Jump to Navigation

Honeywell UDC3500 1/4 DIN, High Accuracy, 2-Loop Universal Controller

1/4 DIN, High Accuracy, 2-Loop Universal Controller
UDC3500

New Power and Flexibility The UDC3500 Universal Digital Controller packs new powerful features in the popular 1/4 DIN size. Unmatched application power includes: Infrared (IR) Configuration interface, three universal analog inputs, two loops of control and two Math Algorithms. When these are combined with the Accutune III™ tuning with fuzzy logic overshoot suppression, the result is price/performance leadership. Application flexibility is assured by the universal analog inputs, universal AC power supply, four digital inputs, a maximum of seven analog and digital outputs, Infrared, RS422/485 Modbus RTU or Ethernet 10Base-T TCP/IP Modbus communication protocols, simple configuration plus total field upgrade capability for any optional feature.

• 3 Universal Analog Inputs (can be configured to operate as 1 Universal and 4 High Level Inputs)
• 0.10% Accuracy
• Fast scanning rate (166ms)
• Up to 3 Analog Outputs
• Up to 5 Digital Outputs
• 4 Digital Inputs
• Math Functions
• Ethernet or RS-485 communication
• Cascade or 2 Loops of control
• Infrared PC & Pocket PC configuration
• Healthwatch Maintenance Tool
• NEMA4X and IP66 front face protection
• Multilanguage prompts
• ¼ DIN Size
• Easily Field Upgradeable
• Bright, dual displays with multi-language prompts (in English, French, German, Spanish, or Italian) make the operator interface easy to read, understand, and operate. Simple keystrokes let you set operating parameters that meet your process control needs.

Select a link under the "item" tab below to order.

Table 1Table 2Table 3Table 4Table 5Table 6Table 7Table 8Table 9Table 10Table 11Table 12Table 13Table 14Table 15Table 16Table 17
XXXXXXXXXXXXXXXXXXXXXX
Table 1KEY NUMBER - UDC3500 Single & Dual Loop Controller
DC3500Digital Controller for use with 90 to 264Vac Power + Current Output #1
DC3501Digital Controller for use with 24Vac/dc Power + Current Output #1
Table 2Input 2
0None
1TC, RTD, mV, 0-5V, 1-5V, 0-20mA, 4-20mA
2TC, RTD, mV, 0-5V, 1-5V, 0-20mA, 4-20mA, -1-1V, 0-10V
3Two HLAI instead of 1 LLAI
Table 3Approvals
0CE (Standard)
1CE, UL and CSA
Table 4Tags
0None
TStainless Steel Customer ID Tag - 3 lines w/22 characters/line
Table 5Input 3
0None
1TC, RTD, mV, 0-5V, 1-5V, 0-20mA, 4-20mA
2TC, RTD, mV, 0-5V, 1-5V, 0-20mA, 4-20mA, -1-1V, 0-10V
3Two HLAI instead of 1 LLAI
4Slidewire Input for Position Prop. (Requires Dual Relay Output)
Table 6Special Options
0None
1Custom Calibration (0.05%) For one Range Type Only ( Note 1)
Table 7Future Options
0None
0None
Table 8Manuals
0Product Information on CD - (English)
EEnglish Manual (Hard copy)
Table 9Certificate
0None
CCertificate of Conformance (F3391)
Table 10Specify optional Output and/or Alarms-Output #2
0None
CCurrent Output (4 to 20mA, 0 to 20 mA) (Current Output #3)
EElectro Mechanical Relay (5 Amp Form C)
ASolid State 1 Amp (Zero-Crossing Type)
TOpen Collector transistor output
RDual 2 Amp Relays (Form A) (Heat/Cool, Pos Prop, TPSC, Relays 1 & 2)
Table 11Specify optional Output and/or Alarms-Relay Outputs #3, #4 and #5
0None
EThree (3) E-M Relay (5 Amp Form C)
Table 12Communications
0None
1Current Output #2 + (4) Digital Inputs
2Current Output #2 + (4) Digital Inputs + Modbus RS-485
310 Base-T Ethernet (Modbus RTU) + (4) Digital Inputs
Table 13Software Selections
0Standard Function, Includes Accutune
AMath Option
BSet Point Programming (1 Program, 20 Segments)
CSet Point Programming Plus Math (1 Program, 20 Segments)
DHealthWatch
ESPP + HealthWatch (1 Program, 20 Segments)
FMath + HealthWatch
GSPP + Math + HealthWatch (1 Program, 20 Segments)
Table 14Enhanced
HEnhanced SPP (4 Programs, 20 Segments each)
JEnhanced SPP + Math (4 Programs, 20 Segments each)
KEnhanced SPP + HealthWatch (4 Programs, 20 Segments each)
LEnhanced SPP + Math + HealthWatch (4 Programs, 20 Segments each)
Table 15Loops of Control
0Single Loop
22 Loops + Internal Cascade
Table 16Real-Time Clock
0None
CReal-Time Clock (RTC)
Table 17Input 1
1TC, RTD, mV, 0-5V, 1-5V
2TC, RTD, mV, 0-5V, 1-5V, 0-20mA, 4-20mA
3TC, RTD, mV, 0-5V, 1-5V, 0-20mA, 4-20mA, -1-1V, 0-10V
15Relative Humidity (Requires Input 2)
16Carbon, Oxygen or Dewpoint (Requires Input 2)
CE Conformity (Europe) This product is in conformity with the protection requirements of the following European Council Directives: 73/23/EEC, the Low Voltage Directive, and 89/336/EEC, the EMC Directive. Conformity of this product with any other "CE Mark" Directive(s) shall not be assumed.
EMC Classification Group 1, Class A, ISM Equipment (EN 55011, emissions), Industrial Equipment (EN61326, immunity)
Method of EMC Assessment Technical File (TF)
Declaration of Conformity 51453681
Approval Body Ratings UL Listed (Optional): UL61010C-1
CSA Certified (Optional): CSA1010-1
Front Bezel: UL and CSA approved as Type 4 moisture protection when used with 4
screws.
Analog Inputs (One or Two)
(See Table 1 for Input
Actuations)
Up to three Universal analog inputs. These can easily be configured to operate as two
Universal and two High Level inputs or as one Universal and four High Level inputs.

Accuracy:
    ± 0.10% of full scale typical (± 1 digit for display)
    Can be field calibrated to ± 0.05% of full scale typical
    16-bit resolution typical
Sampling Rate: All inputs are sampled six times per second
Temperature Stability: ± 0.0075% of Full Scale span / °C change typical

Input Impedance:
    0-20 and 4-20 Milliampere Inputs: 250 ohms
    0-10 Volt and –1 to +1 Volt Inputs: 200K ohms
    All Others: 10 megohms

Maximum Lead Wire Resistance:
    Thermocouples: 50 ohms/leg
    100 ohm, 200 ohm, 500 ohm and 1000 ohm RTD: 100 ohms/leg
    100 ohm Low RTD: 10 ohms/leg

Slidewire Input for Position Proportional Control (Input 3 only):
    100 ohm to 1000 ohm slidewire types
    Herculine© Models 10260 and 11280 Slidewire Emulation

Analog Input Signal Failure
Operation
Burnout Selections: Upscale, Downscale, Failsafe or None
Thermocouple Health: Good, Failing, Failure Imminent or Failed
Failsafe Output Level: Configurable 0-100% of Output range
Digital Inputs (Four) (Optional) +30 Vdc source for external dry contacts or isolated solid state contacts. Digital Inputs are isolated from line power, earth ground, analog inputs and all outputs.
Current and Auxiliary
Outputs
Up to three Milliamp Outputs. These outputs provide a 0 to 21 mA current output into a negative or positive grounded load or into a non-grounded load. Current outputs are isolated from each other, line power, earth ground and all inputs. Outputs can easily be configured via the keyboard to be 0 to 20 mA or 4 to 20 mA without field calibration and for either direct or reverse action when used as a control output.

Any current output not being used as a control output can be used in an Auxiliary Output mode. Auxiliary Outputs can be configured to represent any Analog Input, PV, Setpoint, Deviation, or Control Output. The range of an Auxiliary Output can be scaled per the range of the selected variable and can be set anywhere between 0 to 21 mA.
    Resolution: 14 bits over 0 to 21 mA
    Accuracy: 0.05% of full scale
    Temperature Stability: 0.01% F.S./°C
    Load Resistance: 0 to 1000 ohms

The First Current Output is a standard feature and is present on all instruments. The Second Current Output is an option and is mutually exclusive with Ethernet Communications. The Third Current Output is an option and is mutually exclusive with the other Output 2 Options listed directly below.

Power Consumption 24 VA maximum (90 to 264 Vac)
18 VA maximum (24 Vac/dc)
Weight 3 lbs. (1.3 kg)


Main menu 2