Jump to Navigation

Honeywell UDC3200 1/4 DIN, Enhanced Display, Universal Controller

1/4 DIN, Enhanced Display, Universal Controller
UDC3200

New Power and Flexibility The UDC3200 Universal Digital Controller packs new powerful features in the popular 1/4 DIN size. Unmatched application power includes: Infrared (IR) Configuration interface, two universal analog inputs and a Math Algorithm. When these are combined with the Accutune III™ tuning with fuzzy logic overshoot suppression, the result is price/performance leadership. Application flexibility is assured by the universal analog inputs, universal AC power supply, two digital inputs, a maximum of five analog and digital outputs, RS422/485 Modbus RTU or Ethernet 10Base-T TCP/IP communication protocols, simple configuration plus total field upgrade capability for any optional feature.

• 2 Universal Analog Inputs
• 0.20% Accuracy
• Fast scanning rate (166ms)
• Up to 5 Output Types
• 2 Digital Inputs
• Math Functions
• Ethernet and Modbus communication
• Infrared PC & Pocket PC configuration
• NEMA4X and IP66 front face protection
• Multilanguage prompts
• ¼ DIN Size
• Jumper free configuration
• Easily Field Upgradable Bright, dual displays with multi-language prompts (in English, French, German, Spanish, or Italian) make the operator interface easy to read, understand, and operate. Simple keystrokes let you set operating parameters that meet your process control needs.

Select a link under the "item" tab below to order.

Table 1Table 2Table 3Table 4Table 5Table 6Table 7Table 8Table 9Table 10Table 11Table 12Table 13Table 14Table 15
XXXXXXXXXXXXXXXXXXXXX
Table 1KEY NUMBER - UDC3200 Single Loop Controller
DC3200Digital Controller for use with 90 to 264Vac Power
DC3201Digital Controller for use with 24Vac/dc Power
Table 2Approvals
0CE (Standard)
1CE, UL and CSA
Table 3Future Options
0None
0None
0None
Table 4Tags
0None
TLinen Customer ID Tag - 3 lines w/22 characters/line
SStainless Steel Customer ID Tag - 3 lines w/22 characters/line
Table 5Manuals
0Product Information on CD - All Languages
EEnglish Manual
Table 6Certificate
0None
CCertificate of Conformance (F3391)
Table 7No Selection
0None
Table 8Specify Control Output and/or Alarms-Output #1
CCurrent Output (4 to 20 ma, 0 to 20 ma)
EElectro Mechanical Relay (5 Amp Form C)
ASolid State Relay (1 Amp)
TOpen Collector transistor output
RDual 2 Amp Relays (Both are Form A) (Heat/Cool Applications)
Table 9Specify Control Output and/or Alarms-Output #2 and Alarm #1 or Alarms 1 and 2
0No Additional Outputs or Alarms
BOne Alarm Relay Only
EE-M Relay (5 Amp Form C) Plus Alarm 1 (5 Amp Form C Relay)
ASolid State Relay (1 Amp) Plus Alarm 1 (5 Amp Form C Relay)
TOpen Collector Plus Alarm 1 (5 Amp Form C Relay)
Table 10Communications
0None
1Auxiliary Output/Digital Inputs (1 Aux and 1 DI or 2 DI)
2RS-485 Modbus Plus Auxiliary Output/Digital Inputs
310 Base-T Ethernet (Modbus RTU) Plus Auxiliary Output/Digital Inputs
Table 11Software Selections
0Standard Functions, Includes Accutune
AMath Option
BSet Point Programming (1 Program, 12 Segments)
CSet Point Programming Plus Math
Table 12Reserved
0No Selection
Table 13Infrared interface
RInfrared Interface Included (Can be used with a Pocket PC)
Table 14Input 1
1TC, RTD, mV, 0-5V, 1-5V
2TC, RTD, mV, 0-5V, 1-5V, 0-20mA, 4-20mA
3TC, RTD, mV, 0-5V, 1-5V, 0-20mA, 4-20mA, 0-10V
160Carbon, Oxygen or Dewpoint (Provides 2 Inputs)
Table 15Input 2
00None
10TC, RTD, mV, 0-5V, 1-5V, 0-20mA, 4-20mA
20TC, RTD, mV, 0-5V, 1-5V, 0-20mA, 4-20mA, 0-10V
40Slidewire Input for Position Proportional (Requires 2 Relay Outputs)
CE Conformity (Europe) This product is in conformity with the protection requirements of the following European Council Directives: 73/23/EEC, the Low Voltage Directive, and 89/336/EEC, the EMC Directive. Conformity of this product with any other "CE Mark" Directive(s) shall not be assumed.
EMC Classification Group 1, Class A, ISM Equipment (EN 55011, emissions), Industrial Equipment (EN61326, immunity)
Method of EMC Assessment Technical File (TF)
Declaration of Conformity 51453663
Approval Body Ratings CE (Standard)
UL Listed (Optional): UL61010C-1
CSA Certified (Optional): CSA1010-1
Analog Inputs (One or Two)
(See Table 1 for Input
Actuations)
Accuracy:
    • ± 0.20% of full scale typical (± 1 digit for display)
    • Can be field calibrated to ± 0.05% of full scale typical
    • 16-bit resolution typical
Sampling Rate: Both inputs are sampled six times per second
Temperature Stability: ± 0.01% of Full Scale span / °C change—typical
Input Impedance:
    • 4-20 Milliampere Input: 250 ohms
    • 0-10 Volt Input: 200K ohms
    • All Other: 10 megohms
Maximum Lead Wire Resistance:
    • Thermocouples: 50 ohms/leg
    • 100 ohm, 200 ohm and 500 ohm RTD: 100 ohms/leg
    • 100 ohm Low RTD: 10 ohms/leg
Analog Input Signal Failure
Operation
Burnout Selections: Upscale, Downscale, Failsafe or None
Thermocouple Health: Good, Failing, Failure Imminent or Failed
Failsafe Output Level: Configurable 0-100% of Output range
Digital Inputs (Two) (Optional) +30 Vdc source for external dry contacts or isolated solid-state contacts. Digital Inputs are isolated from line power, earth ground, analog inputs and all outputs except for the Second Current Output.
On contact closure the controller will respond according to how each digital input is configured. Opening the contact causes a return to previous state.
The second Digital Input is mutually exclusive with the Second Current Output.
Alarm Outputs (Optional) One SPDT electromechanical relay. A second alarm is available if the second control relay is not used for control purposes.
Up to four setpoints are independently set as high or low alarm, two for each relay. Setpoint can be on any Input, Process Variable, Deviation, Manual Mode, Failsafe, PV Rate, RSP Mode, Communication Shed, or Output. A single adjustable hysteresis of 0.0 to 100.0% is provided. The alarm can also be set as an ON or OFF event at the beginning of a setpoint ramp/soak segment.
Alarm Relay Contacts Rating
Resistive Load: 5 amps at 120 Vac or 240 Vac or 30 Vdc


Main menu 2