Jump to Navigation

Honeywell TP972 Pneumatic Heating/Cooling Thermostat

Pneumatic Heating/Cooling Thermostat
TP972

Two-pipe, one- or two-temperature, pneumatic thermostat used to provide proportional control of pneumatic valves and damper actuators in heating and air conditioning systems. Replacement kits are available for Johnson, Powers, Robertshaw, Barber- Colman, and older Honeywell two-pipe pneumatic thermostats.

• Durable TP970 Series Thermostat. Pilot operated for high capacity.
• Two-temperature energy conservation model available.
• Adapter plate in Convertastat™ kits covers existing thermostat wall mark.
• Backplate has molded air connections-no separate fittings needed.
• Universal locking cover with satin chrome finish and horizontal, vertical, or blank window options with Tradeline model-other covers available.

Select a link under the "item" tab below to order.

Cat #IncludesSetpointSetpoint Temperature RangeChangeoverThrottling Range
TP972A2002Order Cover SeparatelySingle60 F to 90 FHeat 18 psi, Cool 13 psi2 F to 10 F
TP972A2010Order Cover SeparatelySingle-Heat 18 psi, Cool 13 psi2 F to 10 F
TP972A2036Energy Conservation Model, Order Cover SeparatelyDualHeating 50 F to 75 F, Cooling 60 F to 90 FHeat 18 psi, Cool 13 psi2 F to 10 F
TP972A2143Order Cover SeparatelySingle60 F to 90 FHeat 14 psi, Cool 19 psi2 F to 10 F
TP972A2192Thermostat, small wall plate and satin chrome coverSingle60 F to 90 FHeat 18 psi, Cool 13 psi2 F to 10 F
TP972A2226Thermostat and satin chrome cover.Single60 F to 90 FHeat 14 psi, Cool 19 psi2 F to 10 F
TP972A2242Thermostat and satin chrome cover.Single60 F to 90 FHeat 18 psi, Cool 13 psi2 F to 10 F
Application Type: Wall Thermostat, Heat/Cool Operation
Dimensions, Approximate: 1/4 in. high x 2 in. wide x 1 5/8 in. deep
(83 mm high x 51 mm wide x 41 mm deep)
Action: Direct Acting Heating, Reverse Acting Cooling
Airflow Usage: 0.011 scfm (5.2 mL/s)
Mounting: Wall
Operating Temperature: 100 F maximum
Storage Temperature: 150 F maximum (66 C maximum)