Honeywell CTP/CTS Solid and Split Core Current Transmitters

Solid and Split Core Current Transmitters
CTP/CTS

Depending on model selected the current is converted into a linear and proportional output signal of 0-5 Vdc, 0-10 Vdc or 4-20 mA, which can be monitored by a building management controller. These current sensors should be used in load trending (current monitoring) type applications. The split core transmitters are ideal for retrofit or existing installations, since it is not necessary to power down the unit and disconnect any wires during the installation process. Solid core transmitters are extremely easy to install, they are an excellent choice for new installations.

• Solid or split core loop-powered current
• transmitters for 4-20 mA models
• Solid or split core 0-5 or 0-10 Vdc models
• Fast response time
• Integral DIN rail mounting flange
• Easy wiring, polarity sensitive output
• Accepts up to a 350 MCM (17.3 mm) cable
• Operates up to 250 continuos amps
• True RMS versions are available
• RoHS and WEEE Complaint
• Limited 5 Year Warranty

Select a link under the "item" tab below to order.

Cat #FrequencyDescriptionsTypeSupply VoltageOutput Switch RatingCore TypeCurrent RangeResponse Time
CTP-05-050-VDC-00150 Hz to 600 HzCurrent SensorsAdjustableInduced from monitored conductor0 to 5 VdcSplit0-10 Amps; 0-20 Amps; 0-50 Amps<100 mS
CTP-05-250-VDC-00150 Hz to 600 HzCurrent SensorsAdjustableInduced from monitored conductor0 to 5 VdcSplit0-100 Amps; 0-200 Amps; 0-250 Amps<100 mS
CTP-10-050-VDC-00150 Hz to 600 HzCurrent SensorsAdjustableInduced from monitored conductor0 to 10 VdcSplit0-10 Amps; 0-20 Amps; 0-50 Amps<100 mS
CTP-10-250-VDC-00150 Hz to 600 HzCurrent SensorsAdjustableInduced from monitored conductor0 to 10 VdcSplit0-100 Amps; 0-200 Amps; 0-250 Amps<100 mS
CTP-20-005-AVG-00130 Hz to 1 kHzLoop Powered Current SensorFixed12 to 30 Vdc4-20 mA AverageSplit0-5 Amps<75 mS
CTP-20-005-VFD-00130 Hz to 1 kHzLoop Powered Current SensorFixed12 to 30 Vdc4-20 mA Average True RMSSplit0-5 Amps<200 mS
CTP-20-050-AVG-00130 Hz to 1 kHzLoop Powered Current SensorAdjustable12 to 30 Vdc4-20 mA AverageSplit0-10 Amps; 0-20 Amps; 0-50 Amps<75 mS
CTP-20-050-VFD-00130 Hz to 1 kHzLoop Powered Current SensorAdjustable12 to 30 Vdc4-20 mA Average True RMSSplit0-10 Amps; 0-20 Amps; 0-50 Amps<200 mS
CTP-20-200-AVG-00130 Hz to 1 kHzLoop Powered Current SensorAdjustable12 to 30 Vdc4-20 mA AverageSplit0-100 Amps; 0-150 Amps; 0-200 Amps<75 mS
CTP-20-200-VFD-00130 Hz to 1 kHzLoop Powered Current SensorAdjustable12 to 30 Vdc4-20 mA Average True RMSSplit0-100 Amps; 0-150 Amps; 0-200 Amps<200 mS
CTS-05-050-VDC-00150 Hz to 600 HzCurrent SensorsAdjustableInduced from monitored conductor0 to 5 VdcSolid0-10 Amps; 0-20 Amps; 0-50 Amps<100 mS
CTS-05-250-VDC-00150 Hz to 600 HzCurrent SensorsAdjustableInduced from monitored conductor0 to 5 VdcSolid0-100 Amps; 0-200 Amps; 0-250 Amps<100 mS
CTS-10-050-VDC-00150 Hz to 600 HzCurrent SensorsAdjustableInduced from monitored conductor0 to 10 VdcSolid0-10 Amps; 0-20 Amps; 0-50 Amps<100 mS
CTS-10-250-VDC-00150 Hz to 600 HzCurrent SensorsAdjustableInduced from monitored conductor0 to 10 VdcSolid0-100 Amps; 0-200 Amps; 0-250 Amps<100 mS
CTS-20-005-AVG-00130 Hz to 1 kHzLoop Powered Current SensorFixed12 to 30 Vdc4-20 mA AverageSolid0-5 Amps<75 mS
CTS-20-005-VFD-00130 Hz to 1 kHzLoop Powered Current SensorFixed12 to 30 Vdc4-20 mA Average True RMSSolid0-5 Amps<200 mS
CTS-20-050-AVG-00130 Hz to 1 kHzLoop Powered Current SensorAdjustable12 to 30 Vdc4-20 mA AverageSolid0-10 Amps; 0-20 Amps; 0-50 Amps<75 mS
CTS-20-050-VFD-00130 Hz to 1 kHzLoop Powered Current SensorAdjustable12 to 30 Vdc4-20 mA Average True RMSSolid0-10 Amps; 0-20 Amps; 0-50 Amps<200 mS
CTS-20-250-AVG-00130 Hz to 1 kHzLoop Powered Current SensorAdjustable12 to 30 Vdc4-20 mA AverageSolid0-100 Amps; 0-200 Amps; 0-250 Amps<75 mS
CTS-20-250-VFD-00130 Hz to 1 kHzLoop Powered Current SensorAdjustable12 to 30 Vdc4-20 mA Average True RMSSolid0-100 Amps; 0-200 Amps; 0-250 Amps<200 mS
Supply Voltage: Induced from monitored conductor
Output Voltage: CTS-05; CTP-05 Series: 0 to 5 Vdc.
CTS-10; CTP-10 Series: 0 to 10 Vdc.
Amperage Ranges: 0 to 250 Amps (See Table 1).
Accuracy: CTS-05; CTP-05: ±1.0% (2 to 100% FSO).
CTS-10; CTP-10: ±1.0% (5 to 100% FSO).
Response Time: CTS-05; CTP-05 Series: <100 mS.
CTS-10; CTP-10 Series: <100 mS.
Load: Calibrated into a 1 mohm Load.
Operating Frequency Range: 50 to 600 Hz.
Isolation Voltage: 1270 Vac.
Aperture (Hole) Size: 3/4 in. (19 mm), Accepts up to 350 MCM (17.3 mm) Cables.
Dimensions: See Figures 1 and 2.
Din Rail Size: 1-3/8 in. (35 mm).
Unit Weight: CTS-05,-10: 0.22 lbs. (0.1 kg).
CTP-05,-10: 0.24 lbs. (0.1 kg).
Enclosure Rating/Color: UL94-5VB.
Operating Temperature Range: 5° to 140° F (-15° to 60° C).
Operating RH Range: 0 to 95% RH, non-condensing.
Agency Approvals: CE, UL
Environmental Compliance RoHS-Directive 2002/95/EC.
WEEE-Directive 2002/96/EC.