Honeywell RA89; RA832; R845 Hydronic Switching Relay

Hydronic Switching Relay
RA89; RA832; R845

Provide intermediate switching of a line voltage device from a low voltage controller.
• Integral transformer provides low voltage power for control circuit
Select a link under the "item" tab below to order.
Cat # | Electrical Ratings: Primary Voltage | Descriptions | Prod No | Includes | Switching Action |
R845A1030 | 120V; 50/60 Hz | Switching relay with internal transformer, provides Dpst switching for hot water zone control systems, or spst control of two separate loads. | * | Integral transformer, enclosure | DPST; one pole line voltage, the other line or low voltage |
RA832A1066 | 120V; 50/60 Hz | Switching Relay with internal transformer, for switching two line voltage loads having a common power source. | * | Integral transformer, enclosure | DPST; one pole line voltage, the other low voltage or millivolt |
RA832A1074 | 240V; 50/60 Hz | Switching Relay with internal transformer, for switching two line voltage loads having a common power source. | * | Integral transformer, enclosure | DPST; one pole line voltage, the other low voltage or millivolt |
RA89A1074 | 120V; 50/60 Hz | Switching Relay with internal transformer, for switching one line voltage load. | * | Integral transformer, enclosure | SPST |
Dimensions, Approximate: | 5 1/4 in. high x 4 1/4 in. wide x 2 5/16 in. deep (133 mm high x 108 mm wide x 59 mm deep) |
Electrical Connections (Control Circuit): | 2-Wire |
Electrical Rating: Maximum Input: | 5.0W |
Coil Ratings | |
Voltage: | 24 Vac |
Current: | 0.4 |
Transformer Primary Rating: | 120 Vac, 50/60 Hz |
Transformer Secondary Rating: | 24 Vac |
Thermostat Compatibility: | Low voltage (Class 2) 2-wire |
Temperature Range: Temperature Range: | 115 F maximum ambient for 60 Hz. 105 F Max. Ambient for 50 Hz. (46 C maximum ambient for 60 Hz. 41 C maximum ambient for 50 Hz.) |
Approvals: | |
Canadian Standards Association: | Certified: File No. LR1620 |
Underwriters Laboratories Inc. Listed: | File No. E4436, Guide No. XAPX |