Rotronic Hygro Flex 3 Transmitters For Humidity and Temperature


The new HygroFlex3-series is the latest development in HVAC transmitters for relative humidity, temperature and dew point. Based on AirChip3000 technology, the instruments achieve a degree of accuracy not seen before.
In combination with advances in sensor technology and integration, the HygroFlex3-series provides superb precision and state-of-the-art functionality, taking humidity, temperature and dew point measurements to a whole new level of performance and reliability (< 2 % rh / 0.3 K).
High flexibility
• Two freely selectable and scalable analog outputs
• Analog outputs assignable to relative humidity, temperature or dew point
• 2-wire or 3/4-wire systems available
• Two integrated relay contacts available as options to convert the transmitters to thermostats/hygrostats
AirChip3000
• Compensates humidity and temperature over 30,000 reference points
• 2,000 data point memory
• Dew/frost point calculation
• Sensor auto-diagnostics and automatic correction
• Active alarming and information
• ASIC (Application Specific Integrated Circuit), micro-controller and EEPROM on one chip
Fast response and precision measurement
• By decoupling the Pt100 temperature sensor from the probe, thermal response is significantly improved
• Use of Pt100 1/3 Class B sensors for maximum accuracy
• Relative humidity, temperature and dew point measurement
• Outstanding accuracy and repeatability
• Hygromer® IN-1 humidity sensor
• Auto-diagnostics and automatic correction
• Freely selectable and scalable analog outputs
• Also available as hygrostat and thermostat
HF32 2-wires |
HF33 3/4-wires |
HF34 Hygro-/Thermostat |
|
Integrated sensors | Yes | ||
Humidity sensor | ROTRONIC Hygromer® IN-1 | ||
Temperature sensor | Pt100 1/3 Class B | ||
Accuracy at 23 ±5 °C | ±2.0 %rh / 0.3 K (±1.0 %rh / 0.2 K Type R) | ||
Resolution AirChip3000 | <0.02 %rh / 0.01 K | ||
Long-term stability humidity sensor | <1 %rh / year | ||
Response time τ 63 | <10 s | ||
Measurement range | -40…60 °C / 0…100 %rh | ||
Electronics operating range | -40…60 °C / 0…100 %rh (-10…60 °C with LCD) | ||
Display (option room version) (HF32S: not illuminated) |
Graphic LCD Parameters freely configurable |
||
Alarm functions (programmable) | Sensor interruption or short circuit | ||
Output signals | Freely scalable by user 0...1 V, 0...5 V, 0...10 V, 0(4)...20 mA |
||
Change in signal type | HF33 only | ||
Power supply | HF32: 10...28 VDC: 10 V + (0.02 x load) HF33: 15…40 VDC/12…28 VAC HF34: 8…40 VDC /6…28 VAC |
||
Power consumption | HF32: max 40 mA, other models < 100 mA | ||
Circuit type | HF32: 2 x 2 wires, HF33: 3/4 wires | ||
Min. / Max. load | V-signal:≥1 kΩ/V / mA signal: ≤ 500 Ω | ||
Firmware update | Possible by HW4 software | ||
Sensor diagnostics (Drift, state) | Programmable. Default: off | ||
Sensor protection | Polyethylene filter | ||
Max. wind speed | 20 m/s at probe | ||
Adjustments | Via ROTRONIC accessories Humidity: multi point; temperature: 2 points |
||
Hygro- /Thermostat | 2 Relays, HF34 only | ||
Data logging | Internal, 2000 data point memory | ||
Dewpoint /frostpoint calculation | Yes | ||
PC interface | With ROTRONIC interface cable, HW4 compatible |
||
Housing material / weight | ABS / approx. 120g | ||
Cable connections | 1 x M16x1.5, on terminals | ||
Norms | CE- compliant, 2007/108/EG | ||
Audit trail, Electronic Records | FDA CFR21 Part 11 and GAMP compliant | ||
IP protection rating & fire protection class | IP65 / Corresponds to UL94-HB |