Action Instruments Q106 DC Input, Field Configurable Limit Alarm


The ActionI/Q model Q106 is a DIN rail mount, DC voltage or current input limit alarm with dual setpoints and two contact closure outputs. The field configurable input and alarm functions offer flexible setpoint capability. Input voltage spans from 10mV to 200V and input current spans from 1mA to 100mA can be field configured. Bipolar inputs are also accepted.
Thanks to Action Instruments TouchCAL Technology, the Q106 is configurable as a single or dual setpoint alarm, with HI or LO trips and failsafe or non-failsafe operation. Also included are adjustable deadbands (up to 100% of full scale input) for each setpoint, a 24VDC voltage source (isolated from line power) for transducer excitation, and a universal AC power supply which accepts any voltage between 85 and 265VAC.
• Easy Field Configurable Input Ranges
• TouchCALTM Technology for Easy Setpoint Calibration
• Adjustable Setpoints Programmable HI or LO and Failsafe or Non- Failsafe
• High Density DIN Rail Mounting
• Universal AC Power 85 to 265 VAC
• 24VDC Transducer Excitation
• SnapLocTM, Plug-in Terminals for Low MTTR
• ASIC Technology for High Reliability
Input | |
Voltage Input: | |
Range: | Range: |
Impedance: | >100KW |
Overvoltage: | 200V rms, max. |
Current Input |
|
Range: | 1mA to +100mA |
Impedance: | 20W, typical |
Overcurrent: | 170mA rms, max. |
Overvoltage: | 60VDC (protected by self resetting fuse) |
Common Mode (Input to Ground): | 1800VDC, max. |
LED Indicators | |
Input Range (Green): | >110% input: 8Hz flash <10% input: 4Hz flash |
Setpoint (Red): | Tripped: Solid red, Safe: Off |
Limit Differentials (Deadbands) | |
>50mV/5mA: | 0.25% to 100% of span |
<50mV/5mA: | 1% to 100% of span |
Response Time: | |
Dynamic Deadband: | Relay status will change when proper setpoint/process condition exists for 100msec. Normal Mode (analog filtering): <250mSec, (10-90%) |
Stability | |
Temperature: | +0.05% of full scale/°C, max. |
Excitation Voltage: | 24VDC, 20mA, maximum |
CMRR: | DC to 60Hz: 120dB |
Isolation: | 1800VDC between contacts, input and power |
Temperature Range: | |
Operating: | 0 to 55°C (32 to 131°F) |
Storage: | -25 to 70°C (-13 to 158°F) |
Power: | 2.5W max.,100 to 240VAC +10%, 50Hz -400Hz |
Relay Contacts: | 2 SPDT (2 form C) Relays 1 Relay per setpoint |
Current Rating (resistive): | 120VAC: 5A, 240VAC: 2A, 28VDC: 5A |
Wire Terminations: | Screw terminations for 12-22 AWG |
Weight: | 0.56lbs. |
Agency Approvals: | CSA certified per standard C22.2 (File No LR42272) UL recognized per standard UL508 (File No E99775) CE EN61326, EN61010-1 |