Schneider Electric 2211 through 2218 Series Room Thermostats

Room Thermostats
2211 through 2218 Series

These pneumatic room thermostats are designed for proportional temperature control of pneumatic valves and damper actuators to maintain room air temperatures in heating, ventilating, and air conditioning systems.

• Small size, approximately 2 x 2 in. (51 x 51 mm).
• Factory calibrated. Stainless steel ball-in-seat provides pneumatic feedback for linear, stable operation.
• Easy-to-use throttling range adjustment and recalibration.
• Adjustable bimetal shows actual throttling range in both °F and °C. Adjustable 2 to 12°F (1 to 6.7°C).
• Setpoint (in both °F and °C) shown on thermostat body with cover removed.
• Leakproof, O-ring sealed, spring-loaded self-closing branch gauge tap.
• 2214 and 2216: - Separate factory-calibrated night bimetal and setpoint dial, with fixed 4 F° (2 C°) night throttling range for accurate “night” operation. - Snap-acting (not gradual) changeover from “day” to “night” operation and vice versa.
• 2216: - Third port (R) output with manual reset lever allows full restoration of day operation (typically, of unit ventilator), with either manual or automatic reset to day-night schedule.
• 2218: - Snap-acting (not gradual) changeover from direct-action to reverse-action and vice versa.

Select a link under the "item" tab below to order.

Cat #DescriptionsAir ConsumptionReplaces Model No.Dial Range °F (°C)
2211-012Single temperature, one-pipe, D.A.0.017 scfm at 20 psigT12-30155 to 85 (13 to 29)
2211-013Single temperature, one-pipe, R.A.0.017 scfm at 20 psigT13-30155 to 85 (13 to 29)
2212-118Single temperature, two-pipe, D.A., throttling range adjustable 2° to 12°.15.6 scim at 20 psigT18-30155 to 85 (13 to 29)
2212-119Single temperature, two-pipe, R.A., throttling range adjustable 2° to 12°.15.6 scim at 20 psigT19-30155 to 85 (13 to 29)
2212-618Single temperature, two-pipe, R.A., throttling range adjustable 2° to 12°.15.6 scim at 20 psig-55 to 85 (13 to 29)
2212-619Single temperature, two-pipe, R.A., throttling range adjustable 2° to 12° (includes 20-023).15.6 scim at 20 psig-55 to 85 (13 to 29)
2214-121Day-Night Thermostat, two-pipe, D.A. 16 psig day, 25 psig night.29.4 scim at 16 psigT23-301Day 55 to 85 (13 to 29)
2214-121Day-Night Thermostat, two-pipe, D.A. 16 psig day, 25 psig night.43.2 scim at 25 psigT23-301Night 50 to 80 (10 to 27)
2214-122Day-Night Thermostat, two-pipe, R.A. 16 psig day, 25 psig night29.4 scim at 16 psigT24-301Day 55 to 85 (13 to 29)
2214-122Day-Night Thermostat, two-pipe, R.A. 16 psig day, 25 psig night43.2 scim at 25 psigT24-301Night 50 to 80 (10 to 27)
2216-126Day-Night Thermostat, three-pipe, with manual reset lever D.A. 16 psig day, D.A. 25 psig night.29.4 scim at 16 psigT27-301Day 55 to 85 (13 to 29)
2216-126Day-Night Thermostat, three-pipe, with manual reset lever D.A. 16 psig day, D.A. 25 psig night.43.2 scim at 25 psigT27-301Night 50 to 80 (10 to 27)
2218-132Summer-Winter, throttling range adjustable 2° to 12°. 16 psig Main - R.A., Summer. 25 psig Main - D.A., Winter. (Can be used with 8 psig summer main if recalibrated in the field.)31.1 scim at 16 psigT32-30155 to 85 (13 to 29)
2218-132Summer-Winter, throttling range adjustable 2° to 12°. 16 psig Main - R.A., Summer. 25 psig Main - D.A., Winter. (Can be used with 8 psig summer main if recalibrated in the field.)43.2 scim at 25 psigT32-30155 to 85 (13 to 29)
2218-134Summer-Winter Thermostat for use with Honeywell 13 to 18 psig Systems. 13 psig Main - R.A., Summer. 18 psig Main - D.A., Winter.22.5 scim at 13 psigT32-32155 to 85 (13 to 29)
2218-134Summer-Winter Thermostat for use with Honeywell 13 to 18 psig Systems. 13 psig Main - R.A., Summer. 18 psig Main - D.A., Winter.34.5 scim at 18 psigT32-32155 to 85 (13 to 29)
2218-133Summer-Winter Thermostat for use with Johnson main air systems. 25 psig Main - R.A., Summer. 16 psig Main - D.A., Winter.29.4 scim at 15 psigT33-30155 to 85 (13 to 29)
2218-133Summer-Winter Thermostat for use with Johnson main air systems. 25 psig Main - R.A., Summer. 16 psig Main - D.A., Winter.34.5 scim at 20 psigT33-30155 to 85 (13 to 29)
Action: Proportional; refer to Model Chart.
Setpoint range: 55 to 85°F (13 to 29°C).
Throttling range: 2 to 12°F/12 psi (1.1 to 6.7°C/83 kPa) adjustable, factory set 3°F (1.7 °C) [night, 3 to 5°F/12 psi (1.7 to 2.7°C/83 kPa), non-adjustable].
Construction: Components Die cast aluminum, stainless steel, and glass-filled nylon.
Diaphragms Fabric-reinforced neoprene.
Air filter Internal.
Supply air pressure: Clean, dry, oil free air required (Refer to EN-123).
Nominal: Refer to Model Chart and Typical Applications.
Maximum: 30 psig (207 kPa).
Connections: For spring-reinforced 3/16 in. O.D. plastic tubing and required fittings.
Air consumption: Refer to Model Chart and Typical Applications.
Calibration point: 9 psig (62 kPa) branch line pressure when ambient temperature equals setpoint (except 2218-3x1 Series and 2218-133, 12 psig branch line pressure).
Setpoint adjustment: Serrated thumbwheel, external or concealed.
Mounting: Upright position on wall.
Dimensions: 2-1/32 H x 2-1/32 W x 1-3/8 D in. (52 x 52 x 35 mm).