Jump to Navigation

Honeywell V4044 Line Voltage Diverting Valves

Line Voltage Diverting Valves
V4044

On-off and diverting line voltage valves consist of an actuator motor and valve assembly for controlling the flow of hot or chilled water.

• Manual opener (on all models, except straight-through, normally open valves) for valve operation on power failure; valve returns to automatic position when power is restored.
• All models may be installed without disassembling the valve.
• Compact construction for easy installation.
• Complete powerhead may be removed or replaced without breaking plumbing line connections or draining the system.
• Motor may be replaced without removing the valve body or draining the system.
• Suitable for heating and cooling applications.

Select a link under the "item" tab below to order.

Cat #Voltage(inch)Connection Type(psi)(Cv)Manual Opener
V4044A1001120 Vac1/2 in.Flare20 psi4 CvYes
V4044A1019120 Vac1/2 in.Sweat20 psi4 CvYes
V4044A1035208 Vac1/2 in.Sweat20 psi4 CvYes
V4044A1043240 Vac1/2 in.Flare20 psi4 CvYes
V4044A1050220 Vac1/2 in.Sweat20 psi4 CvYes
V4044A1191120 Vac3/4 in.Sweat10 psi7 CvYes
V4044A1258277 Vac1/2 in.Sweat20 psi4 CvYes
V4044A1290120 Vac1/2 in.Sweat20 psi4 CvYes
V4044B1009120 Vac1/2 in.Flare20 psi4 CvYes
V4044B1017120 Vac1/2 in.Sweat20 psi4 CvYes
V4044B1314120 Vac3/4 in.Sweat10 psi7 CvYes
Application: Hydronic Control
Type: 2 position
Body Pattern:

3-Way, Diverting

Valve Action: Spring Return to port A
Power Consumption: 9.6 VA
Nominal Timing (sec, min): 30 sec
De-energized Position: Port A Normally Closed
Electrical Connections: 18 in. leads (457 mm leads)
Static Pressure: 125 psi (862 kPa)
Fluid Temperature Range: 40 F to 200 F (5 C to 93 C)
Maximum Ambient Temperature: 125 F (52 C)
Maximum Ambient Temperature: (Body): Brass
(Stem): Stainless Steel
(Seat): Brass
(Packing O-Ring): EPDM rubber
(Ball Plug): Buna-N (NBR) Rubber Ball
Comments: Use this valve in closed loop hydronic systems that do not contain dissolved oxygen in system water, such as fresh water from frequent source of makeup water.
Valve designed for cycling (not constantly powered on) applications.
Approvals: Underwriters Laboratories Inc. UL Component Listed: File MH11826 Vol. 1


Main menu 2