Johnson Controls T-5800 Series Pneumatic Receiver-Controller

Pneumatic Receiver-Controller
T-5800 Series

The T-5800 Pneumatic Receiver-Controller is designed for use with remote temperature, humidity, or pressure transmitters that are connected to a control variable (CV) input. The controller provides precise control of pneumatic devices. The T-5800 is capable of providing restricted supply air to low volume remote transmitters, reducing the number of air line connections needed between instruments to only one line. The “CV” input accepts the transmitted output of any pneumatic device with a calibrated output of 3 to 15 psig (21 to 105 kPa).

• available as single or dual input models with proportional or proportional plus integral (PI) control
• adjustments for gain, local set point, ratio, master input balance, and integral time are located on the controller face
• provided with hypodermic needle test points for pressure checks
• designed for surface mounting
• action and readjustment are field selectable
• air lines connect to the unit through two detachable connectors, with barbed fittings for 1/4 in. O.D. polytubing
• a clear cover protects the components from dust and dirt, and discourages tampering
• output pressure gauge

Select a link under the "item" tab below to order.

Cat #Descriptions
T-5800-1Single Input, Proportional
T-5800-2Single Input, Proportional Plus Integral
T-5800-3Dual Input, Proportional
T-5800-4Dual Input, Proportional Plus Integral
Action T-5800-1, -2, Single Input Models Direct or Reverse Acting, Field Selectable
T-5800-3, -4, Dual Input Models Direct or Reverse Acting with Direct or Reverse Readjustment, Field Selectable
Set Point Adjustment Factory Set Local at Approximately 9 psig (63 kPa), Field Selectable Local or Remote
Gain T-5800-1, -3
(Proportional-Only Models)
Adjustable From 0.5:1 to 15:1, Factory Set at Approximately 10:1
T-5800-2, -4
(Proportional Plus Integral Models)
Adjustable From 0.5:1 to 15:1, Factory Set at Approximately 5:1
Ratio
(T-5800-3, -4 Only)
Jumper 1:1 Variable From 0.1:1 to 2.5:1, Factory Set at Approximately 1:1
Jumper 3:1 Variable From 0.1:1 to 6:1, Factory Set at Approximately 3:1
Integral Time
(T-5800-2, -4 Only)
Adjustable From 0.01 to 30 Minutes (Per Repeat), Factory Set at Approximately Three Minutes
Supply Pressure 18 to 22 psig (126 to 154 kPa), Nominal 20 psig (140 kPa)
Air Supply Must Be Clean, Dry, and Oil-Free
Air Consumption
(Does Not Include Air Consumption for Transmitter Restrictors)
T-5800-1

45 scim (12 mL/s)

T-5800-2 60 scim (16 mL/s)
T-5800-3 60 scim (16 mL/s)
T-5800-4 75 scim (20 mL/s)
Output Capacity 1000 scim
Materials Body Glass-Reinforced Polypropylene
Cover Clear Acrylic Thermoplastic
Mounting Surface
Air Connections Two Detachable Connectors with Barbed Fittings for 1/4 in. O.D. Polytubing
Ambient Operating
Limits
Temperature 50 to 120°F (10 to 49°C)
Humidity 10 to 90% RH at Maximum Dew Point or 85°F (29°C)
Ambient Storage Temperature Limits -20 to 150°F (-29 to 66°C)