Jump to Navigation

Honeywell RP7517 Electronic-Pneumatic Transducer

Electronic-Pneumatic Transducer
RP7517

Electronic-Pneumatic Transducers are used in electronic pneumatic control systems to convert a proportional electric output signal from a controller into a direct-acting, proportional pneumatic signal.

• Screw mounting or snap rail (models with cover).
• Factory calibrated.
• Dual barb fittings.
• High accuracy

Select a link under the "item" tab below to order.

Cat #Descriptions
RP7517A1009Electronic Pneumatic Transducer with direct action and 2 to 10 vdc input signal
RP7517A1017Electronic Pneumatic Transducer with direct action and 2 to 10 vdc input signal
RP7517B1016Electronic Pneumatic Transducer with direct action and 2 to 10 Vdc at 0.1 mA max input signal. External transformer required.
RP7517B1024Electronic Pneumatic Transducer with direct action and 2 to 10 Vdc at 0.1 mA max input signal. External transformer required.
Application: Electric to pneumatic Transducer
Action: Direct Acting
Airflow Usage: 0.025 scfm (117mL/s)
Connections: Dual barb-fittings for 1/4 in. or 5/32 in. O.D. plastic tubing
Current: 16 mA
Maximum Operating Temperature: 131 F (55 C)
Maximum Operating Pressure: 30 psi (205 kPa)
Pressure Ranges: 0 to 18 psi (0 to 125 kPa)
Nominal High End: 16 psi with 18 psi main pressure at 12 Vdc (110 kPa with 125 kPa main pressure at 12 Vdc)
Nominal Low End: 0.5 psi at 0 Vdc (3.5 kPa at 0 Vdc)
Output Pressure Range: 3 to 15 psi (21 to 103 kPa)
Humidity Ratings: 5 to 95% RH
Capacity: 0.45 scfm (211 mL/s)

 

 

 

 

 

 

 

 

 

 

 



Main menu 2