Johnson Controls TEC200x-4 and TEC200x-4+PIR Series Series Wireless Thermostat Controller

Series Wireless Thermostat Controller
TEC200x-4 and TEC200x-4+PIR Series

The TEC200x-4 and TEC200x-4+PIR Series Wireless Thermostat Controller System provides wireless networked control of Heating, Ventilating, and Air Conditioning (HVAC) equipment on a Building Automation System (BAS) that enables remote monitoring and programming.

The TEC200x-4+PIR Series Wireless Thermostat Controllers have occupancy sensing capability built into the device. These devices provide energy savings in high-energy usage light commercial buildings such as schools and hotels. The devices maximize these energy savings by using additional setpoint strategies during occupied times.

This system integrates into a supervisory controller that uses BACnet® Internet Protocol (IP) or BACnet Master-Slave/Token-Passing (MS/TP) communications.

TEC20 Coordinators allow the supervisory controller to communicate with multiple TEC Wireless Thermostat Controllers. The TEC200x-4 and TEC200x-4+PIR Series Wireless Thermostat Controllers provide networked control of a variety of staged equipment:
     • TEC2001-4(+PIR) Single-Stage Wireless Thermostat Controllers control fan coil units, unit heaters, and single-stage packaged heating/cooling equipment
     • TEC2002-4(+PIR) Heat Pump Wireless Thermostat Controllers control heat pumps with up to three heating and two cooling stages
     • TEC2003-4(+PIR) Multi-Stage Wireless Thermostat Controllers control multi-stage packaged heating/cooling equipment
     • TEC2004-3(+PIR) Multi-Stage Economizer Wireless Thermostat Controllers control economizer operation for single- and multi-stage unitary rooftop equipment.

The wireless mesh network uses ZigBee™ technology to enable remote monitoring and programming and to enhance reliability by providing redundant transmission paths through other TEC200x-4 and TEC200x-4+PIR Wireless Thermostat Controllers, creating a resilient, self-healing mesh network.

• wireless communication — allows BAS communications capability in applications where field bus wiring within the building is prohibitive
• integral wireless signal strength testing built into wireless thermostat controllers and coordinators — provides quick, easy, visual indication of the wireless Radio Frequency (RF) signal strength between a sensor and associated receiver; helps locate optimum device positions during installation; and aids troubleshooting your applications
• onboard occupancy sensor (Passive Infrared [PIR] Models) — provides energy savings without additional installation time and cost
• password protection option — protects against unwanted thermostat controller tampering
• backlit Liquid Crystal Display (LCD) — offers real-time control status of the environment in easy-to-read, English text messages with constant backlight that brightens during user interaction
• two configurable digital inputs on all models — provide additional inputs for advanced functions such as remote night setback, service or filter alarms, or occupancy override
• over 20 configurable parameters — enable the TEC200x-4 and TEC200x-4+PIR Series Wireless Networked Thermostat Controllers to adapt to any application, allowing installer parameter access without opening the cover
• Economizer output (TEC2004-4 and TEC2004-4+PIR models) — provides control of economizer operation for single- and multi-stage unitary rooftop equipment
• optional discharge air sensor — monitors unit efficiency

Product Code Numbers TEC20-3C-2: BACnet IP Version
TEC20-6C-2: BACnet MS/TP Version
Power Requirements 15 VDC, 6 W Maximum
Platform IBM® PowerPC® 405EP 250 MHz Processor
64 MB SDRAM and 64 MB Serial Flash
Battery Backup - Shutdown Begins within 10 Seconds
Real-Time Clock - 3 Month Backup Maximum with Battery
Operating System NiagraAX
Communications Ethernet: Two 10/100 Mbps Ports (RJ-45 Connection)
RS-232: 9-Pin D-Shell Connection
RS-485: 3-Pin Non-Isolated Port
Transmission Range Through Walls: 10 m (30 ft)
Line-of-Sight (Open Space): 30 m (100 ft)
RF Band Direct-Sequence, Spread-Spectrum Transmission; 2.4 Ghz Unlicensed Band
Transmission Power 10 mW Maximum
Wire Size 18 AWG Maximum, 22 AWG Recommended
Ambient Conditions Operating: 0 to 50°C (32 to 122°F); 95% RH Maximum, Noncondensing
Storage: -20 to 60°C (-4 to 140°F); 95% RH Maximum, Noncondensing
Compliance United States:
UL Listed, File E27734, CCN XAPX, Under UL 873, Temperature Indicating and Regulating Equipment
FCC Compliant to CFR 47, Part 15, Subpart B and Part 15 Class A
Canada:
C-UL Listed, File E207782, CCN XAPX7, Under CAN/CSA C22.2 No. 24, Temperature Indicating and Regulating
Equipment, and C22.2 No. 205-M1983 Signal Equipment
Industry Canada, ICES-003
Shipping Weight 1.1 lb (0.499 kg)