Honeywell R7140 Programmer


The Honeywell R7140G, L, M Burner Control Modules are microprocessor-based integrated burner control for automatically fired gas, oil or combination fuel single burner applications.
• Functions provided by the R7140G,L,M include automatic burner sequencing, flame supervision, system status indication, system or self-diagnostics and troubleshooting.
• Upgrade replacement for BC7000 or R4140 legacy Programmer controls.
• Require ST7800 Purge Timer and appropriate R78XX Amplifier to complete the replacement.
Select a link under the "item" tab below to order.
Comments | Cat # | Second Stage Pilot Valve | Interlocks | Pilot | Main | Pilot Type |
LHL-LF Proven | R7140G1000 | Selectable | Running | 4 sec or 10 sec | 10 sec, or 15 sec, or 30 sec, or Intermittent | Interrupted or Intermittent |
LHL-LF Proven | R7140G2008 | Running | 4 sec or 10 sec | 10 sec, or 15 sec, or 30 sec, or Intermittent | Interrupted or Intermittent | |
LHL-LF&HF Proven | R7140L1009 | Interrupted | Lockout | 4 sec or 10 sec | 10 sec or 15 sec | Interrupted |
LHL-LF&HF Proven | R7140L2007 | Interrupted | Lockout | 4 sec or 10 sec | 10 sec or 15 sec | Interrupted |
On/Off-LF Proven | R7140M1007 | Intermittent | Running | 4 sec or 10 sec | 10 sec or Intermittent | Interrupted or Intermittent |