Jump to Navigation

ICON ICD-192 Single Setpoint Pneumatic Room Thermostat

Single Setpoint Pneumatic Room Thermostat
ICD-192

Providing proportional single output, single setpoint, 1-pipe for low air capacity or 2-pipe for high air capacity pneumatic room temperature control, the 192 S Powerstar Single Setpoint Pneumatic Room Thermostat is the most economical model. Refer to the Retroline® Retrostats on page A-15 to replace competitive models.

• Single setpoint dial available in Fahrenheit or Celsius scales
• Available in direct or reverse acting models
• Sensitive bimetal responds to temperature changes
• Integral, field adjustable limit stops
• Wall mounting plate for connection to a variety of rough-in terminal boxes included
• Large volume air capacity relay in 2-pipe models only
• Test port for fast check of output pressure without removing the cover
• Field replaceable thermometer, setpoint dial, restrictor and filters for decreased maintenance cost

Select a link under the "item" tab below to order.

Cat #TypeOutputSetpointAir Output CapacityThermometer & Setpoint ScalesType1Type2Models
ICD192-9002DirectSingleSingle (Heat or Cool)High (Integral Relay)°FControl ActionThermostat Chassis & Wall Plate192 S 2-pipe
ICD192-9003ReverseSingleSingle (Heat or Cool)High (Integral Relay)°FControl ActionThermostat Chassis & Wall Plate192 S 2-pipe
Scale/Range:
Major (minor) Divisions: 45 to 85°F, 10(2)°F
(7 to 30°C, 5(1)°C)
Factory Calibration: 72°F, 7.5 psi ±0.3
(22°C, 52 kPa @ 1.8)
Sensitivity Adjustment Range: 1 to 4 psi/°F (12 to 50 kPa/°C)
Factory Setting: 2.5 psi/°F (31 kPa/°C)
Limit Stop:
Field Adjustment Range: 45/85°F (7/30°C)
Fixed Limit Stop Range: 55/75°F (13/24°C)
Temperature:  
Storage: 10 to +140°F (-23 to +60°C)
Ambient Operating: 40 to 140°F (4 to 60°C)
Accuracy at Factory:
Calibration: ±2°F (±1.1°C)
Response: 0.1°F (0.06°C)
Supply Air Pressure:
Recommended: 25 psi (172 kPa)
Maximum: 30 psi (207 kPa)
Nominal Air Consumption for Air Compressor Sizing:
1-pipe: 25 scim (6.8 ml/s)
2-pipe: 20 scim (5.5 ml/s)
Nominal Air Capacity for Air Main Sizing:
1-pipe: 25 scim (6.8 ml/s)
2-pipe: 20 scim (5.5 ml/s)
Nominal Chassis Air Capacity:
1-pipe Supply: 25 scim (6.8 ml/s)
2-pipe Supply: 230 scim (63 ml/s)
1-pipe Exhaust: 30 scim (8 ml/s)
2-pipe Exhaust: 150 scim (41 ml/s)
Air Connections: 5/32" (4 mm) OD tubing
Dimensions (with cover): 2.16" W x 3.34" H x 1.59" D
(55 mm W x 85 mm H x 40 mm D)
Shipping Weights (with cover):
Thermostat Chassis and Wall Plate: 0.53 lb. (0.24 kg)
Plastic Cover/Metal Cover: 0.07 lb. (0.04 kg)/0.27 lb. (0.12 kg)