion aspirated, single-beam, dual-wave length sensor structure is remarkably simple. It consists of an infrared (IR) source, a sample cell, an IR detector, and a tunable interference filter that enables measurements at two wavelengths. Reference measurements made using a tunable interference filter eliminate the typical weakness of dual-beam sensors and permits shifting the optical pass band electronically. This innovative design provides precise reference readings that eliminate the typically broad deviation expected from a traditional CO₂ sensor.
• stable infrared reference compensates for light-source drift
• CO₂ transmitters with DCV strategies offer a potential for 10 to 70% energy savings
• single-beam, dual-wavelength design provides superior performance compared to other technologies
• silicon, micro-machined construction provides reliable CO₂ measurement in harsh environments
Select a link under the "item" tab below to order.
Cat # | Descriptions |
CD-P00-00-0 | CD-P00-00-0 CD-PR0-00-0 |
CD-PR0-00-0 | Duct Mount CO2 Transmitter with Relay |
CD-Pxx-00-0 Series Duct Mount CO₂ Transmitter | ||
Measuring Range | 0 to 2,000 ppm CO₂ | |
Accuracy at 77°F (25°C) | <±(30 ppm CO₂ + 2.0% of reading) (includes manufacturing deviation and drift). All accuracy specifications reflect testing the transmitters using high-grade, certified gases. Transmitters are intended for an altitude range of 0 to 1,969 ft (0 to 600m) above sea level without compensation. To compensate for higher altitudes, see the Johnson Controls installation instructions for this device. | |
Non-Linearity | <0.5% of Full Scale | |
Temperature Dependence of Output | <0.056% of Full Scale/F° (<0.1% of Full Scale/C°) | |
Long-Term Stability | <±5.0% of Full Scale/5 Years | |
Response Time (0 to 63%) | 1 Minute | |
Operating Temperature Range | 23 to 113°F (-5 to 45°C) | |
Storage Temperature Range | -4 to 158°F (-20 to 70°C) | |
Humidity Range | 0 to 85% RH (non-condensing) | |
Transmitter Output Signal | CO₂ : Jumper Selectable: 0 to 20 mA or 4 to 20 mA or 0 to 10 VDC (Default); Maximum Output Current: 25 mA; Maximum Output Voltage: 12.5 V | |
Relay Output (Optional): Maximum 30 V, 0.5 A, Class 2 | ||
Recommended External Load | Current Output: Maximum 500 ohms Load Resistance Voltage Output: Minimum 1,000 ohms Load Resistance | |
Power Supply Range | 20 to 30 VAC (18 to 30 VDC), Class 2 | |
Power Consumption | <2.5 W Average, 4.1 VA | |
Warm-up Time | <5 Minutes | |
Air Flow Range | 0 to 7,500 ft/minute (0 to 2,286 m/minute) | |
Duct Probe Material | Duct probe meets plenum rating requirements of UL 1995, Heating and Cooling Equipment. | |
Housing Material | ABS Plastic | |
Dimensions (H x W x D) | 3-1/8 x 3-3/16 x 8 in. (80 x 81 x 204 mm) | |
Agency Listings | UL Listed, CCN XAPX (US) and XAPX7 (Canada); EMC Directive (CE Mark), 89/336/EEC; FCC and DOC Compliant |