Jump to Navigation

Honeywell C7061 Dynamic Self-Check Ultraviolet Flame Detector

Dynamic Self-Check Ultraviolet Flame Detector
C7061

Dynamic self-checking flame detector used with R7861 Dynamic Self-check Amplifiers for sensing the ultraviolet radiation generated by the combustion of gas, oil, or other fuels.

• Oscillating shutter interrupts ultraviolet radiation reaching the UV sensor to provide the UV sensor tube checking function.
• Can be mounted horizontally, vertically or at any angle in between.
• The detector requires faceplate alignment and has integral locating reference points to assure proper operation of the shutter mechanism.
• Field replaceable ultraviolet sensing tube and quartz viewing window.
• Models with threaded conduit fitting and color-coded leadwires allow rapid electrical installation.
• C7061A1038 or A1046 5 pin Brad Harrison type (formally 41307N) mating connector not supplied nor available through Honeywell.
• Two detectors can be wired in parallel to reduce nuisance shutdowns in difficult flame sighting applications.
• Protective heat block built into mounting flange.
• -40 F (-40 C) rated ultraviolet sensing tube is supplied.

Select a link under the "item" tab below to order.

Cat #Lead LengthMountingElectrical ConnectionsNEMA Rating
C7061A100496 in.3/4 in. NPTColor-coded lead wiresNEMA 4
C7061A101296 in.3/4 in. NPTColor-coded lead wiresNEMA 4
C7061A1020---¾ in. NPTTerminal BlockNEMA 4
C7061A10383/4 in. NPTBrad Harrison type number 41310 connectorNEMA 4
C7061A10461 in. NPTBrad Harrison type number 41310 connectorNEMA 4
C7061A105396 in.1 in. NPTColor-coded lead wiresNEMA 4
C7061M1016---1 in. NPTBrad Harrison Type 41310 ConnectorIP66
C7061F200196 in.1 in. NPTColor-coded lead wiresExplosion Proof
C7061M100896 in.1 in. NPTColor-coded lead wiresIP66
Description: Ultraviolet Flame Detector
Application: Gas fired burners; Oil fired burners
Electrical Ratings: 120 Vac
Frequency: 50 Hz; 60 Hz
Ambient Temperature Range: -40 F to +175 F (-40 C to +79 C)
Used With: Flame Amplifiers: R7861
Approvals:
Canadian Standards Association: Certified: Master Report LR95329-1
Factory Mutual: Approved: Report No. 14740.01
Underwriters Laboratories Inc. Listed: File No. MP268, Guide No. MCCZ


Main menu 2