Johnson Controls CD-Pxx-00-0 Series Duct Mount CO₂ Transmitter

Duct Mount CO₂ Transmitter
CD-Pxx-00-0 Series

Johnson Controls offers a complete line of carbon dioxide (CO₂) modules that measure and transmit CO₂ levels ranging from 0 to 2,000 parts per million [ppm]. This compact device offers a choice o f 0 to 10 V or 0 to 20 mA output signals and features an optional relay output with or without a digital display. Johnson Controls CO₂ transmitters are easy to install and to operate.

The silicon-based CARBOCAP® sensor delivers high accuracy and long-term measurement stability (±100 ppm) over a five year period without calibration. The diffusion aspirated, single-beam, dual-wave length sensor structure is remarkably simple. It consists of an infrared (IR) source, a sample cell, an IR detector, and a tunable interference filter that enables measurements at two wavelengths. Reference measurements made using a tunable interference filter eliminate the typical weakness of dual-beam sensors and permits shifting the optical pass band electronically. This innovative design provides precise reference readings that eliminate the typically broad deviation expected from a traditional CO₂ sensor.

• stable infrared reference compensates for light-source drift
• CO₂ transmitters with DCV strategies offer a potential for 10 to 70% energy savings
• single-beam, dual-wavelength design provides superior performance compared to other technologies
• silicon, micro-machined construction provides reliable CO₂ measurement in harsh environments

Select a link under the "item" tab below to order.

Cat #Descriptions
CD-P00-00-0CD-P00-00-0 CD-PR0-00-0
CD-PR0-00-0Duct Mount CO2 Transmitter with Relay
CD-Pxx-00-0 Series Duct Mount CO₂ Transmitter
Measuring Range 0 to 2,000 ppm CO₂
Accuracy at 77°F (25°C) <±(30 ppm CO₂ + 2.0% of reading) (includes manufacturing deviation and drift). All accuracy specifications reflect testing the transmitters using high-grade, certified gases. Transmitters are intended for an altitude range of 0 to 1,969 ft (0 to 600m) above sea level without compensation. To compensate for higher altitudes, see the Johnson Controls installation instructions for this device.
Non-Linearity <0.5% of Full Scale
Temperature Dependence of Output <0.056% of Full Scale/F° (<0.1% of Full Scale/C°)
Long-Term Stability <±5.0% of Full Scale/5 Years
Response Time (0 to 63%) 1 Minute
Operating Temperature Range 23 to 113°F (-5 to 45°C)
Storage Temperature Range -4 to 158°F (-20 to 70°C)
Humidity Range 0 to 85% RH (non-condensing)
Transmitter Output Signal CO₂ : Jumper Selectable: 0 to 20 mA or 4 to 20 mA or 0 to 10 VDC (Default); Maximum Output Current: 25 mA; Maximum Output Voltage: 12.5 V
Relay Output (Optional): Maximum 30 V, 0.5 A, Class 2
Recommended External Load Current Output: Maximum 500 ohms Load Resistance Voltage Output: Minimum 1,000 ohms Load Resistance
Power Supply Range 20 to 30 VAC (18 to 30 VDC), Class 2
Power Consumption <2.5 W Average, 4.1 VA
Warm-up Time <5 Minutes
Air Flow Range 0 to 7,500 ft/minute (0 to 2,286 m/minute)
Duct Probe Material Duct probe meets plenum rating requirements of UL 1995, Heating and Cooling Equipment.
Housing Material ABS Plastic
Dimensions (H x W x D) 3-1/8 x 3-3/16 x 8 in. (80 x 81 x 204 mm)
Agency Listings UL Listed, CCN XAPX (US) and XAPX7 (Canada); EMC Directive (CE Mark), 89/336/EEC; FCC and DOC Compliant

The new CO transmitters are easy to install, offer a full three-year warranty, and require no maintenance or field calibration. Use them
• in stand alone mode
• in support of Demand Control Ventilation (DCV)
• with fresh air and Indoor Air Quality (IAQ) systems
• as part of any integrated Building Automation System (BAS)
• with rooftop air handling Economizer controls systems
• connected to Metasys® system or the AD-DME series