Honeywell L4008,L6008 Single and Multi-Function Aquastat Controllers

Single and Multi-Function Aquastat Controllers
L4008,L6008

Aquastat® Controllers are immersion type devices for limiting or regulating the temperature of liquids in boilers, storage tanks, and other applications where temperature control is required.

• Remote temperature sensing element detects and responds rapidly to temperature changes.
• Totally enclosed Micro Switch® snap-acting switch.
• Visible control point scale and external adjustment screw permit easy setting.
• Horizontal or vertical mounting of the remote element into boiler, tank, or other container.
• Case mounts to a vertical surface.

Select a link under the "item" tab below to order.

Cat #Capillary LengthBulb SizeDifferential TempIncludesApplication:Switching ActionMounting
L4008A101566 in.3/8 in. x 2 7/8 in. copper5 F to 30 F adj.5 1/2 ft (1.7 m) capillary.High or Low limitSPST, contacts break on temperature rise.Horizontal or Vertical
L4008A1130120 in.3/8 in. x 2 7/8 in. copper5 F to 30 F adj.10 ft (3.04 m) capillary; factory-set stop at 200 F (93 C).High or Low limitSPST, contacts break on temperature rise.Horizontal or Vertical
L4008B101366 in.3/8 in. x 2 7/8 in. copper5 F to 30 F adj.5 1/2 ft (1.7 m) capillary.CirculatorSPST, contacts break on temperature rise.Horizontal or Vertical
L4008E115666 in.3/8 in. x 2 7/8 in. copperManual Reset5 1/2 ft (1.7 m) capillary; factory-set stop at 250 F (121 C); heat-conductive compound.High Limit; Manual ResetSPST, contacts break on temperature rise.Horizontal or Vertical
L4008E130566 in.3/8 in. x 2 7/8 in. copperManual ResetHigh Limit; Manual ResetSPST, contacts break on temperature rise.Horizontal or Vertical
L4008E131366 in.3/8 in. x 2 7/8 in. copperManual ResetHigh Limit; Manual ResetSPST, contacts break on temperature rise.Horizontal or Vertical
L6008A119266 in.3/8 in. x 2 7/8 in. copper5 F to 30 F adj.66 in. capillaryCirculator Control and Low LimitSPDTHorizontal or Vertical
L6008A124266 in.3/8 in. x 2 7/8 in. copper5 F to 30 F adj.66 in. capillaryCirculator Control and Low LimitSPDTHorizontal or Vertical
Case Dimensions: 5 5/8 in. high x 2 in. wide x 2 1/8 in. deep (143 mm high x 51 mm wide x 54 mm deep)
Maximum Ambient Temperature: 150 F (66 C)
Operating Temperature Range: 100 F to 240 F (38 C to 116 C)
Electrical Ratings: 5.1A @ 240 Vac; 8A @ 120 Vac (Full Load), 30.6A @ 240 Vac; 48A @ 120 Vac (Locked Rotor), 0.25A @ 0.25 to 12 Vdc (Millivolt)
Approvals:
Canadian Standards Association: Certified: File No. LR95329-1
Underwriters Laboratories Inc. UL Component Recognized: File No. MP466, Vol. 6, Sec.1, Guide No. MBPR2