Jump to Navigation

Honeywell VA301C Modbus Controller

Modbus Controller
VA301C

The VA301C continuously monitors and controls toxic gases, combustible gases, and oxygen hazards. Designed for installation and operational simplicity, the VA301C reduces the cost of installation and ownership.

Using an addressable RS-485 Modbus communication protocol, the 301C uses daisy chain wiring requiring only 2 pairs of wires to connect up to 96 transmitters on the 3 input channels. This simplifies installation, in turn lowering costs. The 301C’s zoning and averaging abilities significantly reduce operational and maintenance costs.

Zoning/Averaging Capabilities Reduce Operational Costs
The 301C controller offers unique zoning capabilities which permit the averaging and comparison of multiple sensor readings. Zoning can reduce operational costs by ensuring that localized brief fluctuations registered at a single transmitter do not activate relays. For example, a car idling in a parking structure may locally increase a reading at a nearby transmitter. Rather than activating a fan as a result of the temporary localized fluctuation, zoning can be used to limit relay activation until the average reading for a zone exceeds a set-point. This can reduce run time of fans, yielding savings in both energy usage and wear and tear. The 301C has the capacity to manage input from three Modbus channels for up to 96 transmitters and up to 50 wireless transmitters which can be associated with up to 126 zones. Transmitters can belong to an unlimited number of zones, providing maximum operational and control flexibility.

User Friendly
• Zero maintenance
• Automatic quick self-test and warm-up
• Continuous alphanumeric display

Inexpensive and Reliable
• Low installation costs
• Allows for up to 126 zoning groups which can save energy and extend fan and relay life
• Manages up to 768 events with programmable latching alarms

Flexible Operation
• Modbus compatible; with BACnet/IP available
• Interchangeable transmitters able to detect different gases
• Expands to handle up to 96 transmitters or relay modules and up to 50 301W wireless sensors
• Programmable time delays
• Integrated time clock enables scheduling of system operations

Safety Measures
• Full array of visual indicators and integrated 65dBA alarm levels
• Fully programmable relays (can be set as fail-safe or not)

Beneficial Options
• Available in a heavy duty industrial housing
• Data logging option

Use Modbus controller for centralized gas detection monitoring with real-time gas reading, selective alarm activation and low cost of installation.
Size 28 x 20.3 x 7 cm (11.02 x 7.99 x 2.76 in.)
Weight 1.1 kg (2.4 lb.)
Power Requirement 17-27 Vac, 24-38 Vdc, 500 mA
Network Capacity Three Modbus channels for up to 96 transmitters, one wireless channel for up to 50 301W wireless transmitters and an optional BACnet/IP output
Communication Line Lengths Up to 609 m (2000 ft.) per channel
T-Tap: 20 m (65 ft.), maximum per T-Tap
40 m (130 ft.), maximum for all T-Tap combined
Relay Output Rating 5 A, 30 Vdc or 250 Vac (resistive load)
Alarm Levels 3 fully programmable alarm levels
Time Delays 0, 30 sec., 45 sec., 1-99 minutes before and after alarm
Outputs. 4 DPDT relays (alarms and/or fault); 65dBA buzzer
Display Large 122 x 32 dot matrix display
Operating Humidity Range 0-95% RH, non-condensing
Operating Temperature Range -20 to 50°C (-4 to 122°F)
Ratings and Certifications
Certified to CAN/CSA C22.2 No 61010-1
116662
Conforms to ANSI/UL 61010-1
IEC 61010-1 Including Amendments A1:1992 +
A2:1995 and National Deviations (Canada, US)


Main menu 2