Action Instruments AP1080/AP1090 DC Input, Field Configurable Limit Alarms


Action Pak models AP1080 single setpoint and AP1090 dual setpoint limit alarms offer flexible, wide-ranging DC input capability. Voltage spans from 10mV to 200 volts and current spans from 1mA to 100mA can be field configured. Bipolar inputs are also accepted. Both models offer configurable latching, failsafe and HI/LO operation. The AP1080 and AP1090 also include 0.25%-50% adjustable deadbands and selectable 120/240VAC operation.
● Selectable 120/240VAC Operation (9 to 30 VDC Available)
● Field Configurable Input Ranges for DC Voltage and Current
● Setpoint(s)Programmable HI or LO
● Exclusive“Dynamic Deadband” Prevents False Trips
● Selectable Failsafe/Latching Operation
Select a link under the "item" tab below to order.
Cat # | Descriptions |
1080-2000-1 | Field Configurable Single Limit Alarm, AC Powered |
1080-2000-D | Field Configurable Single Limit Alarm, DC Powered |
1090-2000-1 | Field Configurable Dual Limit Alarm, AC Powered |
1090-2000-D | Field Configurable Dual Limit Alarm, DC Powered |
Voltage Input: | Range: 10mV to 200V Impedance: >100K Ohmns Overvoltage: Intermittent, 400Vrms Continuous, 264 Vrms |
||
Current Input: | Full Scale Range: 1mA to 100mA Impedance: 20 Ohms, typical Overcurrent: 200mA, max Overvoltage: 60VDC Common Mode (Input toGround): 1500VDC, max |
||
LED Indications: | Input Range (Green) >100% input: 8Hz flash <0% input: 4Hz flash Setpoint (Red) Tripped: Solid red Safe: Off |
||
Limit Differential: | >50mV/5mA: .25% to 50% of span <50mV/5mA: 1% to 50% of span |
||
Response Time: Dynamic Deadband: | Relay status will change when proper setpoint/process condition exists uninterrupted for 100ms | ||
Normal Mode (analog filtering): | <250ms, (10-90%) | ||
Setpoint: Effectivity: | Setpoints are adjustable over 100% of the selected input span. | ||
Weight: | AP1080: .46lbs; AP1090: .62lbs | ||
Agency Approvals: | CSA certified per standard C22.2, No. M1982. UL recognized per standard UL508. |
||
EMC Compliance (CE Mark): | Emissions: EN50081-1 Immunity: EN50082-2 Safety:EN50178 |
||
Mean Time Between Failures: | 60K Hours | ||
Humidity (Non-Condensing): | Operating: 15 to 95%(@ 45‹C) Soak:90% for 24 hours (@ 65‹C) |
||
Temperature Range: | Operating: 0 to 55°C (32 to 131°F) Storage: -25 to 70°C (-13 to 158°F) |
||
Wire Terminal: | Screw terminals for 12-22AWG | ||
Power: | Consumption: 1.5W typical, 2.5W max. Range: 9 to 30VDC |
||
Weight: | 0.5 lbs. | ||
Agency Approvals: | CSA certified per standard C22.2, No. 0-M91 and 142- M1987 (File No. LR42272). UL recognized per standard UL508 (File No.E99775). CE Conformance per EMC directive 89/336/EEC and Low Voltage 73/23/EEC (Input < 75VDC, only). |