Jump to Navigation

ICON IP500 Industrial I/P Transducer

Industrial I/P Transducer
IP500

The IP500 converts a 4-20mA current input signal to a linearly proportional pneumatic output pressure. This versatile instrument is designed for control applications that require a high degree of reliability and repeatability at an economical cost. Typically, they are used for applications that require the operation of valve actuators, pneumatic valve positioners, damper and louver actuators, fi nal control elements, relays, air cylinders, web tensioners, clutches and brakes. Industries that utilize IP500’s include Petrochemical, HVAC, Energy Management, Textile, Paper, Paper Converting, and Food & Drug.

• Low Cost
• Integral Volume Booster
• Compact Size
• Low Air Consumption
• Field Reversible
• Flexible Zero & Span Adjustments
• Split Ranging
• Standard Process Input (4-20mA)

Min/Max Supply Pressure Minimum - 3 psig (21kPa) Above maximum output
Maximum - 100 psig (700 kPa)
Impedance 180 Ohms
Supply Pressure Sensitivity <± 0.1% of span per psig (<± 0.15% of span per 10 kPa)
Terminal Based Linearity <± 0.75% of span
Repeatability < 0.5% of span
Hysteresis < 1.0% of span
Response Time Typically less than 0.25 sec for 3-15 psig units
Flow Rate 4.5 scfm (7.6 m3/hr ANR) at 25 psig (175 kPa) supply 12.0 scfm (20.0 m3/hr ANR) at 100 psig (700 kPa) supply
Relief Capacity 2 scfm (3.4 m3/hr) at 5 psig (35 kPa) above 20 psig (140 kPa) setpoint
Maximum Air Consumption .05 scfm (0.7 m3/hr) midrange typical
Media Oil free, clean dry air filtered to 40 micron
Temp. Range (Operating) -20°F to 140°F (-30°C to 60°C)
Port Sizes 1/4 NPT (Pneumatic) 1/2 NPT (Electric)
Weight 2.1 lbs. (0.94 kg)