Honeywell RP7517 Electronic-Pneumatic Transducer

Electronic-Pneumatic Transducer
RP7517

Electronic-Pneumatic Transducers are used in electronic pneumatic control systems to convert a proportional electric output signal from a controller into a direct-acting, proportional pneumatic signal.
• Screw mounting or snap rail (models with cover).
• Factory calibrated.
• Dual barb fittings.
• High accuracy
Select a link under the "item" tab below to order.
Cat # | Descriptions |
RP7517A1009 | Electronic Pneumatic Transducer with direct action and 2 to 10 vdc input signal |
RP7517A1017 | Electronic Pneumatic Transducer with direct action and 2 to 10 vdc input signal |
RP7517B1016 | Electronic Pneumatic Transducer with direct action and 2 to 10 Vdc at 0.1 mA max input signal. External transformer required. |
RP7517B1024 | Electronic Pneumatic Transducer with direct action and 2 to 10 Vdc at 0.1 mA max input signal. External transformer required. |
Application: | Electric to pneumatic Transducer | |
Action: | Direct Acting | |
Airflow Usage: | 0.025 scfm (117mL/s) | |
Connections: | Dual barb-fittings for 1/4 in. or 5/32 in. O.D. plastic tubing | |
Current: | 16 mA | |
Maximum Operating Temperature: | 131 F (55 C) | |
Maximum Operating Pressure: | 30 psi (205 kPa) | |
Pressure Ranges: | 0 to 18 psi (0 to 125 kPa) | |
Nominal High End: | 16 psi with 18 psi main pressure at 12 Vdc (110 kPa with 125 kPa main pressure at 12 Vdc) | |
Nominal Low End: | 0.5 psi at 0 Vdc (3.5 kPa at 0 Vdc) | |
Output Pressure Range: | 3 to 15 psi (21 to 103 kPa) | |
Humidity Ratings: | 5 to 95% RH | |
Capacity: | 0.45 scfm (211 mL/s) |