Honeywell XYR3000 G Series Wireless Gateways


The XYR300G Wireless gateway products provide a wireless interface between various data buses used in process and automation applications. The gateway includes an integral 900MHz license-free radio transceiver, and transfers transducer and control signals (I/O) using the highly secure and highly reliable WIB-smart radio protocol.
• Used for Wire in Digital out configuration
• 900MHz, FHSS, 1 Watt strength LOS 20 miles
• High security data encryption on the wireless link
Select a link under the "item" tab below to order.
Cat # | Descriptions | Type | Order Item |
XYR300G-M | Modbus Gateway | Gateways | WHG300GM |
XYR300G-E | Ethernet Gateway | Gateways | WHG300GE |
XYR300D | Wireless Serial Radio Modem | Modems | WHS300D |
XYR300E | Wireless Ethernet Modem | Modems | WHS300E |
XYR400E | WiFi Wireless Ethernet Modem | Modems | WHS400E |
GENERAL | ||
Model XYR300G-M (Modbus) |
Model XYR300G-E (Ethernet) | |
Temperature: | -40 to +140 deg F (-40 to +60 deg C) | 30 to +140 deg F (0 to +60 deg C) |
Humidity: | 0 – 99% | 0 – 95% |
EMC: | EMC Compliant EN55022, EN50082-1, FCC Part 15 |
EMC Compliant EN55022, EN50082-1, FCC Part 15 |
Housing: |
DIN-rail Extruded Aluminum Case Terminals suitable for 12 gauge (2.5 sq mm) wire. |
DIN-rail Extruded Aluminum Case Terminals suitable for 12 gauge (2.5 sq mm) wire. |
Dimensions: | 130 x 185 x 60mm (5.1 x 7.3 x 2.4 inches) | 100 x 22 x 120mm (3.9 x 0.9 x 4.7 inches) |
LED Indication: | For processor OK, radio TX and RX, serial TX and RX, active status | For processor OK, radio TX and RX, serial TX and RX, active status |
Radio Transceiver: |
Frequency Hopping spread spectrum Transmit Power 1W Approved to FCC Part 15.247, RS210 Maximum Line-of-sight range: Range may be extended by using up to four intermediate repeater units. Data Range 19.2 Kbaud with FEC (raw rate 115.2 Kbaud) |
Frequency Hopping spread spectrum Transmit Power 1W Approved to FCC Part 15.247, RS210 Maximum Line-of-sight range: Range may be extended by using up to four intermediate repeater units. Data Range 19.2 Kbaud with FEC (raw rate 115.2 Kbaud) |
I/O Capacity: | Modbus: 4300 I/O points (analog plus discrete | Ethernet: 2048 bytes input and 2048 bytes output; up to 4300 discrete I/O points or up to 1024 analog in/122 analog out |
Power Supply: |
9 - 30VDC / 12 – 24VAC. Battery charging circuit included for 12 V back-up battery, max charge current regulated to 0.7A (>12V supply) Normal Current Drain: 12V 270mA, 24V 170Ma |
9 - 30VDC / 12 – 24VAC. Battery charging circuit included for 12 V back- up battery, max charge current regulated to 0.7A (>12V supply) Normal Current Drain: 12V 270mA, 24V 170Ma |
Radio Transmission: |
Modbus RTU (binary), master / slave configurable. RS232 or RS485, 300 – 19200 bits/sec. |
10/100 Mbit/s, RJ45 connector, Transformer EtherNet/IP level 2 I/O Server |