Honeywell C6097 Pressure Switch


Pressure Switches are safety devices used in positive-pressure or differential-pressure systems to sense gas or air pressure systems.
• For use with natural gas, liquid propane (LP) gas, or air.
• Diaphragm-actuated safety-limit switch.
• Switch can be wired to turn on alarm.
• C6097A models break control circuit at setpoint on pressure fall.
• C6097B models break control circuit at setpoint on pressure rise.
• Lockout with manual reset and recycle options.
• Lockout models have external manual reset button.
• Removable transparent cover protects scaleplate and adjusting knob.
• Pipe tappings allow selection of positive pressure (air only) or venting connections (NPT mount only).
• 1/4 in. NPT or flange mount models for direct mounting to Honeywell Integrated Valve Train.
• Optional switch position indicator lamp available.
• IP54 enclosure standard.
• Ranges: 0.4 to 5 in. wc, 3 to 21 in. wc, 12 to 60 in. wc or 1.5 to 7 psi.
• Surge orifice.
Select a link under the "item" tab below to order.
Cat # | Mounting | Operating Pressure Range (psi) | Pressure Differential (psi) | Switching Action | Nominal Pressure Differential (psi) | Switch Operation | Maximum Pressure Differential (psi) |
C6097A1004 | 1/4 in. NPT internal thread | 0.4 to 5 in. wc | - | Break on pressure fall | 0.16 in. wc | Auto recycle | 0.24 in. wc |
C6097A1012 | 1/4 in. NPT internal thread | 3 to 21 in. wc | max. 2.4 in. wc @ min. setpoint; max. 4.2 in. wc @ max. setpoint | Break on pressure fall | - | Manual Reset | - |
C6097A1020 | Flange Mount | 3 to 21 in. wc | max. 2.4 in. wc @ min. setpoint; max. 4.2 in. wc @ max. setpoint | Break on pressure fall | - | Manual Reset | - |
C6097A1038 | 1/4 in. NPT internal thread | 12 to 60 in. wc | max. 10 in. wc @ min. setpoint; max. 12 in. wc @ max. setpoint | Break on pressure fall | - | Manual Reset | - |
C6097A1046 | Flange Mount | 12 to 60 in. wc | max. 10 in. wc @ min. setpoint; max. 12 in. wc @ max. setpoint | Break on pressure fall | - wc | Manual Reset | - |
C6097A1053 | 1/4 in. NPT internal thread | 3 to 21 in. wc | - | Break on pressure fall | 0.24 in. wc | Auto recycle | 0.48 in. wc |
C6097A1061 | Flange Mount | 3 to 21 in. wc | - | Break on pressure fall | 0.24 in. wc | Auto recycle | 0.48 in. wc |
C6097A1079 | 1/4 in. NPT internal thread | 12 to 60 in. wc | - | Break on pressure fall | 1.1 in. wc | Auto recycle | 2.4 in. wc |
C6097A1087 | Flange Mount | 12 to 60 in. wc | - | Break on pressure fall | 1.1 in. wc | Auto recycle | 2.4 in. wc |
C6097A1095 | 1/4 in. NPT internal thread | 0.4 to 5 in. wc | max. 10 in. wc @ min. setpoint; max. 12 in. wc @ max. setpoint | Break on pressure fall | - | Manual Reset | - |
C6097A1103 | Flange Mount | 1.5 to 7 psi | max. 1.1 in. wc @ min. setpoint; max. 1.4 in. wc @ max. setpoint | Break on pressure fall | - | Manual Reset | - |
C6097A1111 | 1/4 in. NPT internal thread | 1.5 to 7 psi | max. 1.1 in. wc @ min. setpoint; max. 1.4 in. wc @ max. setpoint | Break on pressure fall | - | Manual Reset | - |
C6097A1129 | Flange Mount | 1.5 to 7 psi | - | Break on pressure fall | 0.1 psi | Auto recycle | 0.3 psi |
C6097A1137 | 1/4 in. NPT internal thread | 1.5 to 7 psi | - | Break on pressure fall | 0.1 psi | Auto recycle | 0.3 psi |
C6097A1210 | Flange Mount | 0.4 to 5 in. w | - | Break on pressure fall | 0.16 in. wc | Auto recycle | 0.24 in. wc |
C6097A1228 | Flange Mount | 0.4 to 5 in. w | max. 0.6 in. wc @ min. setpoint; max. 0.25 in. wc @ max. setpoint | Break on pressure fall | - | Manual Reset | - |
C6097B1002 | 1/4 in. NPT internal thread | 12 to 60 in. wc | max. 0.6 in. wc @ min. setpoint; max. 0.25 in. wc @ max. setpoint | Break on pressure rise | - | Manual Reset | - |
C6097B1010 | Flange Mount | 12 to 60 in. wc | max. 10 in. wc @ min. setpoint; max. 12 in. wc @ max. setpoint | Break on pressure rise | - | Manual Reset | - |
C6097B1028 | 1/4 in. NPT internal thread | 3 to 21 in. wc | max. 2.4 in. wc @ min. setpoint; max. 4.2 in. wc @ max. setpoint | Break on pressure rise | - | Manual Reset | - |
C6097B1036 | Flange Mount | 3 to 21 in. wc | max. 2.4 in. wc @ min. setpoint; max. 4.2 in. wc @ max. setpoint | Break on pressure rise | - | Manual Reset | - |
C6097B1044 | Flange Mount | 1.5 to 7 psi | max. 1.1 in. wc @ min. setpoint; max. 1.4 in. wc @ max. setpoint | Break on pressure rise | - | Manual Reset | - |
C6097B1051 | 1/4 in. NPT internal thread | 1.5 to 7 psi | max. 1.1 in. wc @ min. setpoint; max. 1.4 in. wc @ max. setpoint | Break on pressure rise | - wc | Manual Reset | - |
C6097B1069 | Flange Mount | 3 to 21 in. wc | - | Break on pressure rise | 0.24 in. wc | Auto recycle | 0.48 in. wc |
C6097B1077 | Flange Mount | 12 to 60 in. wc | - | Break on pressure rise | 1.1 in. wc | Auto recycle | 2.4 in. wc |
C6097B1085 | 1/4 in. NPT internal thread | 12 to 60 in. wc | - | Break on pressure rise | 1.1 in. wc | Auto recycle | 2.4 in. wc |
C6097B1093 | Flange Mount | 1.5 to 7 psi | - | Break on pressure rise | 0.1 psi | Auto recycle | 0.3 psi |
C6097B1101 | 1/4 in. NPT internal thread | 1.5 to 7 psi | - | Break on pressure rise | 0.1 psi | Auto recycle | 0.3 psi |
C6097B1119 | 1/4 in. NPT internal thread | 3 to 21 in. wc | - | Break on pressure rise | 0.24 in. wc | Auto recycle | 0.48 in. wc |
Application | Safety devices used in positive-pressure or differential pressure systems to sense gas or air pressure changes | |
Pipe Connections, Vent or Low pressure | 1/8 in. NPT internal thread | |
Alternate Ratings | Ignition Transformer: 540 VA, Pilot Valve: 50 VA. Main Valve: 400 VA with 2-1/2 times inrush | |
Electrical Connections | Screw terminals | |
Differential Type | Additive | |
Switch Contact Ratings | 3.0 AFL, 18.0 ALR, 5.0 A resistive (120 Vac); 3.0 AFL, 18.0 ALR, 5.0 A resistive (240 Vac) |
|
Switch Contact Ratings | (120 Vac) | 8.0 AFL, 48.0 ALR, 10.0 A resistive |
(120 Vdc) | 2.0 AFL, 20.0 ALR, 8.0 A resistive | |
(240 Vac) | 5.1 AFL, 30.6 ALR, 5.0 A resistive | |
(240 Vdc) | 1.0 AFL, 10.0 ALR, 4.0 A resistive | |
Temperature Range | -40 F to +140 F (-40 C to +60 C) | |
Approvals | ||
Canadian Standards Association | Certified | |
Factory Mutual | Approved | |
Underwriters Laboratories Inc. Listed | Component Listed | |
Others | CSD-1 AFB: Acceptable |