Honeywell M9164 Modutrol IV™ Motors


Series 90 Modutrol IV™ motors are non-spring return modulating proportional control motors used with controllers that provide a Series 90 output to operate dampers or valves.
• Integral junction box provides NEMA 3 weather protection.
• Motor and circuitry operate from 24 Vac.
• Quick-connect terminals are standard--screw terminal adapter is available.
• Adapter bracket for matching shaft height of older motors is available.
• Motors have field adjustable stroke (90° to 160°).
• Integral auxiliary switches are available factory mounted, or can be field added.
• All models have dual shafts (slotted and tapped on both ends).
• All models have auxiliary switch cams.
• Fixed torque throughout the entire voltage range.
Select a link under the "item" tab below to order.
Cat # | Voltage | Includes | Internal Auxiliary Switch | (lb-in., lb) | (Nm, N) | Nominal | Stroke | Shaft Rotation(upon controlsignal increase) |
M9164A1005 | 120V | Transformer | 0 | 35 lb-in. | 4 Nm | 30-60 sec | Adjustable; 90° to 160°, Asymmetrical | Clockwise (as viewed from power end) (normally closed) |
M9164A1013 | 24/120/ 230V | Transformer | 0 | 35 lb-in. | 4 Nm | 30-60 sec | Adjustable; 90° to 160°, Asymmetrical | Clockwise (as viewed from power end) (normally closed) |
M9164A1070 | 24V | — | 0 | 35 lb-in. | 4 Nm | 30-60 sec | Adjustable; 90° to 160°, Asymmetrical | Clockwise (as viewed from power end) (normally closed) |
M9164C1001 | 24V | — | 2 | 35 lb-in. | 4 Nm | 30-60 sec | Adjustable; 90° to 160°, Asymmetrical | Clockwise (as viewed from power end) (normally closed) |
M9164C1068 | 24V | Transformer | 2 | 35 lb-in. | 4 Nm | 30-60 sec | Adjustable; 90° to 160°, Asymmetrical | Clockwise (as viewed from power end) (normally closed) |
M9164D1009 | 24V | — | 0 | 35 lb-in. | 4 Nm | 30-60 sec | Adjustable; 90° to 160°, Asymmetrical | Clockwise (as viewed from power end) (normally closed) |
Application Type: | Electric | ||
Dimensions Diagram: | See page 425 | ||
Fail Safe Mode: | Non-Spring Return | ||
Control Signal: | Proportional, 135 ohm | ||
External Auxiliary Switches Available: | Yes | ||
Auxiliary Switch Ratings AFL - 120 Vac: | 7.2 A | ||
Auxiliary Switch Ratings ALR - 120 Vac: | 43.2A | ||
Auxiliary Switch Ratings AFL - 240 Vac: | 3.6 A | ||
Auxiliary Switch Ratings ALR - 240 Vac: | 21.6 A | ||
Feedback: | No | ||
Electrical Connections: | Quick-connect terminals | ||
Frequency: | 50 Hz; 60 Hz | ||
Mounting: | Foot-mounted | ||
Motor Shafts: | Dual-ended shaft | ||
Shaft Shape: | square | ||
Shaft Dimensions: | 0.375 in. (10 mm) | ||
Deadweight Load on Shaft (Either End): | 200 lbs. | ||
Deadweight Load (Combined on both Shafts): | 300 lbs. | ||
Ambient Temperature Range: | -40 F to +150 F (-40 C to +60 C) | ||
Weight: | 7.5 lb | ||
Approvals: | |||
Canadian Standards Association: | Certified: File No. LR1620, Guide No. 400-E | ||
CE: | EN55011 (Emission) EN50082-2 (Immunity) 73/23/EEC (LVD) | ||
Underwriters Laboratories Inc. | Listed File: E4436, Guide: XAPX |