Honeywell L8124 Triple Aquastat® Relay

Honeywell
Triple Aquastat® Relay
L8124

Immersion-type controllers that combine high limit protection with low limit and circulator control in forced hydronic heating systems, including domestic hot water service.

• Immersion-type controllers that combine high limit protection with low limit and circulator control in forced hydronic heating systems.
• Provide multizone control by using a separate circulator and R845 Relay for each zone.
• Include diaphragm powerhead and Micro Switch® assembly that respond to temperature changes in boiler water.
• Mount directly to boiler.
• Select models include large transformers and extra terminals for supplying power to low voltage zone valves.
• Require 24 Vac thermostat with heat anticipator set at 0.2 A (plus current draw of gas valve on L8124E).
• TRADELINE models include tube of heat conductive compound and range stops.

Select a link under the "item" tab below to order.

Cat #Application:Mounting
L8124A1007High Limit Protection, Low Limit Circulation ControlVertical
L8124A1015High Limit Protection, Low Limit Circulation ControlVertical
L8124B1039 *Triple Aquastat Relay with High limitVertical
L8124C1003Triple Aquastat Relay with High limitHorizontal
L8124C1102High Limit Protection, Low Limit Circulation ControlHorizontal
L8124E1016 **Triple Aquastat Relay with High limitVertical
L8124G1020Triple Aquastat Relay with High limitVertical
L8124L1011Triple Aquastat Relay with High limitHorizontal
Dimensions, Approximate: 6 1/8 in. high x 4 3/8 in. wide x 3 1/16 in. deep (156 mm high x 111 mm wide x 78 mm deep)
Voltage: 120 Vac
Maximum Ambient Temperature: 150 F at switches, 265 F at sensing element (66 C at switches, 129 C at sensing element.)
Operating Range, High Limit: 130 F to 240 F adj. (54 C to 116 C adj.)
Operating Range, Low Limit: 110 F to 220 F adj. (43 C to 104 C adj.)
Maximum Operating Pressure: 200 psi on outside of immersion well, 100 psi on capsule if inserted directly. (1378 kPa on outside of immersion well, 690 kPa on capsule if inserted directly.)
Operating Humidity Range (% RH): 0 to 95% RH, non-condensing
Approvals:
Canadian Standards Association: File No. LR1620, Guide No. 400-E-O
Underwriters Laboratories Inc. UL Listed (models with well): File No. MP466, Guide No. MBPR; UL Component Recognized (models without well): File No. MP466, Guide No. MBPR2