Jump to Navigation

Honeywell STTWT400 Series XYR6000 Wireless Temperature Transmitter

XYR6000 Wireless Temperature Transmitter
STTWT400 Series

Building upon the tremendously successful ST 3000 series transmitter line; Honeywell brings simple, safe, and secure wireless technology to its measurement portfolio in the XYR 6000 Series Wireless Transmitters.

The XYR 6000 series measurements are part of the Honeywell One Wireless system and are ISA100 - ready field devices.

Measurement and information without wires! The XYR 6000 wireless transmitters series enable customers to obtain data and create information from remote and hazardous measurement locations without the need to run wires, where running wire is cost prohibitive and/or the measurement is in a hazardous location. Without wires, transmitters can be installed and operational in minutes, quickly providing information back to your system. XYR 6000 wireless transmitters send information to an multinode or series of multinodes creating a MESH infrastructure.

Wireless System Gateways (WSG) provide the path to bring that information into Experion PKS or any other control system wirelessly via OPC client or Modbus-TCP. Each multinode accepts signals from up to 20 wireless transmitters reporting at 1 second, and up to 100 transmitters reporting at slower rates. Up to 22 multinodes can be implemented in the same infrastructure. WSG also provides Modbus-TCP data access to wireless data in addition to OPC. Transmitter power is supplied by two “D” size lithium batteries with an expected lifetime of up to ten years. Transmitter range with the integral antenna is 1000’ (305 m) under ideal conditions.

The temperature transmitter supports three thermocouple inputs, two RTD inputs, or one thermocouple and one RTD without sharing field wiring terminals. The temperature transmitter will simultaneously support an integral probe and external inputs. When the integral probe is a thermocouple, then two external thermocouples or one external RTD can be wired to the transmitter. When the integral probe is a RTD, then one external thermocouple or one external RTD can be wired to the transmitter.

• Measure remote access points simply, safe and securely
• Obtain and utilize previously inaccessible information due to high wiring cost or hazardous locations.
• Easily meet Regulatory Requirements
• Improve process efficiency
• Enhance Flexibility to monitor applications:
 - that have no access to power
 - that are remote or difficult to reach
 - that may require frequent reconfiguration
 - where manual readings have been required previously

Select a link under the "item" tab below to order.

Cat #Descriptions
STTW400Wireless Temperature Transmitter Only - Separately supplied Sensor Probe or Thermowells
STTW401Wireless Temperature Transmitter Only - With Two (2) Discrete Inputs
Parameter Description
Wireless Communication:

2,400 to 2,483.5 MHz (2.4 GHz) Industrial, Scientific and Medical (ISM) band

FHSS Selection – Frequency Hopping Spread Spectrum

DSSS Selection – Discrete Sequential Spread Spectrum per FCC 15.247 / IEEE 802.15.4–2006

Every data packet transmitted in either direction is verified (CRC check) and acknowledged by the receiving device.

USA – FCC Certified
Canada – IC Certified
European Union – RTTE/ETSI Conformity

FHSS RF Transmitter Power:

NA Selection – 125 mW (20.9 dBm) maximum transmit power not including antenna per FCC/IC, or 400 mW (26.0 dBm) maximum EIRP including antenna for USA and Canadian locations.

EU Selection – 100 mW (20.0 dBm) maximum EIRP including antenna per RTTE/ETSI for EU locations.

DSSS RF Transmitter Power:

NA Selection – 125 mW (20.9 dBm) maximum transmit power not including antenna per FCC/IC, or 400 mW (26.0 dBm) maximum EIRP including antenna for USA and Canadian locations.

EU Selection – 10 mW (10.0 dBm) maximum EIRP including antenna per RTTE/ETSI for EU locations.

Data:

PV Publish Cycle Time: Configurable as 1, 5, 10 or 30 seconds

Rate: 250 Kbps

Antennas: Integral – 2 dBi omnidirectional monopole
Integral – 4 dBi omnidirectional monopole
Remote – 8 dBi omnidirectional monopole with up to 20 m cable and lightning surge arrester
Remote – 14 dBi directional parabolic with up to 20 m cable and lightning surge arrester
Signal Range: Nominal 305 m (1,000 feet) between Field Transmitter and Infrastructure Unit (Multinode) or Gateway Unit when using 2 dBi Integral antenna with a clear line of sight


Main menu 2