Jump to Navigation

Schneider Electric AKS-1100 Receiver Controller Setpoint Adjuster and Scale Plates

Receiver Controller Setpoint Adjuster and Scale Plates
AKS-1100

Setpoint adjuster and scale plates used to provide remote setpoint adjustment of RKS-2001, RKS- 4002, and RKSR-4000 receiver-controllers. May also be used to manually pilot pneumatic relays.

• Allows the setpoint of a pneumatic receiver-controller to be raised or lowered from a location up to 1000 ft. (305 m) from the receiver-controller.
• Series available to work with various transmitter ranges.
• A receiver gauge, mounted near the setpoint adjuster shows the actual result of remotely adjusting the receivercontroller’s setpoint.

Select a link under the "item" tab below to order.

Cat #Descriptions
AKS-1100Remote setpoint adjuster.
Construction: Aluminum housing, precision flapper-nozzle assembly.
Output: Linear 3 to 15 psig (21 to 102 kPa).
Air pressure: Clean, oil free, dry air required (reference EN-123).
Maximum 30 psig (207 kPa).
Ambient limits: Shipping temperatures -40 to 150°F (-40 to 65°C).
Operating temperatures 40 to 120°F (4 to 49°C).
Humidity 5 to 95% RH, non-condensing.
Air connection: Barbed connection for 1/4 in. O.D. plastic tubing.
Air consumption for sizing air
compressor:
41.5 scim (11.3 mL/s).
Air capacity for sizing air mains: 48 scim (13.1 mL/s).
Mounting: Panel or wall box. Panel requires 5/8 in. (16 mm) hole for mounting the remote setpoint adjuster.
Panel space required: 2-3/8 H x 2-1/4 W x 2-1/2 D in. (60 x 57 x 63 mm).
AKS-11xx scale plates (must be
ordered separately):
White letters on black background, keyed for proper locating on setpoint adjuster.


Main menu 2