Jump to Navigation

Honeywell C7915 Infrared (Lead Sulfide) Flame sensor

Infrared (Lead Sulfide) Flame sensor
C7915

The C7915 Flame Sensor includes a lead sulfide photocell that is sensitive to the infrared radiation emitted by the combustion of fuels such as natural gas, oil, and coal.

• Used for combination or dual-fuel applications.
• Detects pilot and main flame.
• Mounts quickly and easily on a standard 3/4 in. sighting pipe.
• Works where flame rod or rectifying photocell mounts are difficult to apply.
• The C7015 includes 110634A Bushing with magnifying lens.
• The C7015 uses photoconductive lead sulfide cells 104662B and D.
• The C7915 includes 50019469-001 Bushing with magnifying lens.
• The C7915 uses photoconductive lead sulfide cells 32007255-001.

Select a link under the "item" tab below to order.

Cat #Used WithIncludesLead Length
C7915A1010Flame Amplifiers: R7852; Flame Amplifiers: R7248, R7848, R7748, R7258With magnifying lens, 32007255-001 Cell30 in.
C7915A1028Flame Amplifiers: R7852With magnifying lens, 32007255-001 Cell, Orifice, heat block, and reducer bushing48 in.
C7915A1036Flame Amplifiers: R7852With magnifying lens, 32007255-001 Cell96 in.
Description: Infrared (Lead Sulfide) Flame Detector
Application: Used for combination or dual-fuel applications
Dimensions, Approximate: 1 1/4 in. diameter x 2 3/4 in. long (32 mm diameter x 70 mm long)
Mounting: 3/4 in. NPT
Electrical Connections: Two no.18 AWG wires
Ambient Temperature Range: 125 F max at sensor (52 C max at sensor)
Type: Infrared (Lead Sulfide)
Comments: Infrared (Lead Sulfide) Flame Detector
Approvals:
Canadian Standards Association: Certified: Master Report LR95329-1
Factory Mutual: Approved: Report No. 24181.03
Underwriters Laboratories Inc. Listed: File No. MP268, Guide No.
MCCZ