Universal Hot Surface Ignition Module is designed to provide easy field replacement of a wide range of hot surface ignition modules manufactured by Honeywell, Robertshaw and White-Rodgers. The S8910U Module provides operating control of a direct ignition system using a 120 Vac hot surface igniter.

• Replaces many White-Rodgers, Robertshaw and Honeywell hot surface ignition models.
• For 120 Vac (up to 5.0A) surface igniter (Norton 201/271 or equivalent).
• For local (single rod) or remote (dual rod) rectification type flame sensing.
• Contains easy-to-use instructions plus the accessories required to adapt the existing hot surface ignition module.
• Provides one or three ignition trials (four-second or seven-second trials) per call for heat; prepurge of 32 seconds or less; up to 96 seconds between purge trial times.
• Temperature range is -40 to +175 F (-40 to +79 C).

Select a link under the "item" tab below to order.

Cat #Pre PurgeFlame Failure Responce Time (sec)Ignition Trial Time (sec)Between Trial Time (sec)Ignition Trials To LockoutLockout Timing
S8910U100032 seconds1.5 sec.4 sec. or 7 sec.(2) 96 sec.- 3 trial mode only1 or 34 sec. or 7 sec.
Application Provide electronic control of direct hot surface ignition systems used on gas fired furnaces, boilers, and other heating appliances
Dimensions, Approximate 5 1/4 in. high x 4 1/16 in. wide x 1 15/16 in. long (133 mm high x 103 mm wide x 49 mm deep)
Type of Gas Natural or LP
Electrical Ratings 24 Vac
Frequency 60 Hz
Flame Sense Single Rod or Two Rods
Ignition Sequence The number of trials for ignition and trial time is determined by the selection tab. If a selection tab is not installed, the module will operate at four seconds trial time and one ignition trial
Ignition Source Line Voltage (120 VAC) Hot Surface Element (Norton Model 201 or 270)
Ignition System Type Direct Hot Surface Ignition
Maximum Valve Load @ 24 Vac (Amps) 2A
Typical Gas Control VR8205, VR8305
Typical Ignition Hardware Norton 201, Norton 271, Q354
Maximum Ambient Temperature (-40 C to +79 C) -40 F to +175 F
Approvals Canadian Standards Association: Design Certified