Jump to Navigation

Johnson Controls P10 Low Pressure Control (Single or Two-Stage)

Low Pressure Control (Single or Two-Stage)
P10

These pressure controls open or close electrical circuits from a change in operating air pressure. R to Y terminals make (cut-in) on pressure rise.

• visible calibrated adjustable range scale
• snap-acting switch in a dust protected enclosure
• easily accessible wiring terminals

Select a link under the "item" tab below to order.

Cat #Contact ActionNo. of StagesRange psig (kPa)psig (kPa)Switch Diff psi (kPa)Pressure Connector
P10BC-7CSPDT13 to 20 (21 to 138)12 (R to Y Cut-in)2Barbed Fitting
P10BG-3CSPDT13 to 20 (21 to 138)12 (R to Y Cut-in)0.21/8 in. Female NPSF
P10BJ-1CSPDT13 to 20 (21 to 138)12 (R to Y Cut-in)21/8 in. Female NPSF
P10FC-4CSPDT23 to 20 (21 to 138)(R-Y Cutout) Low Stage 8 (55) (R-Y Cut-in) High Stage 12 (82)Low Stage 2 (14) High Stage 2 (14)1/8 in. Barbed Fitting
P10PA-11CSPDT33 to 20 (21 to 138)Stage 1 Open High 6 (41) Stages 2 & 3 Open High 18 (120)Stage 1 3 (21) Stages 2 & 3 0.4 (3)1/8 in. Barbed Fitting


Main menu 2