Honeywell VersaFlow TWM 9000 Electromagnetic Flow Converter


The TWM 9000 is the only electromagnetic flow converter with diagnostics for the instrument and application. TWM 9000 is compatible with all electromagnetic flow sensors and is suitable for all applications.
• Complete Diagnostics of the application and instrument
• Quick to install and easy to operate
• Excellent long-term stability
• Optimal zero point stability independent from process properties
• One converter for all applications; helps facilitate procurement, engineering and inventory management.
• Exceeds requirements VDI / VDE/ WIB 2650 and NAMUR NE 107
• Integrated temperature and conductivity measurement
• Suitable for Custody Transfer
Model: | |
C (compact) (Integrally Mounted) | TWM 9000 C |
F (field), W (wall), R (19" rack) (Remote Mounted) | TWM 9000 F, TWM 9000 W, TWM 9000 R |
Performance: | |
Maximum measuring error | See Accuracy Curves |
Repeatability | ±0.06% to OIML R117 |
Full-scale range (see flow table) | v = 0.3...12 m/s / 1...40 ft/s |
Conductivity: | |
Min. process liquid conductivity (non-water) | As low as 1 μS/cm (see flow sensor ) |
Min. process liquid conductivity (water) | 20 μS/cm |
Content of solids | |
Maximum percentage (by volume) | 30% |
Display: | |
With local display (2 meas. pages: 1 status page, 1 graphical page) | Standard |
Languages: | |
English, French, German, Dutch, Polish, Portuguese, Danish , Spanish, Swedish, Slovenian, Italian | Standard |
Combinations: | |
VersaFlow Mag 100 Specification 34-VF-03-08 | DN10...150 (3/8” to 6”) |
VersaFlow Mag 1000 Specification 34-VF-03-16 | DN25...3000 (1” to 120”) |
VersaFlow Mag 4000 Specification 34-VF-03-01 | DN2.5...3000 (1/10” to 120”) |
VersaFlow Mag 2000 Specification 34-VF-03-21(F), 34-VF-03-22(SW) | DN2.5...250 (1/10” to 10”) |
VersaFlow Mag 3000 Specification 34-VF-03-23 | DN2.5...150 (1/10” to 6”) |
Communication: | |
Current, pulse & status output, frequency output, limit switch | Standard |
HART communication, control input, 3 counters | Standard |
Ex-i | Option |
Foundation Fieldbus | Option |
Profibus PA | Option |
Profibus DP | Option |
Modbus | Option |
Verification : | |
Integrated verification, diagnostics: | Standard |
- instrument / process / measurement | Standard |
- empty pipe indication / stabilization | Standard |
Custody transfer: | |
Without |
Standard |
Cold potable water (OIML R-49, KIWA K618) |
Option |
Other than water (OIML R-117) |
Option |
Power supply: | |
Voltage, Power Consumption, Standard/Option |
100…230 VAC (-15% / +10%), 50/60 Hz, 22 VA, Standard |
24 VDC (-55% / +30%), 12 W, Option | |
24 VAC/DC (AC: -15% / +10%; DC: -25% / +30%), AC 22 VA; DC: 12 W, Option | |
Approval : | |
Non Ex |
Standard |
EEx - zone 1 |
Option |
FM - Class I DIV 2 |
Option |
CSA - Class I DIV 2 |
Option |
NEPSI zone 1 | Option |
SAA – Aus Ex zone 1 / 2 (pending) |
Option |
Protection category (according to IEC 529 / EN 60 529) : |
|
C (compact) |
IP 66 / 67 (eq. to NEMA 6) |
F (remote) |
IP 66 / 67 (eq. to NEMA 6) |
W (wall) | IP 65 (eq. to NEMA 4/4X) |
R (19" rack | IP 20 (eq. to NEMA 1) |
Temperature: |
|
Process temperature |
See flow sensor |
Ambient temperature |
-40…+65°C / -40…+149°F |
Storage temperature |
-50…+70°C / -58…+158°F |
Signal cabl: | |
Separate - DS (dep. on measuring sensor and conductivity) |
5...600 m / 15...1950 ft |
Separate - BTS (dep. on measuring sensor and conductivity) |
5...600 m / 15...1950 ft |
Separate - LIYCY (Class 1 Div. 2 only) (dep. on measuring sensor and conductivity) |
5...100 m / 15...330 ft |
Cable connection: | |
M20 x 1.5 |
Standard |
½" NPT |
Option |
PF ½ |
Option |
Materials used: |
|
Die-cast aluminum (polyurethane coated); C and F version only |
Standard |
Polyamide - polycarbonate; W version only |
Standard |
Stainless steel 316 L (1.4404); C and F version only |
Option |
Custody transfer lead & sealing; C and F version only |
Option |