Honeywell S87 Direct Spark Ignition Modules

Direct Spark Ignition Modules
S87

Provide electronic control of direct spark ignition systems used on gas fire furnaces, boilers, and other heating appliances.
• Control ignition sequence and gas control operation.
• Generate high voltage potential for main burner ignition.
• Lockout after one trial for ignition if main burner fails to ignite.
• Reset from thermostat after lockout.
• Use modules (except S87C) with any combination gas control designed for direct spark applications and rated 2.0A or less.
Select a link under the "item" tab below to order.
Cat # | Pre Purge | Flame Failure Responce Time (sec) | Includes | Ignition Trial Time (sec) | Ignition Trials To Lockout | Lockout Timing | Flame Failure Reignition Time (sec) | Flame Sense |
S87B1008 | None | 0.8 sec. @ 5.0 microamp | Alarm terminal | 6 sec. | 1 | 6 sec. | 0.8 sec. maximum | Single rod |
S87B1016 | None | 0.8 sec. @ 5.0 microamp | Alarm terminal | 11 sec. | 1 | 11 sec. | 0.8 sec. maximum | Single rod |
S87B1024 | None | 0.8 sec. @ 5.0 microamp | Alarm terminal | 21 sec. | 1 | 21 sec. | 0.8 sec. maximum | Single rod |
S87B1065 | None | 0.8 sec. @ 5.0 microamp | Alarm terminal | 4 sec. | 1 | 4 sec. | 0.8 sec. maximum | Single rod |
S87C1006 | None | 0.8 sec. @ 5.0 microamp | — | 6 sec. | 1 | 6 sec. | 0.8 sec. maximum | Two rod |
S87C1030 | None | 0.8 sec. @ 5.0 microamp | — | 21 sec. | 1 | 21 sec. | 0.8 sec. maximum | Two rod |
S87D1004 | None | 0.8 sec. @ 5.0 microamp | Alarm terminal | 6 sec. | 1 | 6 sec. | 0.8 sec. maximum | Two rod |
S87D1012 | None | 0.8 sec. @ 5.0 microamp | Alarm terminal | 11 sec. | 1 | 11 sec. | 0.8 sec. maximum | Two rod |
S87D1020 | None | 0.8 sec. @ 5.0 microamp | Alarm terminal | 4 sec. | 1 | 4 sec. | 0.8 sec. maximum | Two rod |
S87D1038 | None | 0.8 sec. @ 5.0 microamp | Alarm terminal | 21 sec. | 1 | 21 sec. | 0.8 sec. maximum | Two rod |
S87J1026 | 30 sec. minimum | 0.8 sec. @ 5.0 microamp | — | 11 sec. | 1 | 11 sec. | 0.8 sec. maximum | Single rod |
S87J1034 | 30 sec. minimum | 0.8 sec. @ 5.0 microamp | — | 21 sec. | 1 | 21 sec. | 0.8 sec. maximum | Single rod |
S87K1008 | 30 sec. minimum | 0.8 sec. @ 5.0 microamp | — | 4 sec. | 1 | 4 sec. | 0.8 sec. maximum | Two rod |
Application | Provide electronic control of direct spark ignition systems used on gas fired furnaces, boilers, and other heating appliances. |
Dimensions, Approximate | 5 1/4 in. high x 4 1/16 in. wide x 1 15/16 in. long (133 mm high x 103 mm wide x 49 mm deep) |
Type of Gas | Natural or LP |
Electrical Ratings | 24 Vac |
Frequency | 60 Hz |
Flame Sensor | Single Rod |
Ignition Sequence | Single trial for main burner ignition (then shut down and lockout) |
Ignition Source | Internal high voltage spark generator |
Ignition System Type | Direct Spark Ignition |
Maximum Valve Load @ 24 Vac (Amps) | 2A |
Typical Gas Control | VR8205, VR8305 |
Typical Ignition Hardware | Q347A |
Maximum Ambient Temperature | (-40 C to +79 C) -40 F to +175 F |