Jump to Navigation

Honeywell C7012 Solid State Purple Peeper® Ultraviolet Flame Detector

Solid State Purple Peeper® Ultraviolet Flame Detector
C7012

Solid state electronic flame detectors for use with Honeywell Flame Safeguard controls and amplifiers. Sense ultraviolet radiation produced by combustion of gas, oil, coal or other fuels.

• Mount horizontally, vertically or at any angle in between.
• Provide quick electrical hookup with threaded conduit fitting and color-coded leadwires.
• Reduced nuisance shutdowns by wiring two in parallel.
• C7012E1278 5 pin Brad Harrison type (formally 41307N) mating connector not supplied nor available through Honeywell.

Select a link under the "item" tab below to order.

Cat #FrequencyIncludesTypeMountingElectrical ConnectionsNEMA Rating(°F)(°C)Electrical Ratings
C7012A114550 Hz; 60 HzCast case and coverUltraviolet, Purple Peeper3/4 in. NPT4 NEC Class 1 Color-coded leadwires.NEMA 425 °F to 175 °F-4 °C to +79 °C120 Vac
C7012A115250 Hz; 60 HzCast case and coverUltraviolet, Purple Peeper1 in. NPT4 NEC Class 1 Color-coded leadwires.NEMA 425 °F to 175 °F-4 °C to +79 °C120 Vac
C7012A116050 Hz; 60 HzCast case and coverUltraviolet, Purple Peeper1 in. NPT4 NEC Class 1 Color-coded leadwires.NEMA 4-40 °F to +175 °F-40 °C to +79 °C120 Vac
C7012A118650 Hz; 60 HzCast case and coverUltraviolet, Purple Peeper3/4 in. NPT4 NEC Class 1 Color-coded leadwires.NEMA 425 °F to 175 °F-4 °C to +79 °C208 Vac
C7012A119450 Hz; 60 HzCast case and coverUltraviolet, Purple Peeper3/4 in. NPT4 NEC Class 1 Color-coded leadwires.NEMA 425 °F to 175 °F-4 °C to +79 °C240 Vac
C7012C104250 Hz; 60 HzUltraviolet, Purple Peeper1 in. NPT4 NEC Class 1 Color-coded leadwires.Explosion Proof25 °F to 175 °F-4 °C to +79 °C120 Vac
C7012E110450 Hz; 60 HzCast case and coverUltraviolet, Purple Peeper, Self-Checking3/4 in. NPT6 NEC Class 1 Color-coded leadwires.NEMA 4-20 °F to +175 °F-20 °C to +79 °C120 Vac
C7012E111250 Hz; 60 HzCast case and coverUltraviolet, Purple Peeper, Self-Checking1 in. NPT6 NEC Class 1 Color-coded leadwires.NEMA 4-20 °F to +175 °F-20 °C to +79 °C120 Vac
C7012E112050 Hz; 60 HzCast case and coverUltraviolet, Purple Peeper, Self-Checking1 in. NPT6 NEC Class 1 Color-coded leadwires.NEMA 4-40 °F to +175 °F-40 °C to +79 °C120 Vac
C7012E114650 Hz; 60 HzCast case and coverUltraviolet, Purple Peeper, Self-Checking3/4 in. NPT6 NEC Class 1 Color-coded leadwires.NEMA 4-20 °F to +175 °F-20 °C to +79 °C208 Vac
C7012E115350 Hz; 60 HzCast case and coverUltraviolet, Purple Peeper, Self-Checking3/4 in. NPT6 NEC Class 1 Color-coded leadwires.NEMA 4-20 °F to +175 °F-20 °C to +79 °C240 Vac
C7012E116150 Hz; 60 HzCast case and coverUltraviolet, Purple Peeper, Self-Checking1 in. NPT10 foot 5 conductor cable and 5 PIN connectorNEMA 4-20 °F to +175 °F-20 °C to +79 °C120 Vac
C7012E118750 HzCast case and coverUltraviolet, Purple Peeper, Self-Checking3/4 in. NPT6 NEC Class 1 Color-coded leadwires.NEMA 4-20 °F to +175 °F-20 °C to +79 °C220 Vac
C7012E119550 HzCast case and coverUltraviolet, Purple Peeper, Self-Checking3/4 in. NPT6 NEC Class 1 Color-coded leadwires.NEMA 4-20 °F to +175 °F-20 °C to +79 °C110 Vac
C7012E127850 Hz; 60 HzCast case and coverUltraviolet, Purple Peeper, Self-Checking1 in. NPTBrad Harrison type number 41310 connectorNEMA 4-20 °F to +175 °F-20 °C to +79 °C120 Vac
C7012F105250 Hz; 60 HzUltraviolet, Purple Peeper, Self-Checking1 in. NPT6 NEC Class 1 Color-coded leadwires.Explosion Proof-20 °F to +175 °F-20 °C to +79 °C120 Vac
Description: Ultraviolet Flame Detector (Purple Peeper)
Application: Gas, Oil or Coal fired burners
Lead Length for NEC Class 1 leadwires:  96 in. (2438 mm)
Approvals:
Canadian Standards Association: Certified: Master Report LR95329-1
Factory Mutual: Approved: Report No. 14740.01
Underwriters Laboratories Inc. Listed: File No. MP268, Guide No.
MCCZ