Jump to Navigation

Honeywell LP916 Pneumatic Thermostat

Pneumatic Thermostat
LP916

Two-pipe, single temperature, unit mounted, remote bulb pneumatic thermostat used to provide proportional control of pneumatic valves and damper actuators in heating and air conditioning systems.

• Liquid filled remote bulb.
• Direct Acting (DA), Reverse Acting (RA) and Heating/Cooling (DA/ RA) models are available.

Select a link under the "item" tab below to order.

Cat #ChangeoverSensor ElementActionScale MarkingsCommentsSetting Temperature RangeIncludesThrottling Range
LP916A1019-Bulb 1/2 x 5 7/8 in., capillary 36 in. (914mm) longDirect ActingWarmer / Cooler-65 F to 85 FIntegral Mounting Bracket and 304528A Bag Assembly (mounting hardware). Order bulb hangers (316297-00021) sparately.3.5 F
LP916A1134-Bulb 3/8 x 7 in., capillary 36 in. (914 mm) longDirect ActingWarmer / Cooler-65 F to 85 FIntegral Mounting Bracket, (2) 316297-00021 Bulb Hangers and 304528A Bag Assembly (mounting hardware).3.5 F
LP916A1175-Bulb 3/8 x 7 in., capillary 36 in. (914 mm) longDirect Acting40 F to 80 F-40 F to 80 FIntegral Mounting Bracket, (2) 316297-00021 Bulb Hangers and 304528A Bag Assembly (mounting hardware).7 F
LP916B1017Heat 18 psi, Cool 13 psiBulb 1/2 x 5 7/8 in., capillary 36 in. (914 mm) longDirect Acting Heating, Reverse Acting CoolingWarmer / Cooler-65 F to 85 FIntegral Mounting Bracket and 304528A Bag Assembly (mounting hardware). Order bulb hangers (316297-00021) separately.3.5 F
LP916B1058Heat 18 psi, Cool 9 psiBulb 1/2 x 5 7/8 in., capillary 36 in. (914 mm) longDirect Acting Heating, Reverse Acting CoolingWarmer / Cooler-65 F to 85 FIntegral Mounting Bracket and 304528A Bag Assembly (mounting hardware). Order bulb hangers (316297-00021) separately.3.5 F
LP916B1074Heat 18 psi, Cool 13 psiBulb 3/8 x 7 in., capillary 36 in. (914 mm) longDirect Acting Heating, Reverse Acting CoolingWarmer / Cooler-65 F to 85 FOrder Mounting Bracket, Knob, Bulb Hangers, and Scale Plate separately.3.5 F
LP916B1082Heat 18 psi, Cool 13 psiBulb 3/8 x 7 in., capillary 36 in. (914 mm) longDirect Acting Heating, Reverse Acting CoolingWarmer / CoolerNew installation model65 F to 85 FIntegral Mounting Bracket, (2) 316297-00021 Bulb Hangers and 304528A Bag Assembly (mounting hardware).3.5 F
LP916B1090Heat 18 psi, Cool 13 psiBulb 3/8 x 9 in., capillary 36 in. (914 mm) longDirect Acting Heating, Reverse Acting CoolingWarmer / Cooler-65 F to 85 FIntegral Mounting Bracket, (2) 316297-00021 Bulb Hangers and 304528A Bag Assembly (mounting hardware).3.5 F
LP916C1023-Bulb 3/8 x 9 in., capillary 36 in. (914 mm) longReverse Acting60 F to 80 F-60 F to 80 FIntegral Mounting Bracket, (2) 316297-00021 Bulb Hangers and 304528A Bag Assembly (mounting hardware).3.5 F
Application Type: Unit Ventilator
Dimensions, Approximate: 4 3/4 in. high x 3 3/4 in. wide x 3 in. deep
(121 mm high x 95 mm wide x 76 mm deep)
Airflow Usage: 0.022 scfm (10.4 mL/s) with 0.007 in. restriction
Air Connections: Barb fittings 1/4 in. (6 mm)
Mounting: In compartment of a unit ventilator
Operating Temperature: 135 F maximum (57 C maximum)
Storage Temperature: 150 F maximum (66 C maximum)
Remote Bulb: Yes
Sensor Element: Bulb 1/2 x 5 7/8 in., capillary 36 in. (914 mm) long
Number of Pipes: 2
Setpoint: Single
Maximum Operating Pressure: 25 psi (170 kPa)

 

 

 

 

 

 

 

 

 

 



Main menu 2