Phoenix QUINT-PS-100-240AC/24DC/2.5 Single-Phase Primary-Switched Power Supply Unit

Phoenix
Single-Phase Primary-Switched Power Supply Unit
QUINT-PS-100-240AC/24DC/2.5

QUINT POWER devices are 60...960 W DC power supply units for universal use. This is ensured by the wide-range input, single and three-phase versions, and an international approval package.

QUINT POWER stands for guaranteed supply: powerful capacitors ensure mains buffering of more than 20 ms at full load.

All three-phase devices provide the full output power, even in the event of a continuous phase failure. The POWER BOOST power reserve starts loads with high inrush currents and ensures that fuses are reliably tripped. Preventive function monitoring diagnoses impermissible operating states and minimizes downtimes in your system. An active transistor output and a floating relay contact are used for remote monitoring.

Select a link under the "item" tab below to order.

ItemDescriptionTypePcs./Pkt.
29 38 57 8Single-phase primary-switched power supply unitQUINT-PS-100-240AC/24DC/2.51
29 38 19 6Assembly adapter for QUINT POWER 2.5 A and 5 A on S7 300 railsQUINT-PS-ADAPTERS7/11
Input data
Input nominal voltage range 100...240 V AC
AC input voltage range 85...264 V AC, 90...350 V DC
Frequency range 45...65 Hz (0 Hz at DC input)
Current consumption 0.86 A (at 120 V AC (nominal load)), approximately
0.47 A (at 230 V AC (nominal load)), approximately
Inrush current surge < 20 A (typical), inrush current limiting/Ι2t (25°C): < 2.2 A²s
Mains buffering (for nominal load) > 20 ms (at 120 V AC), > 100 ms (at 230 V AC)
Typical switch-on time < 1 s
Protective circuit Transient surge protection varistor
Input fuse 5 A (slow-blow, internal)
Recommended backup fuse Circuit breaker 6 A, 10 A or 16 A, Characteristic B
Discharge current to PE < 3.5 mA
Connection method COMBICON screw/plug-in connection
Stripping length 7 mm
Output data
Nominal output voltage 24 V DC ±1%
Setting range of the output voltage 22.5...28.5 V DC
Output current 2.5 A (-25...+60°C)
3.75 A (with POWER BOOST, -25...+40°C)
Derating Above +60°C: 2.5% per Kelvin
Maximum capacitive load Unlimited
System deviation < 1% (static load change 10...90%)
< 2% (dynamic load change 10...90%)
< 0.1% (input voltage change ±10%)
Power dissipation Maximum nominal load 10 W
Maximum no load 2 W
Efficiency > 86% for 230 V AC and nominal values
Rise time < 2 ms (UOUT (10...90%))
Residual ripple/switching peaks (20 MHz) < 100 mVpp (for nominal values)
Parallel connection Yes, to create redundant systems and increase efficiency
Internal surge protection Yes, limited to 35 V DC, approximately
Resistance to return supply 35 V DC
Connection method COMBICON screw/plug-in connection
Stripping length 7 mm
DC OK Signal Output, Active
Type of output Transistor output, Uout > 0.9 x UN: High signal
Continuous current 40 mA, maximum
Output voltage +24 V DC (signal)
DC OK Signal Output, Floating
Type of output Relay contact, Uout > 0.9 x UN: Contact closed
Continuous current 1 A, maximum
Maximum switching voltage 30 V AC/DC, maximum
General Data
Insulation voltage Input/output 4 kV AC (type test)/2 kV AC (routine test)
Input/PE 3.5 kV AC (type test)/2 kV AC (routine test)
Insulation voltage output/PE 500 V DC (routine test)
Mounting position On horizontal NS 35 DIN rail according to EN 60715
Degree of protection IP20
Protection class Ι, with PE connection
MTBF > 500,000 h according to IEC 61709 (SN 29500)
Housing version AluNox (AlMg1), closed
Weight 0.850 kg
Dimensions (width x height x depth) 55 mm x 130 mm x 125 mm
Dimensions (width x height x depth) for alternative assembly 122 mm x 130 mm x 58 mm
Status Indicators
DC OK status indicator Green LED (Uout < 0.9 x UN: LED flashes)
Climatic Data
Ambient temperature (operation) -25...+70°C (> 60°C derating)
Ambient temperature (storage/transport) -40...+85°C
Maximum permissible humidity (operation) 95% (at +25°C, no condensation)
Vibration (operation) < 15 Hz, amplitude ±2.5 mm according to IEC 60068-2-6
15...150 Hz, 2.3g, 90 minutes
Shock 30g in all space directions, according to IEC 60068-2-27
Pollution degree 2 according to EN 50178
Climatic class 3K3 according to EN 60721
Certification/Standards
Electrical equipment of machines EN 60204 (Surge Voltage Category III)
Safety transformers for switched-mode power supply units EN 61558-2-17
Electrical safety (of IT equipment) EN 60950/VDE 0805 (SELV), EN 61558-2-17
CB Scheme j
UL/C-UL Recognized UL 60950 u
Industrial control equipment UL/C-UL Listed UL 508 U
Electrical equipment for potentially explosive areas UL/C-UL Recognized UL 1604, Class Ι, Division 2, Groups A, B, C, D
Shipbuilding Germanischer Lloyd F, ABS
Electronic equipment for use in electrical power installations EN 50178 (VDE 0160)
Safety extra-low voltage PELV (EN 60204), SELV (EN 60950)
Safe isolation DIN VDE 0100-410, DIN VDE 0106-1010
Protection against electric shock DIN 57100-410
Protection against electric shock, basic requirements for safe isolation in electrical equipment DIN VDE 0106-101
Limitation of harmonic line currents According to EN 61000-3-2
Device safety (tested safety)