Honeywell L8124 Triple Aquastat® Relay

Honeywell
Triple Aquastat® Relay
L8124

Immersion-type controllers that combine high limit protection with low limit and circulator control in forced hydronic heating systems, including domestic hot water service.

• Immersion-type controllers that combine high limit protection with low limit and circulator control in forced hydronic heating systems.
• Provide multizone control by using a separate circulator and R845 Relay for each zone.
• Include diaphragm powerhead and Micro Switch® assembly that respond to temperature changes in boiler water.
• Mount directly to boiler.
• Select models include large transformers and extra terminals for supplying power to low voltage zone valves.
• Require 24 Vac thermostat with heat anticipator set at 0.2 A (plus current draw of gas valve on L8124E).
• TRADELINE models include tube of heat conductive compound and range stops.

Select a link under the "item" tab below to order.

ItemElectrical Ratings (burner AFL)Electrical Ratings (burner ALR)Electrical Ratings (circulator AFL)Electrical Ratings (circulator ALR)ApplicationDifferential Temperature (F)Insulation Depth (inch)Insulation Depth (mm)MountingIncludes
L8124A1007Line Voltage: 7.4 A @ 120 Vac; 3.7 A @ 240 VacLine Voltage: 44.4 A @ 120 Vac; 22.7 A @ 240 Vac3.7 A @ 240 Vac; 7.4 A @ 120 Vac22.2 A @ 240 Vac; 44.4 A @ 120 VacHigh Limit Protection, Low Limit and Circulation ControlHigh limit: 10 F fixed; low limit: 10-25 F adj.1 1/2 in.38 mmVertical3 in. insertion well
L8124A1015Line Voltage: 7.4 A @ 120 Vac; 3.7 A @ 240 VacLine Voltage: 44.4 A @ 120 Vac; 22.7 A @ 240 Vacv3.7 A @ 240 Vac; 7.4 A @ 120 Vac22.2 A @ 240 Vac; 44.4 A @ 120 VacHigh Limit Protection, Low Limit and Circulation ControlHigh limit: 10 F fixed; low limit: 10-25 F adj.3 in.76 mmVertical3 in. insertion well
L8124B1039Line Voltage: 7.4 A @ 120 Vac; 3.7 A @ 240 VacLine Voltage: 44.4 A @ 120 Vac; 22.7 A @ 240 Vac3.7 A @ 240 Vac; 7.4 A @ 120 Vac22.2 A @ 240 Vac; 44.4 A @ 120 VacTriple Aquastat Relay with High limitHigh limit: 10 F fixed; low limit: 10-25 F adj.Vertical
L8124C1003Line Voltage: 7.4 A @ 120 Vac; 3.7 A @ 240 VacLine Voltage: 44.4 A @ 120 Vac; 22.7 A @ 240 Vac3.7 A @ 240 Vac; 7.4 A @ 120 Vac22.2 A @ 240 Vac; 44.4 A @ 120 VacTriple Aquastat Relay with High limitHigh limit: 10 F fixed; low limit: 10-25 F adj.Horizontal
L8124C1102Line Voltage: 7.4 A @ 120 Vac; 3.7 A @ 240 VacLine Voltage: 44.4 A @ 120 Vac; 22.7 A @ 240 Vac3.7 A @ 240 Vac; 7.4 A @ 120 Vac22.2 A @ 240 Vac; 44.4 A @ 120 VacHigh Limit Protection, Low Limit and Circulation ControlHigh limit: 10 F fixed; low limit: 10-25 F adj.1 1/2 in. to 3 in. less well.38 mm to 76 mm less wellHorizontal
L8124E1016Line Voltage: 7.4 A @ 120 Vac; 3.7 A @ 240 VacLine Voltage: 44.4 A @ 120 Vac; 22.7 A @ 240 Vac3.7 A @ 240 Vac; 7.4 A @ 120 Vac22.7 A @ 240 Vac; 44.4 A @ 120 VacTriple Aquastat Relay with High limiHigh limit: 10 F fixed; low limit: 10-25 F adj.Vertical
L8124G1020Line Voltage: 7.4 A @ 120 Vac; 3.7 A @ 240 VacLine Voltage: 44.4 A @ 120 Vac; 22.7 A @ 240 Vac3.7 A @ 240 Vac; 7.4 A @ 120 Vac22.2 A @ 240 Vac; 44.4 A @ 120 VacTriple Aquastat Relay with High limitHigh limit: 10 F fixed; low limit: 10-25 F adj.Vertical
L8124L1011Line Voltage: 7.4 A @ 120 Vac; 3.7 A @ 240 VacLine Voltage: 44.4 A @ 120 Vac; 22.7 A @ 240 Vac3.7 A @ 240 Vac; 7.4 A @ 120 Vac22.2 A @ 240 Vac; 44.4 A @ 120 VacTriple Aquastat Relay with High limitHigh limit: 10 F fixed; low limit: 10-25 F adj.Horizontal
Dimensions, Approximate: 6 1/8 in. high x 4 3/8 in. wide x 3 1/16 in. deep (156 mm high x 111 mm wide x 78 mm deep)
Voltage: 120 Vac
Maximum Ambient Temperature: 150 F at switches, 265 F at sensing element (66 C at switches, 129 C at sensing element.)
Operating Range, High Limit: 130 F to 240 F adj. (54 C to 116 C adj.)
Operating Range, Low Limit: 110 F to 220 F adj. (43 C to 104 C adj.)
Maximum Operating Pressure: 200 psi on outside of immersion well, 100 psi on capsule if inserted directly. (1378 kPa on outside of immersion well, 690 kPa on capsule if inserted directly.)
Operating Humidity Range (% RH): 0 to 95% RH, non-condensing
Approvals:
Canadian Standards Association: File No. LR1620, Guide No. 400-E-O
Underwriters Laboratories Inc. UL Listed (models with well): File No. MP466, Guide No. MBPR; UL Component Recognized (models without well): File No. MP466, Guide No. MBPR2