Jump to Navigation

Johnson Controls TEC226x-4(+PIR) and TEC220x-4(+PIR) Series LONWORKS® Network Staged Thermostat Controllers

LONWORKS® Network Staged Thermostat Controllers
TEC226x-4(+PIR) and TEC220x-4(+PIR) Series

The TEC226x-4(+PIR) Series Programmable and TEC220x-4(+PIR) Series Non-Programmable LONWORKS® Network Configurable Staged Thermostat Controllers provide control of rooftop units (with and without economizers), heat pumps, and single- and multi-stage heating/cooling equipment. The TEC226x-4+PIR and TEC220x-4+PIR Series Thermostat Controllers have occupancy sensing capability built into the device. These devices provide energy savings in high-energy usage light commercial buildings such as schools and hotels. The devices maximize these energy savings by using additional setpoint strategies during occupied times.

The technologically advanced TEC226x-4(+PIR) and TEC220x-4(+PIR) Series Thermostat Controllers feature a Building Automation System (BAS) LONWORKS Network communication capability that enables remote monitoring and programming for efficient space temperature control.

The TEC226x-4(+PIR) and TEC220x-4(+PIR) Series Thermostat Controllers use an intuitive, plain text, menu-driven, backlit display that makes setup and operation quick and easy. The TEC220x-4+PIR and TEC226x-4+PIR Series includes four models, each include the option of a PIR occupancy sensing cover:
     • Single-stage (TEC22x1-4 and TEC22x1-4+PIR)
     • Heat Pump (TEC22x2-4 and TEC22x2-4+PIR)
     • Multi-stage (TEC22x3-4 and TEC22x3-4+PIR)
     • Economizer (TEC22x4-4 and TEC22x4-4+PIR)

All thermostat controllers use a unique, Proportional-Integral (PI) time-proportioning control algorithm that virtually eliminates temperature offset associated with traditional differential-based thermostat controllers

• LONWORKS network communication — provides compatibility with a proven communication network; LONWORKS Network is widely accepted by Heating, Ventilating, and Air Conditioning (HVAC) control suppliers
• onboard occupancy sensor (Passive Infrared [PIR] models) — provides energy savings without additional installation time and cost
• password protection option — protects against unwanted thermostat controller tampering
• backlit Liquid Crystal Display (LCD) — offers real-time control status of the environment in easy-to-read, English text messages with constant backlight that brightens during user interaction
• simplified setpoint adjustment — enables the user to change the setpoint by simply pressing the UP/DOWN arrow keys
• five easy-to-use interface keys — allow for easy commissioning of the thermostat, and eliminate the need for DIP switches
• two configurable digital inputs — provide additional inputs for advanced functions such as remote night setback, occupancy override, and service or filter alarms
• over 20 configurable parameters — enable the thermostat to adapt to any application, allowing installer parameter access without opening the thermostat cover
• optional discharge air sensor — monitors unit efficiency
• economizer output (TEC22x4-4 and TEC22x4-4+PIR models) — provides control of economizer operation for singleand multi-stage unitary rooftop equipment
• configurable auxiliary output — provides 24 VAC control for lighting, exhaust fans, and other auxiliary functions

Select a link under the "item" tab below to order.

Cat #DescriptionsApplication:Programmable
TEC2261-4Single-StageUnit Heaters and Single-Stage Packaged Heating/Cooling EquipmentYes
TEC2201-4Single-StageUnit Heaters and Single-Stage Packaged Heating/Cooling EquipmentNo
TEC2261-4+PIRSingle-Stage with Onboard Occupancy SensorUnit Heaters and Single-Stage Packaged Heating/Cooling EquipmentYes
TEC2201-4+PIRSingle-Stage with Onboard Occupancy SensorUnit Heaters and Single-Stage Packaged Heating/Cooling EquipmentNo
TEC2262-4Heat PumpHeat Pumps with up to 3 Heating/2 Cooling StagesYes
TEC2202-4Heat PumpHeat Pumps with up to 3 Heating/2 Cooling StagesNo
TEC2262-4+PIRHeat Pump with Onboard Occupancy SensorHeat Pumps with up to 3 Heating/2 Cooling StagesYes
TEC2202-4+PIRHeat Pump with Onboard Occupancy SensorHeat Pumps with up to 3 Heating/2 Cooling StagesNo
TEC2263-4Multi-StageMulti-Staged Packaged Heating/Cooling EquipmentYes
TEC2203-4Multi-StageMulti-Staged Packaged Heating/Cooling EquipmentNo
TEC2263-4+PIRMulti-Stage with Onboard Occupancy SensorMulti-Staged Packaged Heating/Cooling EquipmentYes
TEC2203-4+PIRMulti-Stage with Onboard Occupancy SensorMulti-Staged Packaged Heating/Cooling EquipmentNo
TEC2264-4Multi-Stage, EconomizerEconomizer Operation for Single- and Multi-Stage Unitary Rooftop EquipmentYes
TEC2204-4Multi-Stage, EconomizerMulti-Stage, Economizer with Onboard Occupancy SensorEconomizer Operation for Single- and Multi-Stage Unitary Rooftop EquipmentNo
TEC2264-4+PIRMulti-Stage, Economizer with Onboard Occupancy SensorEconomizer Operation for Single- and Multi-Stage Unitary Rooftop EquipmentYes
TEC2204-4+PIRMulti-Stage, Economizer with Onboard Occupancy SensorEconomizer Operation for Single- and Multi-Stage Unitary Rooftop EquipmentNo
Power Requirements 19 to 30 VAC, 50/60 Hz, 2 VA (Terminals RC and C) at 24 VAC nominal, Class 2 or Safety Extra-Low Voltage (SELV)
Relay Contact Rating 19 to 30 VAC, 1.0 A Maximum, 15 mA Minimum, 3.0 A In-Rush, Class 2 or SELV
Analog Inputs Resistive Inputs (RS and UI3) for 10k ohm Johnson Controls Type II Negative Temperature Coefficient (NTC)
Thermistor Sensors
Digital Inputs Voltage-Free Contacts across Terminal C to Terminals DI1 and DI2
Economizer Output
(TEC22x4-4 and
TEC22x4-4+PIR
Models)
Rating 0 to 10 VDC into 2k ohm resistance minimum
Accuracy ±3%
Wire Size Unshielded Twisted Pair - 22 AWG (0.6 mm Diameter) Minimum, 18 AWG (1.0 mm Diameter) Recommended
Temperature Sensor Type Local 10k ohm Type II NTC Thermistor
LONWORKS Network Standard 64 Devices Maximum without repeater, 128 Devices Maximum with repeater; 6,250 ft (1,905 m) Maximum
Length (Bus Topology)
Wire Size 18 AWG (1.0 mm Diameter) Maximum, 22 AWG (0.6 mm Diameter) Recommended
Temperature Range Backlit Display -40.0°F/-40.0°C to 122.0°F/50.0°C in 0.5° Increments
Heating Control 40.0°F/4.5°C to 90.0°F/32.0°C
Cooling Control 54.0°F/12.0°C to 100.0°F/38.0°C
Accuracy Temperature ±0.9F°/±0.5C° at 70.0°F/21.0°C Typical Calibrated
Minimum Deadband 2F°/1C° between Heating and Cooling
Ambient Conditions Operating 32 to 122°F (0 to 50°C); 95% RH Maximum, Noncondensing
Storage -22 to 122°F (-30 to 50°C); 95% RH Maximum, Noncondensing
Compliance United States UL Listed, File E27734, CCN XAPX,
Under UL 873, Temperature Indicating and Regulating Equipment
FCC Compliant to CFR 47, Part 15, Subpart B, Class A
LONMARK® Certification 3.4
Canada UL Listed, File E27734, CCN XAPX7,
Under CAN/CSA C22.2 No. 24, Temperature Indicating and Regulating Equipment
Industry Canada, ICES-003
Europe CE Mark, EMC Directive 2004/108/EC
EN 61000-6-1 and EN 61000-6-3
Australia and New Zealand C-Tick Mark, Australia/NZ Emissions Compliant
Shipping Weight TEC226x-4 and TEC220x-4 Models: 0.75 lb (0.34 kg)
TEC226x-4+PIR and TEC220x-4+PIR Models: 0.77 lb (0.35 kg)


Main menu 2