Jump to Navigation

Precision Digital F030 Fluidwell Batch Controllers

Fluidwell Batch Controllers
F030

The F030 is a straight forward but basic Batch Controller. The operator can enter a batch quantity easily or execute repeating batches. During the batch, the preset value is displayed as well as the batched (or remaining) quantity and the units of measurement. The automatic self-learning overrun correction will ensure an accurate result each batch again. A wide selection of options further enhance this models capabilities, including Intrinsic Safety.

Display
The display has large 17mm (0.67 ) and 8mm (0.31 ) digits which are used to display the batched quantity and the preset value simultaneously. On-screen engineering units are easily configured from a comprehensive selection. A seven digit resettable day total is available as well as an eleven digit non-resettable accumulated total. All are backed-up in EEPROM memory every minute. A smart display update function achieves a readable display even at -40°C / -40°F.

Backlight 
For those applications where readability during day and night is an issue, a bi-color backlight is available. The background color green or amber and the intensity can be adjusted from the keyboard. The display is a transflective type, which means that a high contrast reading is guaranteed in full sunlight as well as during the night. This backlight option is available Intrinsically Safe.

Configuration 
All configuration settings are accessed via a simple operator menu which can be pass-code protected. Each setting is clearly indicated with an alphanumerical description, therefore avoiding confusing abbreviations. Once familiar with one F-series product, you will be able to program all models in the series without a manual. All settings are safely stored in EEPROM memory in the event of sudden power failure.

Control Output 
One output is available for one stage control of smaller batches. The output signal can be a passive NPN or an active PNP transistor, or an isolated electro-mechanical relay. Signal Input The F030 will accept most pulse and analog input signals for flow or mass flow measurement. The input signal type can be selected by the user in the configuration menu without having to adjust any sensitive mechanical dip-switches, jumpers or trimmers. The analog input version is even available as 4 - 20mA input loop powered display.

Power Supply 
Several power supply options are available to power the F030 and sensor. Also a battery powered version with a long life lithium battery which will last up to five years. For analog sensors, a 4 - 20mA loop powered version is available as well. A real sensor supply is offered with the 24V AC / DC or 115 - 230V AC power supply option.

Hazardous Area 
For hazardous area applications, this model has been ATEX, IECEx, FM and CSA certified Intrinsically Safe for gas and applications, with an allowed operational temperature of -40°C to +70°C (-40°F to +158°F). A flame proof enclosure with ATEX certification offers the rating II 2 GD EExd IIB T5.

Enclosures 
Various types of enclosures can be selected, all ATEX, IECEx, FM and CSA approved. As standard the F030 is supplied in an GRP panel mount enclosure. Most popular is our aluminum field mount enclosure with IP67 / NEMA 4X rating. Both European or U.S. cable gland entry threads are available.

● Large display shows preset value and running batch value simultaneously.
● Self-learning overrun correction.
● Easy operation to enter a batch value and to control the process.
● Count-up and count-down function available.
● Selectable on-screen engineering units; volumetric or mass.
● Ability to process all types of flowmeter signals.
● Operational temperature -40°C up to +80°C (-40°F up to 178°F).
● Rugged aluminum field mount enclosure IP67/NEMA 4X.
● Intrinsically Safe - ATEX, IECEx, FM and CSA approval for gas and dust applications.
● Explosion/flame proof II 2 GD EEx d IIB T5.
● LED backlight option.
● Loop or battery powered, 8 - 24V AC/DC or 115 - 230V AC power supply.
● Sensor supply 3.2 / 8.2 / 12 / 24V DC.

Select a link under the "item" tab below to order.

Cat #DescriptionsType
A(0)4 - 20mA inputSensor Input Signal
PPulse input coil, npn, pnp, namur, reed-switchSensor Input Signal
U0 - 10V DC inputSensor Input Signal
HBAluminum enclosurePanel Mount Enclosures - IP65 / NEMA 4
HCGRP enclosurePanel Mount Enclosures - IP65 / NEMA 4
HDCable entry no holesGRP Field / Wall Mount Enclosures - IP67 / NEMA 4X
HECable entry 2 x 16mm & 1 x 20mmGRP Field / Wall Mount Enclosures - IP67 / NEMA 4X
HFCable entry 1 x 22mm (7/8”)GRP Field / Wall Mount Enclosures - IP67 / NEMA 4X
HGCable entry 2 x 20mmGRP Field / Wall Mount Enclosures - IP67 / NEMA 4X
HHCable entry 6 x 12mmGRP Field / Wall Mount Enclosures - IP67 / NEMA 4X
HJCable entry 3 x 22mm (7/8”)GRP Field / Wall Mount Enclosures - IP67 / NEMA 4X
HKFlat bottom, cable entry no holesGRP Field / Wall Mount Enclosures - IP67 / NEMA 4X
HACable entry 2 x PG9 + 1 x M20Aluminum Field Wall Mount Enclosures - IP67 NEMA 4X
HMCable entry 2 x M16 + 1 x M20Aluminum Field Wall Mount Enclosures - IP67 NEMA 4X
HNCable entry 1 x M20Aluminum Field Wall Mount Enclosures - IP67 NEMA 4X
HOCable entry 2 x M20Aluminum Field Wall Mount Enclosures - IP67 NEMA 4X
HPCable entry 6 x M12Aluminum Field Wall Mount Enclosures - IP67 NEMA 4X
HTCable entry 1 x 1/2” NPTAluminum Field Wall Mount Enclosures - IP67 NEMA 4X
HUCable entry 3 x 1/2” NPTAluminum Field Wall Mount Enclosures - IP67 NEMA 4X
HVCable entry 4 x M20Aluminum Field Wall Mount Enclosures - IP67 NEMA 4X
HZCable entry no holesAluminum Field Wall Mount Enclosures - IP67 NEMA 4X
HSSilicone free ABS field enclosure IP65 – Cable entry: no holes (old HD enclosure)HS
OAOne active transistor output - requires PF or PMOutput
OROne mechanical relay output - requires PF or PMOutput
OTOne passive transistor output - standard configurationOutput
PBLithium battery poweredPower Supply
PCLithium battery powered - Intrinsically SafePower Supply
PD16 - 30V DC + sensor supplyPower Supply
PF24V AC DC + sensor supplyPower Supply
PLInput loop powered from sensor signal 4 - 20mA (type A)Power Supply
PM115 - 230V AC + sensor supplyPower Supply
PXBasic power supply 8 - 30V DC (no real sensor supply)Power Supply
XIIntrinsically SafeHazardous Area
XFEExd enclosure - 3 keysHazardous Area
XXSafe area onlyHazardous Area
ZBBacklightOther Options
ZFCoil input 10mVppOther Options
ZGCoil input 5mVppOther Options
ZXNo optionsOther Options
Display
Type: High intensity reflective numeric and alphanumeric LCD, UV-resistant.
Dimensions: 90 x 40mm (3.5" x 1.6").
Front Panel: Seven 17mm (0.67") and eleven 8mm (0.31") digits. Various symbols and measuring units.
Refresh rate: User definable: 8 times/sec. - 30 secs - off.
Option ZB: Transflective LCD with bi-color LED-backlight; green / amber. Intensity and color selected through the keyboard. Good readings in full sunlight and darkness. Also available Intrinsically Safe.
Operating Temperature
Standard Unit: -40°C to +80°C (-40°F to +178°F).
Intrinsically Safe: -40°C to +70°C (-40°F to +158°F).
Power Requirements
Type PB: Long life Lithium battery - life-time depends upon settings and configuration - up to 5 years.
Type PC: Intrinsically Safe long life lithium battery - life-time depends upon settings and configuration - up to 5 years.
Type PD: 16 - 30V DC. Power consumption max. 1 Watt.
Type PF: 24V AC / DC ± 10%. Power consumption max. 15 Watt.
Type PL: Input loop powered from sensor signal 4 - 20mA (type A).
Type PM: 115 - 230V AC ± 10%. Power consumption max. 15 Watt.
Type PX: 8 - 30V DC. Power consumption max. 0.3 Watt.
Type ZB: 20 - 30V DC. Power consumption max. 1 Watt. With type PF / PM: internally powered.
Note PB/PF/PM Not available Intrinsically Safe
Note PF/PM The total consumption of the sensor, active output type OA and backlight type ZB may not exceed 400mA @ 24V DC
Note For Intrinsically Safe applications, consult the safety values in the certificate
Sensor Excitation
Type PB/PC/PX: 3.2V DC for pulse signals and 1.2V DC for coil pick-up.
Note This is not a real sensor supply. Only suitable for sensors with a very low power consumption like coils (sine wave) and reed-switches.
Type PD: for pulse signals: 1.2 / 3.2 / 8.2V DC - max. mA@8.2V DC. For analog signals, the sensor supply voltage is according to the power supply voltage connected.
Type PF / PM: With pulse input: 1.2 / 3.2 / 8.2 / 12 / 24V DC - max. 400mA @ 24V DC. With analog input: 8.2 / 12 / 24V DC - max. 400mA @ 24V DC.
Terminal Connections
Type: Removable plug-in terminal strip. Wire max. 1.5mm2 and 2.5mm2.
Data Protection
Type: EEPROM backup of all settings. Backup of running totals every minute. Data retention at least 10 years.
Pass-code: Configuration settings can be pass-code protected.
Casing
Window: Polycarbonate window.
Sealing: Silicone.
Control Keys: Three industrial micro-switch keys. UV-resistant silicone keypad.
Aluminum Wall / Field Mount Enclosures
General: Die-cast aluminum wall/field mount enclosure IP67 / NEMA 4X with 2-component UV-resistant coating.
Dimensions: 130 x 120 x 75mm (5.12" x 4.72" x 2.95") - W x H x D.
Weight: 1100 grams/2.42 lbs
Type HA: Cable entry: 2 x PG9 and 1 x M20.
Type HM: Cable entry: 2 x M16 and 1 x M20.
Type HN: Cable entry: 1 x M20.
Type HO: Cable entry: 2 x M20.
Type HP: Cable entry: 6 x M12.
Type HT: Cable entry: 1 x 1/2" NPT.
Type HU: Cable entry: 3 x 1/2" NPT.
Type HV: Cable entry: 4 x M20.
Type HZ: Cable entry: no holes.
GRP Wall / Field Mount Enclosures
General: GRP wall/field mount enclosure IP67 / NEMA 4X, UV-resistant and flame retardant.
Dimensions: 130 x 120 x 75mm (5.12" x 4.72" x 2.95") - W x H x D.
Weight: 600 grams/1.33 lbs
Type HD: Cable entry: no holes.
Type HE: Cable entry: 2 x Ø 16mm and 1 x Ø 20mm.
Type HF: Cable entry: 1 x Ø 22mm (7/8").
Type HG: Cable entry: 2 x Ø 20mm.
Type HH: Cable entry: 6 x Ø 12mm.
Type HJ: Cable entry: 3 x Ø 22mm (7/8").
Type HK: Flat bottom, cable entry: no holes.
Panel Mount Enclosures
Dimensions: 130 x 120 x 60mm (5.12" x 4.72" x 2.36") - W x H x D.
Panel cut-out: 115 x 98mm (4.53" x 3.86") L x H.
Type HB: Die-cast aluminum panel mount enclosure IP65 / NEMA 4.
Weight: 600 grams/1.33 lbs
Type HC: GRP panel mount enclosure IP65 / NEMA 4, UV-resistant and flame retardant.
Weight: 450 grams/1 lb
ABS Wall / Field Mount Enclosures
General: Silicone free ABS wall/field mount enclosure IP65 with EPDM and PE sealings. UV-resistant polyester keypad (old HD enclosure).
Dimensions: 130 x 114 x 71mm (5.1" x 4.5" x 2.8") - W x H x D.
Weight: 450 grams/1 lb
Type HS: Cable entry: no holes.
Intrinsically Safe
ATEX Certification: II 1 G Ex ia IIC T4. II 1 D Ex iaD 20 IP 65 / 67 T 100 °C.
IECEx Certification: Ga Ex ia IIC T4. Ex iaD 20 IP 65 / 67 T 100 °C.
CSA c-us Certification: Intrinsically Safe for Class I/II/III, Div. 1, Groups A, B, C, D, E, F, G, Temp. class T4 and Class I, Zone 0, AEx ia IIC T4.
FM certification: Intrinsically Safe for Class I/II/III, Div. 1, Groups A, B, C, D, E, F, G, Temp. class T4 and Class I, Zone 0, AEx ia IIC T4.
Ambient: -40°C to +70°C / -40° to +158°F.
Hazardous Area
Intrinsically Safe Type XI: ATEX approval ref.: II 1 GD EEx ia IIB/IIC T4 T100°C. Maximum ambient +70° C (158°F).
Explosion proof Type XF: ATEX approval ref.: II 2 GD EEx d IIB T5. Dimensions of enclosure: 300 x 250 x 200mm (11.8" x 9.9" x 7.9") L x H x D.
Weight: Appr. 15kg/33 lbs
Environment
Electromagnetic compatibility: Compliant ref: EN 61326 (1997), EN 61010-1 (1993)
Signal Input
Type P: Coil / sine wave (minimum 20mVpp or 80mVpp - sensitivity selectable), NPN/PNP, open collector, reedswitch, Namur, active pulse signals 8 - 12 and 24V DC.
Frequency: Minimum 0Hz - maximum 7kHz for total and flow rate. Maximum frequency depends on signal type and internal low-pass filter. E.g. reed switch with low-pass filter: max. frequency 120Hz.
K-Factor: 0.000010 - 9,999,999 with variable decimal position.
Low-pass: Filter Available for all pulse signals.
Option ZF: coil sensitivity 10mVpp.
Option ZG: coil sensitivity 5mVpp.
Type A: (0)4 - 20mA. Analog input signal can be scaled to any desired range within 0 - 20mA.
Type U: 0 - 10V DC. Analog input signal can be scaled to any desired range within 0 - 10V DC.
Accuracy: Resolution 16 bit. Error < 0.01mA / ± 0.05% FS. Low level cut-off programmable.
Span: 0.001 / 999,999 with variable decimal position.
Update time: Four times per second
Voltage drop: Type A: max. 2V DC @ 20mA
Load impedance: Type U: 3kΩ
Relationship: Linear and square root calculation
Signal Output
Function: Control output according to the batch process.
Type OA: One active 24V DC transistor output (PNP); load max. 400mA (requires PF or PM).
Type OR: One electro-mechanical relay output - isolated; max. switch power 230V AC (N.O.) - 0.5A (requires PF
or PM).
Type OT: One passive transistor output (NPN) - not isolated. Max. 50V DC - 300mA per output.
Operational
Displayed functions: • Preset value - can be entered by the operator.
• Batched quantity or remaining quantity.
• Total and accumulated total.
• Total can be reset to zero by pressing the STOP-key twice.
Preset and Total
Digits: 7 digits
Units: L, m3, GAL, USGAL, KG, lb, bbl, no unit
Decimals: 0 - 1 - 2 or 3
Accumulated Total
Digits: 11 digits
Units / decimals: According to selection for total
Note Cannot be reset to zero


Main menu 2