Jump to Navigation

Precision Digital PD6300 Pulse Input Dual-Line Flow Rate/Totalizers

Pulse Input Dual-Line Flow Rate/Totalizers
PD6300

The PD6300 ProVu meter is a 1/8 DIN flow rate/totalizer specifically designed for displaying flow rate and total from flowmeters with pulse outputs. These flow rate/totalizers are particularly well-suited for flow applications because they can display flow rate and flow total at the same time, provide power to drive the

• Pulse, Open Collector, NPN, PNP, TTL, Switch
• Contact, Sine Wave (Coil), Square Wave Inputs
• 5, 10 or 24 VDC Flowmeter Power Supply
• Gate Function for Rate Display of Slow Pulse Rates
• K-Factor, Internal Scaling, or External Calibration
• 4-20 mA Output Option Converts the Pulse Input toan Isolated 4-20 mA Output

COMMON RATE/TOTALIZER FEATURES
• Display Rate & Total at the Same Time
• Rate in Units per Second, Minute, Hour, or Day
• Total, Grand Total or Non-Resettable Grand Total
• Password Protection for Total Reset
• 9-Digit Totalizer with Total Overflow Feature
• Any Relay for Rate or Total
• 4-20 mA Output for Rate or Total
• Sampling Relay
• Total Stored in Non-Volatile Memory

Select a link under the "item" tab below to order.

Cat #Descriptions
PD6300-6R0ProVu Pulse Input Dual-line Flow Rate/Totalizer; No Options; Powered from 85- 265 VAC
PD6300-6R2ProVu Pulse Input Dual-line Flow Rate/Totalizer; 2 Relays; Powered from 85-265 VAC
PD6300-6R3ProVu Pulse Input Dual-line Flow Rate/Totalizer; 4-20 mA Output; Powered from 85-265 VAC
PD6300-6R4ProVu Pulse Input Dual-line Flow Rate/Totalizer; 4 Relays; Powered from 85-265 VAC
PD6300-6R7ProVu Pulse Input Dual-line Flow Rate/Totalizer; 4 Relays + 4-20 mA Output ; Powered from 85-265 VAC
PD6300-7R0ProVu Pulse Input Dual-line Flow Rate/Totalizer; No Options; Powered from 12-24 VDC
PD6300-7R2ProVu Pulse Input Dual-line Flow Rate/Totalizer; 2 Relays; Powered from 12-24 VDC
PD6300-7R3ProVu Pulse Input Dual-line Flow Rate/Totalizer; 4-20 mA Output; Powered from 12-24 VDC
PD6300-7R4ProVu Pulse Input Dual-line Flow Rate/Totalizer; 4 Relays; Powered from 12-24 VDC
PD6300-7R5ProVu Pulse Input Dual-line Flow Rate/Totalizer; 2 Relays + 4-20 mA Output; Powered from 12-24 VDC
PD6300-7R7ProVu Pulse Input Dual-line Flow Rate/Totalizer; 4 Relays + 4-20 mA Output; Powered from 12-24 VDC
General
Display: Main display: 0.60" (15 mm) high, second display: 0.46" (12 mm) high. Both displays are 6 digits (-99999 to 999999), red LEDs with leading zero blanking
Display Intensity: Eight user selectable intensity levels
Overrange: Display flashes 999999
Underrange: Display flashes -99999
Front Panel: NEMA 4X, IP65
Programming Methods: Four front panel buttons, digital inputs, PC and multi-point linearization utility, or cloning using Copy function
Recalibration: All ranges are calibrated at the factory. Recalibration is recommended at least every 12 months
Max/Min Display: Max (Peak) / min (Valley) readings reached by the process are stored until reset by the user or until power to the meter is turned off
Password: Three programmable passwords restrict modification of programmed settings and two prevent resetting the totals. Pass 1: Allows use of the F1–F3 function keys. Pass 2: Allows use of the F1–F3 function keys and changing the set/reset points. Pass 3: Restricts all programming and F1–F3 keys. Total: Prevents resetting the total manually. Gtotal: Prevents resetting the grand total manually
Non-Volatile Memory: All programmed settings are stored in non-volatile memory for a minimum of ten years if power is lost
Power Options: 85-265 VAC 50/60 Hz, 90-265 VDC 20 W max, or jumper selectable 12/24 VDC ±10%, 15 W max.
Fuse: Required external fuse: UL Recognized, 5 A max, slow blow; up to 6 meters may share one 5 A fuse
Isolated Transmitter Power Supply: Terminals P+ & P-: 24 VDC ± 5% @ 200 mA max (standard), (12/24 VDC powered models rated @ 100 mA max). 5 or 10 VDC @ 50 mA max, selectable with internal jumper J4
Isolation: 4 kV input/output-to-power line. 500 V input-to-output or output-to-P+ supply
Environmental: Operating temperature range: -40 to 65°C. Storage temperature range: -40 to 85°C. Relative humidity: 0 to 90% non-condensing
Connections: Removable screw terminal blocks accept 12 to 22 AWG wire, RJ45 for external relays, digital I/O, and serial communication adapters
Enclosure: 1/8 DIN, high impact plastic, UL 94V-0, color: black
Mounting: 1/8 DIN panel cutout required: 3.622" x 1.772"(92 mm x 45 mm). Two panel mounting bracket assemblies are provided
Tightening Torque: Screw terminal connectors: 5 lb-in (0.56 Nm)
Overall Dimensions: 4.68" x 2.45" x 5.64" (119 mm x 62 mm x 143 mm) (W x H x D)
Weight: 9.5 oz (269 g)
UL File Number: UL & c-UL Listed. E160849; 508 Industrial Control Equipment
Warranty: 3 years parts & labor