Jump to Navigation

Johnson Controls A25 Series Warm Air Limit Control with Manual Reset

Warm Air Limit Control with Manual Reset
A25 Series

The A25 warm air control locks out on a temperature increase to the control set point. Manual reset is required before the electrical contacts can be reclosed. The A25 is normally located in a return air duct and is wired to shut down air conditioning or ventilating fans when the temperature of the air becomes excessively hot.

• trip-free reset lever does not permit restarting until the reset lever is manually released
• the rod and tube type sensing element provides positive control action

Select a link under the "item" tab below to order.

Cat #Switch ActionRange °F (°C)Range AdjusterDial Stop °F (°C)
A25AN-1CSPST Open High25 to 215 (-4 to 102)KnobHigh Limit Set at 125 (52)
A25CN-1CSPDT25 to 215 (-4 to 102)KnobHigh Limit Set at 125 (52)
A25AP-1CSPST Open High25 to 215 (-4 to 102)Concealed Screwdriver SlotHigh Limit Set at 125 (52)
A25CP-1CSPDT25 to 215 (-4 to 102)Concealed Screwdriver SlotHigh Limit Set at 125 (52)
Motor Ratings VAC: 120 208 240 277
AC Full Load A: 16.0 9.2 8.0
AC Locked Rotor A: 96.0 55.2 48.0
Non-Inductive A: 16.0 A at 120/277 VAC      
The maximum element temperature is 300°F (149°C).
Pilot Duty: 125 VA, 24 to 600 VAC


Main menu 2