Jump to Navigation

Honeywell TP9600 Pneumatic Thermostat

Pneumatic Thermostat
TP9600

Pneumatic thermostat for proportional control of pneumatic valves and actuators with one- or two-pipe systems. Available with two cover options, the TP9600 is not only affordable and easy to install, but it controls temperature with the reliability that only Honeywell can provide.

• TP9600 delivers the Honeywell TP970s unparalleled sensing and control.
• Redesigned models fit your high-volume pneumatic applications.
• Backplate mounts quickly.
• Thermostat snaps onto backplate.
• Cover is mounted and locked into place with concealed setscrews.
• Attractive Euro-contoured design comes with choice of two cover options.
• Neutral taupe color blends with today’s commercial interiors.
• Adapter kits are available to retrofit most pneumatic jobs.
• Branch line capacity Low for TP9630 and TP9633 Branch line capacity High for TP9600, TP9610, TP9603, TP9620.

Select a link under the "item" tab below to order.

Cat #IncludesSetpointActionNumber of PipesThrottling Range (F)Setpoint Temperature Range (F)Changeover
TP9600A1007Cover, Setpoint, and Thermometer are VisibleSingleDirect Acting22 F to 10 F60 F to 90 F-
TP9600B1006Cover, Setpoint, and Thermometer are VisibleSingleReverse Acting22 F to 10 F60 F to 90 F-
TP9603A1001Blank Cover, Setpoint, and Thermometer are Not VisibleSingleDirect Acting22 F to 10 F60 F to 90 F-
TP9610A1006Cover, Setpoint, and Thermometer are VisibleDay/NightDirect Acting22 F to 10 FDay: 60 F to 90 F, Night: 50 F to 75 FDay 13 psi, Night 18 psi
TP9620A1005Cover, Setpoint, and Thermometer are VisibleSingleDirect Acting Heating, Reverse Acting Cooling22 F to 10 F60 F to 90 FHeat 18 psi, Cool 13 psi
TP9630A1004Cover, Setpoint, and Thermometer are VisibleSingleDirect Acting1 or 22 F to 10 F60 F to 90 F-
TP9630B1003Cover, Setpoint, and Thermometer are VisibleSingleReverse Acting1 or 22 F to 10 F60 F to 90 F-
Application Type: Wall Thermostat
Dimensions, Approximate: 3 1/4 in. high x 2 in. wide x 1 5/8 in. deep
(83 mm high x 51 mm wide x 41 mm deep)
Airflow Usage: 0.011 scfm (5.2 mL/s)
Air Connections: Barb fittings 5/32 in. (4 mm)
Mounting: Vertical Wall Mounting
Operating Temperature: 50 F to 100 F (10 C to 38 C)
Storage Temperature: 150 F maximum (66 C maximum)
Remote Bulb: Sensor Element: Bimetal
Maximum Operating Pressure: 25 psi (170 kPa)