Jump to Navigation

Siemens 184 Temperature Transmitters

Temperature Transmitters
184

The 184 Temperature Transmitters are direct acting, one-pipe instruments that sense temperature and transmit a proportional 3 to15 psi (21 to 103 kPa) pneumatic signal to a remotely located receiver gauge and/or receiver controller. Temperature Transmitters operate on the force-balance principle, using internal feedback for excellent linearity and accuracy. Retroline transmitters easily replace any competitive model. Refer to the appropriate product to locate the Retroline replacement.

• 1-pipe, direct acting
• Rapid response to temperature changes over their full range
• Available in a variety of sensing elements and temperature ranges
• Available with rigid bulb, remote averaging bulb, and room transmitter
• Internal feedback for excellent linearity and accuracy

 

Select a link under the "item" tab below to order.

Cat #DescriptionsTemperature Range
184-0001Rigid Bulb Transmitter Bulb ¼” Dia. x 9” L (6 mm Dia. x 229 mm L)35 to+135°F (2 to 57°C)
184-0002Rigid Bulb Transmitter Bulb ¼” Dia. x 9” L (6 mm Dia. x 229 mm L)50 to 100°F (10 to 38°C)
184-0003Rigid Bulb Transmitter Bulb ¼” Dia. x 9” L (6 mm Dia. x 229 mm L)80 to 240°F (27 to 116°C)
184-0028Rigid Bulb Transmitter Bulb ¼” Dia. x 9” L (6 mm Dia. x 229 mm L)0 to 100°F (-18 to 38°C)
184-0004Remote Averaging Bulb Transmitter 3/32” Dia. x 20’ L (2 mm Dia. x 6.1 m L) with 12” (305 mm) Capillary35 to+135°F (2 to 57°C)
184-0048Remote Averaging Bulb Transmitter 3/32” Dia. x 20’ L (2 mm Dia. x 6.1 m L) with 12” (305 mm) Capillary0 to +120°F (-40 to 49°C)
184-0005Rigid Bulb Transmitter ¼” Dia. x 4” L (6 mm Dia. x 102 mm L) 3’ (0.92 m) Capillary-40 to 240°F (4 to 116°C)
184-0018Rigid Bulb Transmitter ¼” Dia. x 4” L (6 mm Dia. x 102 mm L) 3’ (0.92 m) Capillary50 to 100°F (10 to 38°C)
184-0014Rigid Bulb Transmitter ¼” Dia. x 4” L (6 mm Dia. x 102 mm L) 3’ (0.92 m) Capillary80 to 240°F (27 to 116°C)
184-0036Rigid Bulb Transmitter ¼” Dia. x 4” L (6 mm Dia. x 102 mm L) 3’ (0.92 m) Capillary0 to 100°F (-18 to 38°C)
184-0015Rigid Bulb Transmitter ¼” Dia. x 4” L (6 mm Dia. x 102 mm L) 3’ (0.92 m) Capillary-10 to +65°F (-23 to +18°C)
184-0034Rigid Bulb Transmitter ¼” Dia. x 4” L (6 mm Dia. x 102 mm L) 3’ (0.92 m) Capillary35 to+135°F (2 to 57°C)
184-0041Rigid Bulb Transmitter ¼” Dia. x 4” L (6 mm Dia. x 102 mm L) 3’ (0.92 m) Capillary30 to+190°F (-1 to +88°C)
184-0006Remote Bulb Transmitter ¼” Dia. x 4” L (6 mm Dia. x 102 mm L) 3’ (0.92 m) Armored Capillary-40 to 120°F (-40 to +49°C)
184-0340Room Transmitter With Cover and wall plate50 to 100°F (10 to 38°C)
Action: Direct
Output Air Pressure: 3 to 15 psi (21 to 103 kPa)
Ambient Temperature Range: 40 to 120°F (4.4 to 49°C)
Input (supply) Air Pressure:
Restrictor Size: 40 scim (11 ml/s)
Calibration Pressure: 22± 1.0 psi (152± 6.9 kPa)
Maximum: 30 psi (207 kPa)
Thermal System:
Room: Bimetal
Rigid Bulb: Rod and tube
Remote Bulb: Liquid-filled
Air Consumption: 35 scim (10 ml/s)
Air Connections: 1/8" NPT (Except for room type)
Mounting:  
Room: Wall terminal
Rigid Bulb: Mounting flange
Remote Bulb: Mounting flange or well bracket mounting kit
Averaging Bulb: Mounting flange
Cover Finish :
Room: Desert Beige, plastic
Rigid, Averaging and Remote Bulb: Gray
Dimensions:
Room: 2.16" W x 3.35" H x 1.59" D (55 mm W x 85 mm H x 40 mm D)
Rigid Bulb/Remote Bulb: 1.875" W x 3" H x 1.69" D
(48 mm W x 76 mm H x 33 mm D)
Shipping Weights :
Room: 0.83 lb. (0.38 kg)
Rigid Bulb: 1.5 lb. (0.68 kg)
Remote Bulb: 2.0 lb. (0.91 kg)
Averaging Bulb with Armored Capillary: 3.0 lb. (1.36 kg)
Averaging Bulb: 2.0 lb. (0.91 kg)


Main menu 2