Jump to Navigation

Honeywell C6097 Pressure Switch

Pressure Switch
C6097

Pressure Switches are safety devices used in positive-pressure or differential-pressure systems to sense gas or air pressure systems.

• For use with natural gas, liquid propane (LP) gas, or air.
• Diaphragm-actuated safety-limit switch.
• Switch can be wired to turn on alarm.
• C6097A models break control circuit at setpoint on pressure fall.
• C6097B models break control circuit at setpoint on pressure rise.
• Lockout with manual reset and recycle options.
• Lockout models have external manual reset button.
• Removable transparent cover protects scaleplate and adjusting knob.
• Pipe tappings allow selection of positive pressure (air only) or venting connections (NPT mount only).
• 1/4 in. NPT or flange mount models for direct mounting to Honeywell Integrated Valve Train.
• Optional switch position indicator lamp available.
• IP54 enclosure standard.
• Ranges: 0.4 to 5 in. wc, 3 to 21 in. wc, 12 to 60 in. wc or 1.5 to 7 psi.
• Surge orifice.

Select a link under the "item" tab below to order.

Cat #MountingOperating Pressure Range (psi)Pressure Differential (psi)Switching ActionNominal Pressure Differential (psi)Switch OperationMaximum Pressure Differential (psi)
C6097A10041/4 in. NPT internal thread0.4 to 5 in. wc-Break on pressure fall0.16 in. wcAuto recycle0.24 in. wc
C6097A10121/4 in. NPT internal thread3 to 21 in. wcmax. 2.4 in. wc @ min. setpoint; max. 4.2 in. wc @ max. setpointBreak on pressure fall-Manual Reset-
C6097A1020Flange Mount3 to 21 in. wcmax. 2.4 in. wc @ min. setpoint; max. 4.2 in. wc @ max. setpointBreak on pressure fall-Manual Reset-
C6097A10381/4 in. NPT internal thread12 to 60 in. wcmax. 10 in. wc @ min. setpoint; max. 12 in. wc @ max. setpointBreak on pressure fall-Manual Reset-
C6097A1046Flange Mount12 to 60 in. wcmax. 10 in. wc @ min. setpoint; max. 12 in. wc @ max. setpointBreak on pressure fall- wcManual Reset-
C6097A10531/4 in. NPT internal thread3 to 21 in. wc-Break on pressure fall0.24 in. wcAuto recycle0.48 in. wc
C6097A1061Flange Mount3 to 21 in. wc-Break on pressure fall0.24 in. wcAuto recycle0.48 in. wc
C6097A10791/4 in. NPT internal thread12 to 60 in. wc-Break on pressure fall1.1 in. wcAuto recycle2.4 in. wc
C6097A1087Flange Mount12 to 60 in. wc-Break on pressure fall1.1 in. wcAuto recycle2.4 in. wc
C6097A10951/4 in. NPT internal thread0.4 to 5 in. wcmax. 10 in. wc @ min. setpoint; max. 12 in. wc @ max. setpointBreak on pressure fall-Manual Reset-
C6097A1103Flange Mount1.5 to 7 psimax. 1.1 in. wc @ min. setpoint; max. 1.4 in. wc @ max. setpointBreak on pressure fall-Manual Reset-
C6097A11111/4 in. NPT internal thread1.5 to 7 psimax. 1.1 in. wc @ min. setpoint; max. 1.4 in. wc @ max. setpointBreak on pressure fall-Manual Reset-
C6097A1129Flange Mount1.5 to 7 psi-Break on pressure fall0.1 psiAuto recycle0.3 psi
C6097A11371/4 in. NPT internal thread1.5 to 7 psi-Break on pressure fall0.1 psiAuto recycle0.3 psi
C6097A1210Flange Mount0.4 to 5 in. w-Break on pressure fall0.16 in. wcAuto recycle0.24 in. wc
C6097A1228Flange Mount0.4 to 5 in. wmax. 0.6 in. wc @ min. setpoint; max. 0.25 in. wc @ max. setpointBreak on pressure fall-Manual Reset-
C6097B10021/4 in. NPT internal thread12 to 60 in. wcmax. 0.6 in. wc @ min. setpoint; max. 0.25 in. wc @ max. setpointBreak on pressure rise-Manual Reset-
C6097B1010Flange Mount12 to 60 in. wcmax. 10 in. wc @ min. setpoint; max. 12 in. wc @ max. setpointBreak on pressure rise-Manual Reset-
C6097B10281/4 in. NPT internal thread3 to 21 in. wcmax. 2.4 in. wc @ min. setpoint; max. 4.2 in. wc @ max. setpointBreak on pressure rise-Manual Reset-
C6097B1036Flange Mount3 to 21 in. wcmax. 2.4 in. wc @ min. setpoint; max. 4.2 in. wc @ max. setpointBreak on pressure rise-Manual Reset-
C6097B1044Flange Mount1.5 to 7 psimax. 1.1 in. wc @ min. setpoint; max. 1.4 in. wc @ max. setpointBreak on pressure rise-Manual Reset-
C6097B10511/4 in. NPT internal thread1.5 to 7 psimax. 1.1 in. wc @ min. setpoint; max. 1.4 in. wc @ max. setpointBreak on pressure rise- wcManual Reset-
C6097B1069Flange Mount3 to 21 in. wc-Break on pressure rise0.24 in. wcAuto recycle0.48 in. wc
C6097B1077Flange Mount12 to 60 in. wc-Break on pressure rise1.1 in. wcAuto recycle2.4 in. wc
C6097B10851/4 in. NPT internal thread12 to 60 in. wc-Break on pressure rise1.1 in. wcAuto recycle2.4 in. wc
C6097B1093Flange Mount1.5 to 7 psi-Break on pressure rise0.1 psiAuto recycle0.3 psi
C6097B11011/4 in. NPT internal thread1.5 to 7 psi-Break on pressure rise0.1 psiAuto recycle0.3 psi
C6097B11191/4 in. NPT internal thread3 to 21 in. wc-Break on pressure rise0.24 in. wcAuto recycle0.48 in. wc
Application Safety devices used in positive-pressure or differential pressure systems to sense gas or air pressure changes
Pipe Connections, Vent or Low pressure  1/8 in. NPT internal thread
Alternate Ratings Ignition Transformer: 540 VA, Pilot Valve: 50 VA. Main Valve: 400 VA with 2-1/2 times inrush
Electrical Connections Screw terminals
Differential Type Additive
Switch Contact Ratings 3.0 AFL, 18.0 ALR, 5.0 A resistive (120 Vac);
3.0 AFL, 18.0 ALR, 5.0 A resistive (240 Vac)
Switch Contact Ratings (120 Vac) 8.0 AFL, 48.0 ALR, 10.0 A resistive
(120 Vdc) 2.0 AFL, 20.0 ALR, 8.0 A resistive
(240 Vac) 5.1 AFL, 30.6 ALR, 5.0 A resistive
(240 Vdc) 1.0 AFL, 10.0 ALR, 4.0 A resistive
Temperature Range -40 F to +140 F (-40 C to +60 C)
Approvals
Canadian Standards Association Certified
Factory Mutual Approved
Underwriters Laboratories Inc. Listed Component Listed
Others CSD-1 AFB: Acceptable