Siemens 192 HC Powerstar Heating/Cooling Pneumatic Room Thermostats

Powerstar Heating/Cooling Pneumatic Room Thermostats
192 HC

Providing proportional single output, dual setpoint with 2-pipe for high air capacity pneumatic room temperature control, the 192 HC Powerstar Heating/Cooling Pneumatic Room Thermostat provides two thermostats under one cover; one side for heating and the other for cooling. Switchover is accomplished by changing the air pressure to the thermostat.

• Dual setpoint dial available in Fahrenheit or Celsius scales
• Available in direct or reverse acting models
• Sensitive bimetal responds to temperature changes
• Integral, field adjustable limit stops
• Adjustable changeover pressure
• Large volume air capacity relay
• Wall mounting plates provides connection to a variety of rough-in terminal boxes
• Test port for fast check of output pressure without removing the cover
• Field replaceable thermometer, setpoint dials, restrictor and filters Options

Select a link under the "item" tab below to order.

Cat #OutputSetpointAir Output CapacityThermometer & Setpoint ScalesActionControl Action Type
192-207SingleDual (Heat and Cool)High (Integral Relay)°FCool (DA)Heat Direct
192-208SingleDual (Heat and Cool)High (Integral Relay)°FCool (RA)Heat Direct
192-227SingleDual (Heat and Cool)High (Integral Relay)°CCool (DA)Heat Direct
192-228SingleDual (Heat and Cool)High (Integral Relay)°CCool (RA)Heat Direct
192-209SingleDual (Heat and Cool)High (Integral Relay)°FCool (DA)Heat Reverse
192-210SingleDual (Heat and Cool)High (Integral Relay)°FCool (RA)Heat Reverse
192-229SingleDual (Heat and Cool)High (Integral Relay)°CCool (DA)Heat Reverse
192-230SingleDual (Heat and Cool)High (Integral Relay)°CCool (RA)Heat Reverse
Scale; Range: Major (minor) Divisions 45 to 85°F, 10(2)°F (7 to 30°C, 5(1)°C)
Factory Calibration: 72°F, 7.5 psi ± 0.3 (22°C, 52 kPa @ 1.8)
Sensitivity Adjustment Range: 1 to 4 psi/°F (12 to 50 kPa/°C)
Factory Setting: 2.5 psi/°F (31 kPa/°C)
Limit Stop: Field Adjustment Range 45/85°F (7/30°C)
Fixed Limit Stop Range 55/75°F (3/24°C)
Temperature: Storage -10 to +140°F (-23 to +60°C)
Ambient Operating 40 to 140°F (4 to 60°C)
Accuracy at Factory: Calibration ±2°F (±1.1°C)
Response 0.1°F (0.06°C)
Supply Air Pressure: Two Pressure (Recommended) Cooling/Heating 18 psi (124kPa)/ (124 kPa)/25 psi (172 kPa)
Supply Air Pressure:
Two Pressure (Range)
Cooling 15 to 19 psi (103 to 131 kPa)
Heating 23 to 30 psi (159 to 207 kPa)
Two Pressure, Honeywell Competitive Model:
Cooling/Heating
13 psi (90 kPa)/18 psi (124 kPa)
Two Pressure, Johnson Competitive Model1:
Cooling/Heating
15 psi (103 kPa)/20 psi (138 kPa)
Nominal Air Consum. for Air Compressor Sizing: 25 scim (6.8 ml/s)
Nominal Air Capacity for Air Main Sizing: 40 scim (11 ml/s)
Nominal Air Capacity: Supply/Chassis Exhaust 150 scim (41 ml/s)/150 scim (41 ml/s)
Air Connections: 5/32" (4 mm) OD tube
Dimensions (with cover): 2.16" W x 3.34" H x 1.59" D (55 mm W x 85 mm H x 40 mm D)
Shipping Weights: Thermostat Chassis and Wall Plate 0.53 lb. (0.24 kg)
Plastic Cover 0.07 lb. (0.04 kg)
Metal Cover (single/dual) 0.27 lb. (0.12 kg)/0.7 lb. (0.3 kg)