Jump to Navigation

Honeywell C7035 Minipeeper Ultraviolet Flame Detector

Minipeeper Ultraviolet Flame Detector
C7035

Compact flame detector for use with flame safeguard controls with ultraviolet amplifiers.

• Use with Honeywell Flame Safeguard primary safety controls and burners requiring ultraviolet flame detection.
• Mounts on a 1 in. sighting pipe by using an integral collar.
• Protects the sensing tube with a shield.
• Meets outdoor rain tight requirements of Underwriters Laboratories Inc., NEMA 4 and NEMA 4X.
• Wires in parallel for difficult sighting applications.
• Seals against pressures as high as 5 psi (34.5 kPa) when correctly installed.
• Field-replaceable ultraviolet sensing tube.

Select a link under the "item" tab below to order.

Cat #Used WithIncludes(°F)(°C)(inch)(mm)
C7035A1023Flame Amplifiers: R7249A,B, R7849A, B, R7749B, R7259, R72900 °F to 250 °F-18 °C to +121 °C72 in.1829 mm
C7035A1031Flame Amplifiers: R7249A,B, R7849A, B, R7749B, R7259, R7290-40°F to +250 °F-40 °C to +121 °C72 in.1829 mm
C7035A1049Flame Amplifiers: R7249A,B, R7849A, B, R7749B, R7259, R72900 °F to 250 °F-18 °C to +121 °C72 in.1829 mm
C7035A1056Flame Amplifiers: R7249A,B, R7849A, B, R7749B, R7259, R7290-40°F to +250 °F-40 °C to +121 °C144 in.3658 mm
C7035A1064Flame Amplifiers: R7249A,B, R7849A, B, R7749B, R7259, R7290-40°F to +250 °F-40 °C to +121 °C72 in.1829 mm
C7035A1080Flame Amplifiers: R7249A,B, R7849A, B, R7749B, R7259, R7290600F leads0 °F to 250 °F-18 °C to +121 °C72 in.1829 mm
Description: Minipeeper
Application: Coal fired burners; Gas fired burners; Oil fired burners
Mounting: Integral nut for 1 in. sighting pipe
Vibration: 0.5 G max
NEMA Rating: NEMA 3 and NEMA 4
Electrical Connections: 2 NEC Class 1 leadwires
Comments: Detects ultraviolet radiation in flames
Weight: 6 oz (0.17 kg)
Approvals:
Canadian Standards Association: Certified: Master Report LR95329-1
Factory Mutual: Approved: Report No. 24181.03
Underwriters Laboratories Inc. Listed: File No. MP268, Guide No. MCCZ


Main menu 2