Jump to Navigation

Precision Digital PD6000 Dual-line 6-digit process meters

Dual-line 6-digit process meters
PD6000

The ProVu meter boasts specifications and functionality that clearly makes it one of the most advanced process meters available. Its dual-line 6-digit display (999,999), advanced math functions, function keys, and optional expansion modules are only a few of the features you will find on the ProVu.

Front Panel Display
Precise, Accurate, and More Informative
    ProVu’s large 0.6 main display will provide you with a highly accurate and precise 6-digit view of your process. Its 24-bit A/D is accurate to ±0.03% of calibrated span ±1 count.

Configurable
    The main display can be programmed to indicate PV, maximum (peak), minimum (valley), alternating maximum/ minimum, or one of eight alarm set points. The secondary display can also be configured to display engineering units, setpoints, user defined legends, or simply turned off.

Function Keys
    There are three function keys available to the user. These keys can be programmed to trigger certain events (i.e. acknowledge alarms, reset max and/or min, disable/enable output relays, or hold current relay states), provide direct menu access points, and more.

Rugged

    A unique front panel design makes the ProVu nearly impenetrable in typical applications. Here, the ProVu easily survives a direct hit on the display from a heavy 2 solid stainless steel ball dropped from eight feet.

Easy to Use
    The user friendly dual-line display makes the ProVu easy to set up & program. No jumpers to set for input selection. All setup & programming is done via the front panel. Three levels of password protection help maintain the reliability of the programming.

• 0-20 mA, 4-20 mA, 0-5 V, 1-5 V, and ±10 V Inputs
• NEMA 4X, IP65 Front
• Universal 85-265 VAC or 12/24 VDC Input Power
• Large Dual-Line 6-Digit Display, 0.60 & 0.46
• Isolated 24 VDC @ 200 mA Transmitter Power Supply
• Math Functions for Flow & Round Horizontal Tanks
• Programmable Displays & Function Keys
• Sunlight Readable Display
• 32-Point, Square Root, or Exponential Linearization
• Multi-Pump Alternation Control
• 2 or 4 Relays + Isolated 4-20 mA Output Options
• External 4-Relay & Digital I/O Expansion Modules
• RS-232, RS-422/485 Serial Communication Options
• -40 to 65°C Operating Temperature Range

Select a link under the "item" tab below to order.

Cat #TypeOptions Installed
PD6000-6R085-265 VAC ModelNone
PD6000-6R285-265 VAC Model2 Relays
PD6000-6R385-265 VAC Model4-20 mA Output
PD6000-6R485-265 VAC Model4 Relays
PD6000-6R585-265 VAC Model2 Relays & 4-20 mA Output
PD6000-6R785-265 VAC Model4 Relays & 4-20 mA Output
PD6000-7R012/24 VDC ModelNone
PD6000-7R212/24 VDC Model2 Relays
PD6000-7R312/24 VDC Model4-20 mA Output
PD6000-7R412/24 VDC Model4 Relays
PD6000-7R512/24 VDC Model2 Relays & 4-20 mA Output
PD6000-7R712/24 VDC Model4 Relays & 4-20 mA Output
General
Display: Main display: 0.60" (15 mm) high, second display: 0.46" (12 mm) high. Both displays are 6 digits (-99999 to 999999), red LEDs with leading zero blanking.
Display Intensity: Eight intensity levels
Display Update Rate: 5/second (200 ms)
Overrange: Display flashes 999999
Underrange: Display flashes -99999
Front Panel: NEMA 4X, IP65
Programming Methods: Four front panel buttons, PC based linearization utility, cloning using Copy function, or via digital inputs.
Noise filter: Programmable from 2 to 199 (0 will disable filter)
Filter Bypass: Programmable from 0.1 to 99.9% of calibrated span
Recalibration: Calibrated at the factory. Recalibration is recommended at least every 12 months.
Max/Min Display: Max (Peak) / min (Valley) readings reached by the process are stored until reset by the user or until power to the meter is turned off.
Non-Volatile Memory: All programmed settings are stored in nonvolatile memory for a minimum of ten years if power is lost.
Power Options: 85-265 VAC 50/60 Hz, 90-265 VDC 20 W max, or
jumper selectable 12/24 VDC ±10%, 15 W max.
Fuse: Required external fuse: UL Recognized, 5 A max, slow blow; up to 6 meters may share one 5 A fuse.
Isolated Transmitter Power Supply: 5, 10, or 24 VDC selectable by internal jumper. 24 VDC ± 10% supply rated @ 200 mA max (100 mA max for 12/24 VDC powered models). The 5 or 10 VDC supplies rated @ 50 mA max.
Normal Mode Rejection: Greater than 60 dB at 50/60 Hz
Isolation: 4 kV input/output-to-power line. 500 V input-to-output or output-to-P+ supply.
Environmental: Operating temperature range: -40 to 65°C. Storage temperature range: -40 to 85°C. Relative humidity: 0 to 90% non-condensing.
Connections: Removable screw terminal blocks accept 12 to 22 AWG wire, RJ45 for external relays, digital I/O, and serial communication adapters.
Enclosure: 1/8 DIN, high impact plastic, UL 94V-0, color: black
Mounting: 1/8 DIN panel cutout required: 3.622" x 1.772" (92 mm x 45 mm). Two panel mounting bracket assemblies are provided.
Tightening Torque: Screw terminal connectors: 5 lb-in (0.56 Nm)
Overall Dimensions: 4.68" x 2.45" x 5.64" (119 mm x 62 mm x 143 mm) (W x H x D)
Weight: 9.5 oz (269 g)
UL File Number: UL & c-UL Listed. E160849; 508 Industrial Control Equipment.
Warranty: 3 years parts & labor